Commissioning, Operation and Decommissioning
38
AH-SVX008C-EN
•
If compressors or compressor oils are to be removed,
ensure they have been evacuated to an acceptable
level to make certain flammable refrigerant does not
remain within the lubricant. The evacuation process
must be carried out prior to returning the compressor
to the suppliers. Only electric heating of the
compressor body can be employed to accelerate this
process. When oil is drained from a system, it must be
carried out safely.
Labeling Decommissioned Equipment
Equipment must be labelled stating that it has been de-
commissioned and emptied of refrigerant. The label must
be dated and signed. Ensure that there are labels on the
equipment stating the equipment contains flammable
refrigerant.