CLCH-SVX06A-EN •
T-Series Climate Changer Air Handler IOM
41
Installation-Mechanical
Unit Isolation
Review the mechanical specifications and determine the type of isolation to be used prior
to removing the shipping tie-downs. Remove the tie-downs only if the factory-provided
isolation is to be used.
Internal Isolation
The T-Series air handler fan section is internally isolated. The unit ships with the internal
isolation base secured to prevent damage to the fan and motor assembly during
shipment. To activate the isolation, remove the shipping tie-down blocks. Retain these
blocks for use in adjusting isolators if necessary.
Shipping Tie-down Removal
There are four types of shipping tie-downs used to secure the isolation base:
•
Sizes 3 - 8 use a 3/8-inch x1-inch pipe. See
Figure 27
.
•
Sizes 10 - 30, except plug fans, use washers with a bolt. See
Figure 27
.
•
Sizes 35 - 50, except plug fans, use a tie-down bolt and shim. See
Figure 27
.
•
Size 66 -100 and plug fans use a tie-down angle and bolt. See
Figure 28
.
Figure 27.
Isolator tie-down removal for unit
sizes 3-57
Figure 28. Isolator tie-down removal for unit sizes 66 to 120
and plenum fans
Remove the shipping tie-downs per the following instructions:
•
Shipping tie-downs are located at each corner of the
isolation base. Access for removal of shipping spacer is
available through the fan section access doors.
•
Remove the bolt. This will release the isolator and make it
possible to remove the pipe or spacer.
Unit sizes 3 to 8
Unit sizes 10 to 57
Isolator spring
Remove tie down
bolt and washers
and discard.
Remove tie down
angle and discard.
Angle, isolator
tie-down (4 required)
Screw (4 per angle)
lockwasher and hex nut