background image

9

11

UNT-PRC002-GB

Sound power levels

Discharge

Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.

Fan

Power level in dB(A), per Hz frequency band

Overall power

Unit

speed

125

250

500

1000

2000

4000

8000

dB(A)

1

55

50

42

37

37

31

30

46

FWD 08

2

57

54

47

40

30

38

40

50

3

58

57

50

42

32

40

43

53

1

57

51

45

42

34

33

28

48

FWD 10

2

58

54

48

45

38

39

35

51

3

60

58

50

48

40

42

39

54

1

57

51

45

42

34

33

28

48

FWD 12

2

58

54

48

45

38

39

35

51

3

60

58

50

48

40

42

39

54

1

56

62

50

48

39

38

36

56

FWD 14

2

61

66

55

53

47

46

45

60

3

63

69

58

56

50

50

49

63

1

57

63

51

49

40

39

37

57

FWD 20

2

61

66

55

53

47

46

45

60

3

63

69

58

56

50

50

49

63

Intake

Measurement conditions:
Measurements taken at the horizontal air intake.

Fan

Power level in dB(A), per Hz frequency band

Overall power

Unit

speed

125

250

500

1000

2000

4000

8000

dB(A)

1

56

55

55

53

46

45

42

57

FWD 08

2

63

62

60

60

53

53

53

64

3

66

65

63

62

56

55

57

67

1

62

58

55

58

51

48

44

61

FWD 10

2

66

63

60

62

56

55

52

66

3

70

67

63

65

59

59

57

69

1

62

58

55

58

51

48

44

61

FWD 12

2

66

63

60

62

56

55

52

66

3

70

67

63

65

59

59

57

69

1

66

65

65

65

57

50

46

68

FWD 14

2

73

72

69

71

64

59

57

74

3

78

76

73

75

69

64

63

78

1

68

72

64

64

56

52

50

69

FWD 20

2

76

76

68

71

65

61

61

75

3

78

79

71

74

69

66

66

78

AH-SVX03C-GB

CAUTION!

 Never lift the units by the heat exchanger connections or by any other projections. Do not tilt the fan 

module to avoid possible impingement on the dampers. 
Sections will be delivered with a base frame equipped with wooden blocks positioned on each corner. To remove 
the wooden blocks, the unit must be lifted from the ground, providing access to the screws. Damper movement is 
factory-tested. At unit reception, carefully check that dampers move freely. Refer to the "Reception" paragraph if there 
is a problem. Trane will not assume responsibility for damper movement after reception of the unit.
If a section is provided on a base frame without any fork holes or without feet, insert the fork of the lift below the 
section lifting it by a lever action. In this case, the bar must only bear against the base frame or profile (see Figure 2). 
Use the same instructions to extract forks or belts.
With larger units, the use of several forklifts may be required.
When rigging the unit by crane, follow these guidelines:
1.  If lifting holes are provided on the unit base frame, always use sling spreader bars (see Figure 1).
2.  If lifting points (eye bolts) are provided, crane belts can be connected directly to them. In this case, after handling 

and positioning, replace the eye bolt with bolts to avoid injury (see Figure 1).

3.  The minimum rated lifting capacity (vertical) of each sling and spreader bar should be no less than the shipping 

weight.

4.  The unit must be lifted with care, avoiding shock load by lifting the unit slowly and evenly.
5.  All lifting points in one axis of the unit must be used when offloading and moving the unit.
6.  Belts are to be provided by the rigger and attached to all lifting points.

CAUTION!

 Loading, unloading and removal of single sections have to be carried out by employing means able to 

support the unit weight indicated in the technical sheet. Ensure that the belts do not damage the top surface of the 
unit structure using proper devices.
When the unit is provided with an outdoor protection roof, reinforcement parts may have been added in the factory 
to avoid damage during transport. Remove the reinforcement parts after unloading.

