48
T-Series Climate Changer Air Handler IOM •
CLCH-SVX06A-EN
Installation-Mechanical
Traq Damper
Size the duct connections to attach to the specified portion on the face of the Traq damper
section.
For a mitered corner, provide one hydraulic duct diameter between the entering face of
the Traq dampers and the duct turn. For a radius elbow, or sweep, place the elbow directly
against the face of the Traq dampers (see
Figure 35
).
Miscellaneous Sections
Miscellaneous sections include access sections, coil sections, fan sections and intake
sections. If the duct is lined, it is important that the insulation does not obstruct the
opening of the section.
Internal Face-and-Bypass
Duct connections for internal face-and-bypass damper sections are similar to the
miscellaneous sections. Duct work can be attached directly to this frame.
Figure 35. Traq damper duct connections
Traq damper
mixing box
H
W
d
Inlet duct
Mitered
corner
Traq damper
mixing box
Radius elbow
(sweep)
Mitered
corner
Mitered
corner
d = 1 hydraulic duct diameter = 2 x W x H
W+H