CLCH-SVX06A-EN •
T-Series Climate Changer Air Handler IOM
47
Installation-Mechanical
Damper Section
Standard damper sections include mixing sections, filter mixing sections, face damper sections,
internal face and bypass sections, and economizer sections.
There are two damper blade
configurations available: parallel-blade and opposed-blade. Traq™ dampers are another
type of damper available in mixing box section.
Duct work attached to the standard damper sections should be sized to fit the opening of the
damper. This information is provided in the submittals. When using lined duct, ensure that the
insulation does not obstruct the damper opening. See
Figure 33
and
Figure 34
.
Discharge Plenum
Discharge plenum sections are available with or without openings. Sections with
openings have a framed opening that can be used to secure the duct to the frames. If the
duct is lined, it is important the insulation does not obstruct the opening of the section.
For a discharge plenum with field-cut openings, attach the duct to the side panel.
Figure 33. Typical section with duct flat/flange
connections - uninsulated
Figure 34. Typical section with duct flat/flange
connections - insulated
Uninsulated Duct
Airflow
Section
Flat Connection
Section
Flat Connection
Airflow
Insulated Duct