Storage

In case of external storage, units must be protected from adverse weather conditions. Make sure that air ventilation 
and recirculation between the protective film wrapping and the section is warrented. 
A protective wax can be applied to the unit casing to avoid corrosion due to condensate which can form between the 
film and the casing. Remove it using paper and a heptane-based solvent, taking care to not damage the paint and the 
profile.
With internal and external storage, the unit must also be protected against damage. 
To avoid damage to the bearings, the motor and fans should be rotated once a month. 
If the units do not operate for more than 18 months, the grease in the bearings must be changed. For long term 
storage, all electrical equipment and accessories delivered separately in a box (filters, humidifiers, etc) and fan belts 
must be removed and stored in a dry atmosphere. The unit shall be electrically grounded.

Unit assembly

When selecting and preparing the unit site, follow these guidelines:
1.  Ensure that the site can support the total weight of the unit. Unit weight figures only provide total gross weights 

and do not include the additional weight for water in coils and humidifiers.

2.  Confirm that the foundation of the mounting platform is large enough to include the unit dimensions plus a safe 

service access including anti-fall protection.

3.  The floor or foundation must be level for correct assembly, coil drainage and condensate flow.
4.  Provide adequate lighting for maintenance personnel to perform maintenance duties.
5.  Provide sufficient clearance around the unit for correct installation of drain, overflow tubes, and for coil removal. 

Clearance should also be allowed around the unit to ensure that correct operation and effective and safe 
maintenance can be carried out.

6.  If the unit has more that one section, ensure that all the air-handling unit sections are positioned in the correct 

order, as indicated in the drawings. 

7.  Adjoining sections must be perfectly aligned in height and depth. If necessary, minor corrections may be made 

using steel sheet pieces as underlay.

Installation

Summary of Contents for CLCF Climate Changer

Page 1: ...AH SVX03C GB CLCF Climate Changer Air Handling Units February 2021 Confidential and proprietaryTrane information Original instructions ...

Page 2: ... 450 650 Shipped unit dimensions Width x Depth mm 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333 1133 Height mm 260 310 360 460 660 Weight kg 32 46 61 76 118 Colour galvanised steel Recommended fuse size Unit alone aM gI A 8 16 8 16 8 16 8 25 8 25 Unit with electric heater gI A 16 2kW 25 4kW 40 230V 3 16 400V 3 20 3 25 3 25 1 Conditions Water entering leaving temperature 7 12 C Air inlet tempera...

Page 3: ...at the horizontal air intake Fan Power level in dB A per Hz frequency band Overall power Unit speed 125 250 500 1000 2000 4000 8000 dB A 1 56 55 55 53 46 45 42 57 FWD 08 2 63 62 60 60 53 53 53 64 3 66 65 63 62 56 55 57 67 1 62 58 55 58 51 48 44 61 FWD 10 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 62 58 55 58 51 48 44 61 FWD 12 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 66 65 ...

Page 4: ...instructions are given as a guide to good practice in the installation start up operation and maintenance by the user ofTrane CLCF Air Handling Units They do not contain full service procedures necessary for the continued successful operation of this equipment The services of a qualified technician should be employed through the medium of a maintenance contract with a reputable service company Rea...

Page 5: ...nel 5 For inspection on the Air Handling Units and to avoid risks the units surroundings are to be sufficiently lighted 6 Any components which contain refrigerant shall be handled only by Authorized personnel The refrigerant shall be always recovered before any intervention on such component or before the end of life of equipment The recovered refrigerant shall be disposed accordingly Any componen...

Page 6: ... refrigerant with a temperature below than 2 C The unit controls should be designed in order to protect the exchanger against freezing Trane cannot be held responsible for damages coming from freezing de freezing operation Electrical motors Electrical motors are factory tested and properly run when leaving the factory Any wiring faults on motors will cause damage for whichTrane cannot be held resp...

