104
CVHH-SVX001G-EN
the past seven days that occurred while the chiller
was operating. You can use it to help determine if a
leak is present on the high side or the low side of
the chiller.
•
P
Pu
um
mp
po
ou
utt C
Ch
hiilllle
err O
Offff—
—7
7 D
Da
ay
yss.. Indicates the
percentage of the total purge pump-out time during
the past seven days that occurred when the chiller
was not operating. You can use it to help determine
if a leak is present on the high side or the low side
of the chiller.
•
P
Pu
um
mp
po
ou
utt—
—L
Liiffe
e.. Indicates the total purge pump-out
time that has accumulated over the life of the
purge.
•
P
Pu
urrg
ge
e R
Rffg
gtt C
Cp
prrssrr S
Su
uccttiio
on
n T
Te
em
mp
p.. Indicates the
purge refrigerant compressor suction temperature.
It is useful for diagnosing purge system problems.
•
P
Pu
urrg
ge
e L
Liiq
qu
uiid
d T
Te
em
mp
p.. Indicates the temperature
sensed by the controller and used to inhibit purge
operation. The purge liquid temperature sensor,
when the chiller is operating, is the chiller saturated
condenser temperature sensor; when the chiller is
Off, it is the chiller saturated evaporator
temperature sensor. If this temperature is below the
Pumpout Inhibit Temperature that is defined in the
S
Se
ettttiin
ng
gss menu, pump-out is not allowed. This
value is used to prevent inefficient operation of the
purge under certain conditions.
•
C
Ca
arrb
bo
on
n T
Ta
an
nkk T
Te
em
mp
p.. Indicates the carbon bed
temperature and is useful for monitoring
regeneration and for diagnosing regeneration
system problems.