86
CVHH-SVX001G-EN
Start-up and Shut-down
This section provides basic information on chiller
operation for common events.
Sequence of Operation
Adaptive control algorithms are used on CenTraVac
™
chillers. This section illustrates common control
sequences.
Software Operation Overview Diagram
The following figure is a diagram of the five possible
software states. This diagram can be thought of as a
state chart, with the arrows and arrow text, depicting
the transitions between states:
•
The text in the circles are the internal software
designations for each state.
•
The first line of text in the circles are the visible top
level operating modes that can be displayed in
Tracer
®
AdaptiView
™
.
•
The shading of each software state circle
corresponds to the shading on the time lines that
show the state that the chiller is in.
There are five generic states that the software can be
in:
•
Power Up
•
Stopped
•
Starting
•
Running
•
Stopping
Figure 51.
Software operation overview
Conf
irmed
Shutdown
Stopped
Stopped
Run Inhibit
Stopping
Preparing to Shut Down
Shutting Down
Running
Running
Running—Limit
Starting
Auto
Waiting to Start
Starting Compressor
Power
Up
Start
Comm
and
Diagnostic
Res
et
Fast Restart or Satisfied Setpoint
Stop Command or Diagnostic
Stop
Comma
nd
Diagnosti
c
Sta
rt
Conf
irmed
In the following diagrams:
•
The time line indicates the upper level operating
mode, as it would be viewed in the Tracer
®
AdaptiView
™
.
•
The shading color of the cylinder indicates the
software state.
•
Text in parentheses indicates sub-mode text as
viewed in the Tracer
®
AdaptiView
™
.
•
Text above the time line cylinder is used to illustrate
inputs to the UC800. This may include user input to
the Tracer
®
AdaptiView
™
touch screen, control
inputs from sensors, or control inputs from a
generic BAS.
Summary of Contents for CVHH CenTraVac
Page 126: ...126 CVHH SVX001G EN N No ot te es s ...