Page 7: ... 57 69 1 66 65 65 65 57 50 46 68 FWD 14 2 73 72 69 71 64 59 57 74 3 78 76 73 75 69 64 63 78 1 68 72 64 64 56 52 50 69 FWD 20 2 76 76 68 71 65 61 61 75 3 78 79 71 74 69 66 66 78 AH SVX03C GB Maintenance contract It is strongly recommended that you sign a maintenance contract with your local Service Agency This contract providesTrane regular maintenance of your installation by a specialist in our eq...

Page 8: ...eater gI A 16 2kW 25 4kW 40 230V 3 16 400V 3 20 3 25 3 25 1 Conditions Water entering leaving temperature 7 12 C Air inlet temperature 27 19 C DB WB Nominal air flow 2 Conditions Water entering leaving temperature 50 45 C Air inlet temperature 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5...

Page 9: ...pacity vertical of each sling and spreader bar should be no less than the shipping weight 4 The unit must be lifted with care avoiding shock load by lifting the unit slowly and evenly 5 All lifting points in one axis of the unit must be used when offloading and moving the unit 6 Belts are to be provided by the rigger and attached to all lifting points CAUTION Loading unloading and removal of singl...

Page 10: ...the presence of an electrical cabinet for instance one of the following junction systems can be used depending on the unit configuration On the casing nylon or aluminium angles are positioned on the inside or outside of each section Pull together the unit sections ensuring that the nylon or aluminium angles fit with the angles of the adjoining section Secure the assembly with bolts If a technical ...

Page 11: ...f protrudes 20 mm on each side of the unit 4 Panel 5 Factory installed gasket to be covered by a layer of Silicone not supplied byTrane for outdoor installation Figure 4 Fixing of the unit Remove the mounting vibrator blocks before starting the unit They are just used to ensure safe transportation To minimize noise transmission depending on the site location additional insulation material such as ...

Page 12: ...5 Unit with electric heater gI A 16 2kW 25 4kW 40 230V 3 16 400V 3 20 3 25 3 25 1 Conditions Water entering leaving temperature 7 12 C Air inlet temperature 27 19 C DB WB Nominal air flow 2 Conditions Water entering leaving temperature 50 45 C Air inlet temperature 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C...

Page 13: ...ower level in dB A per Hz frequency band Overall power Unit speed 125 250 500 1000 2000 4000 8000 dB A 1 56 55 55 53 46 45 42 57 FWD 08 2 63 62 60 60 53 53 53 64 3 66 65 63 62 56 55 57 67 1 62 58 55 58 51 48 44 61 FWD 10 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 62 58 55 58 51 48 44 61 FWD 12 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 66 65 65 65 57 50 46 68 FWD 14 2 73 72 6...

Page 14: ...ee To avoid noise transmission the fitting of an intermediate flexible connection of at least 140 mm depth between duct work and the unit is recommended This should be unstressed when initially positioned To ensure the best possible performance of the units whilst avoiding excessive pressure loss in the duct system and minimizing air stream noise compliance with good practice in duct assembly and ...

Page 15: ... ground the unit use a bolt already on the unit or screw it onto the base The operator safety can be ensured by either a belt guard or a factory mounted micro switch on the fan section door The electrical connection of this micro switch made by the contactor will cut off the electrical feeding to the motor and stop the fan motor group when the door of the fan section is opened Motor connection As ...

Page 16: ...teel Recommended fuse size Unit alone aM gI A 8 16 8 16 8 16 8 25 8 25 Unit with electric heater gI A 16 2kW 25 4kW 40 230V 3 16 400V 3 20 3 25 3 25 1 Conditions Water entering leaving temperature 7 12 C Air inlet temperature 27 19 C DB WB Nominal air flow 2 Conditions Water entering leaving temperature 50 45 C Air inlet temperature 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 ...

Page 17: ...e access To access the Frostat frame if present it is necessary to remove the small side panel provided with a handle see Figure 10 Remove the black gasket placed around the frostat frame Remove the screws that fix the panel Using the handle remove the frostat panel Access the frostat frame sliding it on the side of the unit Figure 10 Frostat frame access 1 Panel gasket 2 Screws 3 Frostat panel wi...

