28
Pre-Start-up
Default Switch Setting
N Type
Mode
SW1
Bit1
Bit2
Bit3
Bit4
Bit5
Bit6
Bit7
Bit8
Modular IP
Void
Void
Void
All
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Mode
SW2
Bit1
Bit2
Bit3
Bit4
Bit5
Bit6
Bit7
Bit8
MODE
C/H
FAN
TYPE
ENSAVE CONTROL
CXAJ045/065
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
CXAJ045/065
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
CXAJ130
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
CGAJ130
OFF
OFF
OFF
ON
ON
ON
OFF
OFF
Bit1-5 of SW1, Bit8 of SW2 need adjust by actual jobsite
H Type
Mode
SW1
Bit1
Bit2
Bit3
Bit4
Bit5
Bit6
Bit7
Bit8
Modular IP
Type
En-Save
Control
CXAJ045/065 /130
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
CXAJ045/065 /130
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
Bit1-5 and Bit8 of SW1 need adjust by actual jobsite
Operating Parameter Setting
The unit protection parameters and the operating parameters can be set in the shutdown mode
through the Single Unit Controller. The set values of the default parameters are shown in the
table below.
Code of Single Unit
Controller / Centralized
Controller
Parameter Setting
Maximum Minimum Regulation
Precision
Factory
Setting
016
Set temperature for
COOLING mode
25
℃
5
℃
1
℃
12
℃
017
Set temperature for
HEATING mode
50
℃
25
℃
1
℃
40
℃
022
Anti-freezing temperature
in winter
5
℃
1
℃
1
℃
3
℃
001
Defrosting interval
90min
30min
1min
45min
002
Minimum defrosting time
8min
1min
1min
3min
Password input range
75
50
-
50
For N Type unit
:
setting temperature of cooling should above 10
℃
,
or will has E3 alarm.