72
CVHH-SVX001G-EN
System Control Circuit Wiring (Field Wiring)
Table 24. Unit control panel wiring 120 Vac
Standard Control Circuits: Unit
Control Panel Control Wiring
(120 Vac)
Unit Control Terminations
Input or Output Type
Contacts
Chilled Water Flow Proving Input
(a)
1X1-5 to 1K16-J3-2
Binary Input
Normally Open, Closure with Flow
Condenser Water Flow Proving
Input
(b)
1X1-6 to 1K16-J2-2
Binary Input
Normally Open, Closure with Flow
Chilled Water Pump Relay Output
1K15-J2-4 to 6
Binary Output
Normally Open
Condenser Water Pump Relay
Output
1K15-J2-1 to 3
Binary Output
Normally Open
Optional Control Circuits (120
Vac)
Note:
Defaults are factory programmed; alternates can be selected at start-up using the service tool.
Alarm Relay MAR (Non-Latching)
Output
1K19-J2-1 to 3
Binary Output
Normally Open
Limit Warning Relay Output
1K19-J2-4 to 6
Binary Output
Normally Open
Alarm Relay MMR (Latching) Output
1K19-J2-7 to 9
Binary Output
Normally Open
Compressor Running Relay Output
1K19-J2-10 to 12
Binary Output
Normally Open
Maximum Capacity Relay Output
1K20-J2-1 to 3
Binary Output
Normally Open
Head Relief Request Relay Output
1K20-J2-4 to 6
Binary Output
Normally Open
Purge Alarm Relay Output
1K20-J2-7 to 9
Binary Output
Normally Open
Ice Making Relay Output
1K15-J2-10 to 12
Binary Output
Normally Open
Free Cooling Relay Output
1K21-J2-4 to 6
Binary Output
Normally Open
Standard Low Voltage Circuits
(Less than 30 Vac)
(c)
Unit Control Panel Terminations
Input or Output Type
Contacts
External Auto Stop Input
1K2-J2-1 to 2
Binary Input
Closure Required for Normal
Operation
Emergency Stop Input
1K2-J2-3 to 4
Binary Input
Closure Required for Normal
Operation
Optional Low Voltage Circuits
External Base Loading Enable Input
1K8-J2-1 to 2
Binary Input
Normally Open
External Hot Water Control Enable
Input
1K8-J2-3 to 4
Binary Input
Normally Open
External Ice Machine Control
Enable Input
1K9-J2-1 to 2
Binary Input
Normally Open
External Free Cooling Input Enable
Input
1K10-J2-1 to 2
Binary Input
Normally Open
% RLA Compressor Output
1K5-J2-1 to 3
Analog Output
2–10 Vdc
External Condenser Pressure
Output
1K5-J2-4 to 6
Analog Output
2–10 Vdc
Evaporator/Condenser Differential
Pressure Output
1K5-J2-4 to 6
Analog Output
2–10 Vdc
Condenser Head Pressure Control
1K5-J2-4 to 6
Analog Output
2–10 Vdc
External Current Limit Setpoint
Input
1K6-J2-2 to 3
Analog Input
2–10 Vdc, or 4–20 mA
External Chilled Water Setpoint
Input
1K6-J2-5 to 6
Analog Input
2–10 Vdc, or 4–20 mA
External Base Loading Setpoint
Input
1K7-J2-2 to 3
Analog Input
2–10 Vdc, or 4–20 mA
Generic Refrigerant Monitor Input
1K7-J2-5 to 6
Analog Input
2–10 Vdc, or 4–20 mA
Outdoor Air Temperature Sensor
Inter-processor Communication
(IPC) Bus Connection and Sensor
Communication and Sensor
Tracer
®
Comm 4 Interface
1K3-J2-1(+) to 2(-)
1K3-J2-3(+) to 4(-)
Communication to Tracer
®
(As Ordered; See Sales Order)
BACnet
®
or MODBUS
®
1K1, 5(+) to 6(-)
Communication to BACnet
®
or
MODBUS
®
(As Ordered; See Sales Order)
LonTalk
®
Comm 5 Interface
1K4-J2-1(+) to 2(-)
1K4-J2-3(+) to 4(-)
Left Panel
Communication to LonTalk
®
(As Ordered; See Sales Order)
Note:
All wiring to be in accordance with National Electrical Code (NEC) and any local codes.
(a)
If the Chilled Water Flow Proving Input is a factory-installed ifm efector
®
flow-sensing device, the secondary field device (recommended with 38°F [3.3°C]
and lower leaving chilled water temperatures) for proof of flow connects from 1X1-5 to 1K26-4 (binary input; normally open, closure with flow). Remove
factory jumper when used.
Summary of Contents for CVHH CenTraVac
Page 126: ...126 CVHH SVX001G EN N No ot te es s ...