Page 18: ...inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The measurement is taken in the room containing the blower unit Heat exchanger operating limits FWD water temperature max 100 C absolute service pressure min 1 bar max 11 bars Accessories Hot water coil water temperature min 2 C max 100 C absolute service pressure min 1 bar max 11 bars AH S...

Page 19: ...igures 14 17 it is important to note that 1 The cooling coil sections and the evaporative or honeycomb humidifier sections without recirculating pump are equipped with a condensate drain pipe Item 1 Figure 14 A B 2 For evaporative humidifier sections equipped with are circulation pump the drain pipe used typically for cleaning purposes item 3 Figure 16 A B needs to be connected to a shut off valve...

Page 20: ...aving temperature 7 12 C Air inlet temperature 27 19 C DB WB Nominal air flow 2 Conditions Water entering leaving temperature 50 45 C Air inlet temperature 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The measurement is take...

Page 21: ...2 61 66 55 53 47 46 45 60 3 63 69 58 56 50 50 49 63 Intake Measurement conditions Measurements taken at the horizontal air intake Fan Power level in dB A per Hz frequency band Overall power Unit speed 125 250 500 1000 2000 4000 8000 dB A 1 56 55 55 53 46 45 42 57 FWD 08 2 63 62 60 60 53 53 53 64 3 66 65 63 62 56 55 57 67 1 62 58 55 58 51 48 44 61 FWD 10 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 5...

Page 22: ...absolute service pressure min 1 bar max 11 bars AH SVX03C GB Figure 18 Figure 19 Pre start checklist Initially the complete unit and all components should be thoroughly cleaned and all dust and other deposits completely removed The unit must be maintained in a clean condition Prior to dispatch each unit is thoroughly checked Nevertheless as part of the commissioning procedure it is imperative to r...

Page 23: ...erter settings vibration excessive noise lower efficiencies motor overheating If the inverter is removed and the mechanical issues do not persist the inverter settings must be reconfigured Inverter settings to verify can include attenuated resonance quadratic torque frequency regulation etc Unit connections All electrical water and duct work connections of the unit must be completed by a qualified...

Page 24: ...that the entering air side of the filter is exposed to the contaminated air stream Refer to the certified submittals which maybe different If roll filters are used check that the filter unit drive motor and the switch control are working correctly Humidifiers The evaporative humidifiers with or without recirculating pump are provided with a water flow control valve During fan operation with the do...

Page 25: ...ease the air volume by changing or adjusting the belt drive pulleys Please contact your localTrane sales office to get a proper belt drive selection CAUTION Do not increase the fan speed beyond the motor power rating allowed limit CAUTION Increasing the fan speed should be done only after a careful study of the operating point on the appropriate fan curve Contact your localTrane sales office for a...

Page 26: ...s Hot water coil water temperature min 2 C max 100 C absolute service pressure min 1 bar max 11 bars AH SVX03C GB The regulating valve in the pressure side must be adjusted to the correct water quantity The water purging volume should be roughly equivalent to the amount of water evaporated from the system On request we will advise you in choosing the suitable volume Check the correct setting with ...

Page 27: ... Module Plus can be selected This includes all the standard CCM features with the addition of Power Wiring A Starter Panel and the installation of a Free Issued Controller compatible with the BMS is to be installed If a different control is installed please refer to its user guide or manual Shipping The controls enclosure will normally be factory fitted on the fan section of the air handling unit ...

Page 28: ...ned cable to the control panel One pair supplies power to the device and the other is the pressure signal from the device to the controller Outside temperature sensor The outside temperature sensor should be mounted on a Northfacing wall It requires a single pair of screened wires The sensor can be factory mounted in the fresh air inlet Other items are supplied loose on a project specific basis an...

Page 29: ...mpressor start or run capacitors to discharge ForTrane provided variable frequency drives wait 20 minutes For other manufacturer s variable frequency drives or energy storing components refer to the appropriate manufacturer s literature for allowable waiting periods for discharge of capacitors Verify with an appropriate voltmeter that all capacitors are discharged Failure to disconnect power and o...

