Table 2.
Pipe equivalent lengths
Equivalent Length (ft) of Straight Pipe
O.D.
(in.) Line
Size
Globe
Valve
Angle
Valve
90º Elbow
45º Elbow
Tee Line
Tee Branch
1/2
9.0
5.0
0.9
0.4
0.6
2.0
5/8
12.0
6.0
1.0
0.5
0.8
2.5
7/8
15.0
8.0
1.5
0.7
1.0
3.5
1 1/8
22.0
12.0
1.8
0.9
1.5
4.5
1 3/8
28.0
15.0
2.4
1.2
1.8
6.0
Installation
18
AH-SVX008C-EN
Oil traps must be included every 20 ft in the vertical risers
and the refrigerant lines must be sloped in the horizontal
lines to ensure proper oil return to the compressor. An
inverted trap is required on the discharge line of the
remote condenser to help prevent oil and liquid from
flooding back to the compressor.
Notes:
In the following tables:
•
The line sizes represent the correct size for individual
refrigeration circuits. Dual circuit units, (models 048D
to 120D), have two separate pairs of refrigeration lines,
one per compressor.
•
All pipe lengths are "Equivalent Length," which
accounts for the linear pipe length as well as
equivalent length of valves, elbows and Tee's as
shown in
.
Table 3.
Recommended discharge line sizes for R407C
refrigerant
Model No./
Total Btu/h
Capacity
Compressor to Condenser O.D. (in.)
50 ft
or less
100 ft
or less
150 ft
or less
012/12,000
1/2
5/8
5/8
018/18,000
1/2
5/8
5/8
024/24,000
5/8
5/8
3/4
032/32,000
5/8
3/4
3/4
040/40,000
3/4
3/4
7/8
048/48,000
3/4
7/8
7/8
048D/48,000
5/8
5/8
3/4
060/60,000
3/4
7/8
1-1/8
072D/72,000
5/8
3/4
3/4
084D/84,000
3/4
7/8
7/8
120D/120,000
3/4
7/8
1-1/8
Table 4.
Recommended liquid line sizes for R407C
refrigerant (condenser to receiver)
Model No./
Total Btu/h
Capacity
Compressor to Condenser O.D. (in.)
50 ft
or less
100 ft
or less
150 ft
or less
012/12,000
1/2
1/2
1/2
018/18,000
1/2
1/2
1/2
024/24,000
1/2
5/8
5/8
032/32,000
1/2
5/8
5/8
040/ 40,000
5/8
5/8
5/8
048/48,000
5/8
5/8
3/4
048D/48,000
1/2
1/2
5/8
060/60,000
5/8
3/4
3/4
072D/72,000
1/2
5/8
5/8
084D/84,000
5/8
5/8
3/4
120D/120,000
5/8
3/4
3/4
Table 5.
Recommended suction line sizes for R407C
refrigerant
Model No./
Total Btu/h
Capacity
Line O.D. (in.)
50 ft
or less
100 ft
or less
H
V
H
V
012 / 12,000
3/4
3/4
3/4
3/4
018 / 18,000
3/4
3/4
3/4
3/4
024 / 24,000
3/4
3/4
7/8
7/8
032 / 32,000
7/8
7/8
7/8
3/4
040 / 40,000
7/8
7/8
1-1/8
1-1/8
048 / 48,000
1-1/8
1-1/8
1-1/8
1-1/8
048D / 48,000
3/4
3/4
7/8
7/8
060 / 60,000
1-1/8
1-1/8
1-1/8
1-1/8
072D / 72,000
7/8
7/8
7/8
3/4
084D /84,000
1-1/8
1-1/8
1-1/8
1-1/8