background image

18-CD20D1-18

21

Installer’s Guide

WARNING

!

DO NOT attempt to manually light the burner.  Failure to
follow this warning could result in property damage, per-
sonal injury or death.

START UP AND ADJUSTMENT

PRELIMINARY INSPECTIONS

With gas and electrical power “OFF”

1. Duct connections are properly sealed

2. Filters are in place

3. Venting is properly assembled

4. Blower door is in place

Turn knob on main gas valve within the unit to the “

OFF

position.  Turn the external gas valve to “ON”.  Purge the air
from the gas lines.  After purging, check all gas connections
for leaks with a soapy solution — 

DO NOT CHECK WITH

AN OPEN FLAME.

  Allow 5 minutes for any gas that might

have escaped to dissipate.  LP Gas, being heavier than air,
may require forced ventilation.  Turn the knob on the gas
valve in the unit to the “ON” position.

LIGHTING INSTRUCTIONS

Lighting instructions appear on each unit. Each
installation must be checked out at the time of
initial start up to insure proper operation of all
components.  Check out should include putting
the unit through one complete cycle as outlined
below.

Turn on the main electrical supply and set the thermostat
above the indicated temperature.  The ignitor will automati-
cally heat, then the gas valve is energized to permit the flow
of gas to the burners.  After ignition and flame is established,
the flame control module monitors the flame and supplies
power to the gas valve until the thermostat is satisfied.

TO SHUT OFF

For complete shutdown: Move the control switch on the main
gas valve to the “OFF” position (See Figures 28 and 29).
Disconnect the electrical supply to the unit.

CAUTION

!

If this is done during the cold weather months, provisions
must be taken to prevent freeze-up of all water pipes and
water receptacles.  Failure to follow this warning could
result in property damage.

Whenever your house is to be vacant, arrange to have
someone inspect your house for proper temperature.  This
is very important in below freezing weather.  If for any
reason your furnace should fail to operate damage could
result, such as frozen water pipes.

WARNING

!

FIRE OR EXPLOSION HAZARD

Failure to follow the safety warnings exactly could result in
serious injury, death or property damage.

Never test for gas leaks with an open flame.  Use a com-
mercially available soap solution made specifically for the
detection of leaks to check all connections.  A fire or
explosion may result causing property damage, personal
injury, or loss of life.

SEQUENCE OF OPERATION

Thermostat call for heat (2-stage thermostat)

Call for 1st stage only:

R and W1 thermostat contacts close signaling the control
module to run its self-check routine.  After the control module
has verified that the 1st stage pressure switch contacts are
open and the limit switch(es) contacts are closed, the draft
blower will be energized.

As the induced draft blower comes up to speed, the pressure
switch contacts will close and the ignitor warm up period will
begin.  The ignitor will heat for approx. 20 seconds, then the
gas valve is energized in 1st stage to permit gas flow to the
burners.  The flame sensor confirms that ignition has been
achieved within the 4 second ignition trial period.

As the flame sensor confirms that ignition has been achieved,
the delay to fan ON period begins timing and after approx.
45 seconds the indoor blower motor will be energized at low
speed and will continue to run during the heating cycle.

Call for 2nd stage after 1st stage:

R and W2 thermostat contacts close signaling a call for 2nd
stage heat.  After a 30 second delay, the induced draft blower
will be energized on high speed and the 2nd stage pressure
switch contacts will close allowing the gas valve to be energized
in 2nd stage and the indoor blower motor in high speed.

2nd stage satisfied, 1st stage still called:

R and W2 thermostat contacts open signaling that 2nd stage
heating requirements are satisfied.  The induced draft blower
is reduced to low speed allowing the 2nd stage pressure
switch contacts to open and the gas valve is reduced to 1st
stage.  After approx. 30 seconds the indoor blower motor is
reduced to low speed.

1st stage satisfied:

R and W1 thermostat contacts open signaling that 1st stage
heating requirements are satisfied.  The gas valve will close
and the induced draft blower will be de-energized.  The indoor
blower motor will continue to run for the fan off period (Field
selectable at 60, 100, 140 or 180 seconds - Factory setting is
100 seconds), then will be de-energized by the control module.

Thermostat call for heat (1-stage Thermostat)

R and W1/W2 (jumpered) thermostat contacts close signaling
a call for heat. 1st stage sequence of operation remains the
same as above. 2nd stage heat has a 10 minute delay from
the time of 1st stage ignition.