Page 30: ... temperature 50 45 C Air inlet temperature 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The measurement is taken in the room containing the blower unit Heat exchanger operating limits FWD water temperature max 100 C absolute...

Page 31: ...ponsibility for system cleaning Fan and motor Long term storage 3 months of a fan motor assembly may cause damage to the bearings brinelling in case of long term storage it is necessary to turn the fan wheel from time to time Every six months Check for soiling damage corrosion and any tendency to bind and clean as necessary Touch up any spot damage to the unit casing and the fan impeller using a z...

Page 32: ... fuse size Unit alone aM gI A 8 16 8 16 8 16 8 25 8 25 Unit with electric heater gI A 16 2kW 25 4kW 40 230V 3 16 400V 3 20 3 25 3 25 1 Conditions Water entering leaving temperature 7 12 C Air inlet temperature 27 19 C DB WB Nominal air flow 2 Conditions Water entering leaving temperature 50 45 C Air inlet temperature 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering l...

Page 33: ...3 66 65 63 62 56 55 57 67 1 62 58 55 58 51 48 44 61 FWD 10 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 62 58 55 58 51 48 44 61 FWD 12 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 66 65 65 65 57 50 46 68 FWD 14 2 73 72 69 71 64 59 57 74 3 78 76 73 75 69 64 63 78 1 68 72 64 64 56 52 50 69 FWD 20 2 76 76 68 71 65 61 61 75 3 78 79 71 74 69 66 66 78 AH SVX03C GB Belt tensioning The t...

Page 34: ...s recommended to use a metal ruler instead of a string Correct position is showed on Figure 24 Figure 24 Pulley alignment Pulley removal Pulleys are generally mounted with a conic joint To remove pulleys follow the manufacturer s directions Pulleys not provided with a conic joint are mounted by forcing them onto the shaft To remove them heat the pulley hub and use a pulley extractor Belt replaceme...

Page 35: ...ume and performance change WARNING If a damper or intake discharge hole is positioned on the bottom panel and the section is equipped with inspection access safety devices must be provided to cover the damper hole when entering in the section Note It is recommended to install the gauge or the differential pressure switch if necessary with a visible indicating light to have a constant control over ...

Page 36: ...orrectly and that the water level is correct Adjust as necessary Depending upon the extent of water contamination the degree of hardness and water treatment any scale deposits or other impurities must be cleaned off from the air washers Any severe calcium deposits on components such as spray pipes droplet separators or strainers indicate that the treatment is inadequate Deposits on spray pipes str...

Page 37: ... deposits must be removed Make sure the bypass damper if any is operating properly If a bypass damper is fitted maintain as suggested in above Dampers section Heat wheel Refer to the manufacturer s instructions for proper maintenance of the wheel wheel drive and motor The construction of the matrix is such that it is virtually completely self cleaning The rotor may be cleaned with pressurised air ...

Page 38: ...0 45 C Air inlet temperature 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The measurement is taken in the room containing the blower unit Heat exchanger operating limits FWD water temperature max 100 C absolute service press...

Page 39: ... 50 48 39 38 36 56 FWD 14 2 61 66 55 53 47 46 45 60 3 63 69 58 56 50 50 49 63 1 57 63 51 49 40 39 37 57 FWD 20 2 61 66 55 53 47 46 45 60 3 63 69 58 56 50 50 49 63 Intake Measurement conditions Measurements taken at the horizontal air intake Fan Power level in dB A per Hz frequency band Overall power Unit speed 125 250 500 1000 2000 4000 8000 dB A 1 56 55 55 53 46 45 42 57 FWD 08 2 63 62 60 60 53 5...

Page 40: ...rmation please visit trane com or tranetechnologies com Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice We are committed to using environmentally conscious print practices 2021Trane AH SVX03C GB February 2021 Supersedes AH SVX03B_0114 Confidential and proprietaryTrane information ...

Reviews: