CVGF-SVU02B-E4
29
Unit Control
Panel (UCP)
Reference
Top Level Mode
Sub Level Mode
BAS Code
SYSTEM RESET
NA
Stopped
Local Stop
00
Stopped
Panic Stop
00
Stopped
Diagnostic Shutdown – Manual Reset
00
Run Inhibit
Tracer Inhibit
100
Run Inhibit
External Source Inhibit
100
Run Inhibit
Diagnostic Shutdown – Auto Reset
100
Auto
Waiting For Evaporator Water Flow
58
Auto
Waiting For A Need To Cool
58
Auto
Waiting For A Need To Heat
58
Auto
Power Up Delay Inhibit: MIN:SEC
58
Waiting To Start
Waiting For Condenser Water Flow
70
Waiting To Start
Establishing Oil Pressure
70
Waiting To Start
Pre-Lubrication Time: MIN:SEC
70
Waiting To Start
Motor Temperature Inhibit:
70
Motor Temperature / Inhibit Temperature
Waiting To Start
Restart Time Inhibit: MIN:SEC
70
Waiting To Start
Low Oil Temperature Inhibit:
70
Oil Temperature / Inhibit Temperature
Waiting To Start
Waiting For Starter To Start: MIN:SEC
70
Starting Compressor
There is no sub mode displayed
72
Running
There is no sub mode displayed
74
Running
Surge
74
Running
Base Loaded
74
Running
Current Control Soft Loading
74
Running
Capacity Control Soft Loading
74
Running – Limit
Current Limit
75
Running – Limit
Phase Unbalance Limit
75
Running – Limit
Condenser Pressure Limit
75
Running – Limit
Evaporator Temperature Limit
75
Running – Limit
Minimum Capacity Limit
75
Running – Limit
Maximum Capacity Limit
75
Preparing To Shutdown
Closing IGV
IGV Position %
7E
Shutting Down
Post-Lubrication Time:
MIN:SEC
7E
Shutting Down
Evaporator Pump Off Delay:
MIN:SEC
7E
Shutting Down
Condenser Pump Off Delay:
MIN:SEC
7E
Boot & Application software part number, self-test, and
configuration validity screens will be present.