26
Pre-Start-up
Auto:
(
135
)
0
Need manual start-up (by default) when powering on
1
Allow automatic start-up (in case of power-down in running state) when powering on
Defrost:
(
136, only single unit controller
)
0
“
Manual defrosting
”
disabled (by default)
1
“
Manual defrosting
”
enabled
Flow :
(
133
)
0
“
Water flow switch mode
”
disabled (by default)
1
“
Water flow switch mode
”
enabled (if the switch is still closed within 30 seconds after the
water pump is stopped, the alarm will be issued)
Temp:
(
134
)
0
“
Suction temperature
”
enabled
1
“
Suction temperature
”
disabled
DIP Switch Setting (H Type Unit)
Definition of SW1 Functions
Bit1
Bit2
Bit3
Bit4
Bit5
Bit6
Bit7
Bit8
Modular IP
Type
EnSave
Control
The bits 1-5 of this switch is used for the centralized control of address coding. (Note: 00 must be
set for the host unit of this modular unit.)
SW1: centralized control of address setting
Number
SW1 Switch
1
2
3
4
5
0 (the centralized controller displays A0)
OFF
OFF
OFF
OFF
OFF
1 (the centralized controller displays A1)
ON
OFF
OFF
OFF
OFF
2 (the centralized controller displays A2)
OFF
ON
OFF
OFF
OFF
3 (the centralized controller displays A3)
ON
ON
OFF
OFF
OFF
4 (the centralized controller displays A4)
OFF
OFF
ON
OFF
OFF
5 (the centralized controller displays A5)
ON
OFF
ON
OFF
OFF
6 (the centralized controller displays A6)
OFF
ON
ON
OFF
OFF
7 (the centralized controller displays A7)
ON
ON
ON
OFF
OFF
8 (the centralized controller displays A8)
OFF
OFF
OFF
ON
OFF
9 (the centralized controller displays A9)
ON
OFF
OFF
ON
OFF
10 (the centralized controller displays AA)
OFF
ON
OFF
ON
OFF
11 (the centralized controller displays AB)
ON
ON
OFF
ON
OFF
12 (the centralized controller displays AC)
OFF
OFF
ON
ON
OFF
13 (the centralized controller displays AD)
ON
OFF
ON
ON
OFF
14 (the centralized controller displays AE)
OFF
ON
ON
ON
OFF
15 (the centralized controller displays AF)
ON
ON
ON
ON
OFF
16 (the centralized controller displays B0)
OFF
OFF
OFF
OFF
ON