Controls Interface
The portable operator display is used for temporary connection to and operation of
Tracer MP580/581 and AH540/541 controllers. With the portable operator display, you
can monitor data, change setpoints, monitor alarms, and override points. The portable
operator display includes a 10 ft (3 m) cable with connector that is stored in the storage
compartment of the carrying bag. The cable cannot be disconnected from the operator
display. Keep this document with the portable operator display for access to calibration
and cleaning instructions.
Note: The portable operator display is not used for timeclock scheduling. To provide
scheduling you must use a Tracer Summit system.
Connecting the operator display
To connect the portable operator display:
1.
Open the controller enclosure door.
2. Attach the operator-display cable to the operator-display connector on the controller
circuit board.
The operator display receives power from the controller and turns on
automatically when it is connected to the controller.
Setting up the operator display
CAUTION
Equipment Damage!
To clean the operator display, use a cloth dampened with commercial liquid glass
cleaner. Spraying water or cleansers directly on the screen may result in equipment
damage.
This section shows how to calibrate the operator display touch screen and how to adjust
the brightness and contrast. To set up the operator display screens and security, see the
Tracer MP580/ 581 Programmable Controller Programming guide (CNT-SVP01B-EN).