18
CVHH-SVX001G-EN
Table 1.
Clearance requirements (continued)
Shell Combo
A
B
C
D
E
in.
cm
in.
cm
in.
cm
in.
cm
in.
cm
160M/200M
96
244
166
422
428
1087
37
94
112
285
160M/20HM
96
244
166
422
428
1087
36
91
128
325
200L/200L
107
272
186
472
479
1217
34
86
111
282
200L/20HL
107
272
186
472
479
1217
37
94
131
333
200L/220L
107
272
186
472
480
1219
37
94
120
305
220L/220L
120
305
186
472
493
1252
38
97
118
300
220L/22HL
120
305
186
472
492
1250
42
107
143
363
Note:
All dimensions are approximate; refer to the unit submittal package for exact dimensions for your unit.
General Weights
Weights (lb)
IIm
mp
po
orrtta
an
ntt:: The weight information provided here
should be used for general information
only. Trane does not recommend using this
weight information for considerations
relative to chiller handling, rigging, or
placement. The large number of variances
between chiller selections drives variances
in chiller weights that are not recognized in
these tables. For specific weights for your
chiller, refer to your submittal package.
Table 2.
Representative weights, 60 Hz chillers (lb)
Model
Comp Size
CPKW
Evap Size
Cond Size
Weights without Starters
NTON
EVSZ
CDSZ
Operating
Shipping
CVHH
900–1200
1228
100M
100M
47451
41071
900–1200
1228
100L
100L
49252
42368
900–1200
1340
100M
10HM
54999
47798
900–1200
1340
130M
130M
52868
44894
900–1200
1340
130M
13HM
62184
53398
900–1200
1340
160M
200M
63653
53621
900–1200
1340
200L
220L
71963
58931
900–1200
1340
220L
220L
79082
64664
1500–1700
1340
200L
200L
70921
59137
1500–1700
1340
200L
20HL
80262
67562
1500–1700
1340
220L
220L
79082
64664
1500–1700
1340
220L
22HL
93396
78060
Notes:
1
.
TECU tubes, 0.028 in. tube wall thickness.
2
.
300 psig marine waterboxes.
3
.
Heaviest possible bundle and motor combination.
4
.
Operating weights assume the largest possible refrigerant charge.
5
.
Industrial Control Panel (INDP) option, add 50 lb.
6
.
Control Power Transformer (CPTR) option, add 280 lb.
7
.
Supplemental Motor Protection (SMP) option, add 500 lb.
8
.
To calculate the maximum chiller weight with starter/drive, add the starter/AFD weight from the following table (maximum weights, unit-mounted
starters/AFDs [lb]) to the chiller maximum weight from this table.
Summary of Contents for CVHH CenTraVac