Thermostat satisfied:

R and W1/W2 (jumpered) contacts open signaling the control
module to close the gas valve and de-energize the induced
draft blower.  The indoor blower motor will continue to
operate at high heat speed for approx. 30 seconds after the
flames are extinguished and then is switched to low heat
speed for the remaining FAN-OFF period.

INDOOR BLOWER OPERATION WITH THERMOSTAT FAN
SWITCH “ON”:

Fan is R-G.

R-W energized, fan continues to run without interruption.

Heat Low speed if it is a two stage furnace.

Heat speed if it is a single stage furnace.

Summary of Contents for DD060R9V3F Series

Page 1: ...est version USA CANADA ALTERNATE Category I Venting Guide Pub No 18 CH23D1 latest version Horizontal Conversion for these furnaces may be left or right side rotation ALL phases of this installation mu...

Page 2: ...temperature rise and venting according to the manufacturer s instructions 10 This product must be gas piped by a Licensed Plumber or Gas Fitter in the Commonwealth of Massachusetts Safety signal word...

Page 3: ...n these instructions Category I defined on page 13 CAUTION To prevent shortening its service life the furnace should not be used as a Construction Heater during the finishing phases of construction un...

Page 4: ...4 18 CD20D1 18 Installer s Guide From Dwg 21C341699 Rev 4 UD R9V K OUTLINE DRAWING ALL DIMENSIONS ARE IN INCHES...

Page 5: ...wg 21C341700 Sh 1 Rev 0 DD R9V F OUTLINE DRAWING ALL DIMENSIONS ARE IN INCHES MODEL A B C D DD060R9V3F DD080R9V3F 17 1 2 9 5 8 16 1 4 16 DD100R9V5F 21 13 1 16 19 3 4 19 1 2 DD120R9V5F 24 1 2 15 5 16 2...

Page 6: ...looring For vertical downflow application subbase BAYBASE205 must be used between the furnace and combustible flooring When the downflow furnace is installed vertically with a cased coil a subbase is...

Page 7: ...lated caulked vapor barrier etc may need additional air provided as described for con fined space Confined spaces are installations with less than 50 cu ft of space per 1000 BTU hr input from all equi...

Page 8: ...vibration to the annoyance level When the furnace is located in a utility room adjacent to the living area the system should be carefully designed with returns which minimize noise transmission throu...

Page 9: ...ace If only the front of the furnace is accessible it is recom mended that both supply and return air plenums are removable 8 When replacing a furnace old duct work should be cleaned out Thin cloths s...

Page 10: ...ALLATION With the filter removed the filter rack is compressed and then inserted into the bottom of the furnace The retaining screw pin on each side inserts into engagement holes at the bottom of the...

Page 11: ...Leave the bottom panel in place e After the side cutout is made following the directions in the Return Air Duct Connections section on pages 8 and 9 compress the filter rack and reinstall in the side...

Page 12: ...mine the location to be used The furnace cabinet has dimples for location of the alternate furnace clips Side return only Pre drill clearance holes with a 3 16 drill Bottom return holes are pre drille...

Page 13: ...X20X1 13 1 8 24 1 2 2 16X20X1 11 5 8 Location dimension is from end of duct to the screw holes for the bracket VENT PIPING These furnaces have been classified as Fan Assisted Combus tion System Catego...

Page 14: ...other good venting practices as stated in the venting section of the National Fuel Gas Code ANSI Z223 1 latest edition 10 Vent connectors serving appliance vented by natural draft or non positive pre...

Page 15: ...ircuit board must be cut if optional humidistat is used The jumper must also be cut when applying an airflow command signal to the BK input such as with the variable speed single zone and multi zone s...

Page 16: ...ABLE SPEED 2 STAGE FURNACE 1 STAGE HEATING 1 STAGE COOLING USING A 1 STAGE HEATING 1 STAGE COOLING THERMOSTAT OUTDOOR SECTION WITHOUT TRANSFORMER W14 OUTDOOR UNIT NO TRANSFORMER SEE NOTE 6 SEE NOTE 7...

Page 17: ...BK on the circuit board must be cut if an optional Humidistat is installed h HUMIDISTAT HOOKUP If an optional humidistat is to be connected between R and BK the factory installed jumper between R and...

Page 18: ...e gas supply piping system at test pressures equal to or less than 1 2 psig CAUTION Use a backup wrench on the gas valve when installing gas piping to prevent damage to the gas valve and manifold asse...

Page 19: ...times to verify regulator setting e For the White Rodgers gas valve model 36G 1 Adjust low fire by removing the low adjustment regulator cover screw See Figure 29 2 To increase outlet pressure turn th...

Page 20: ...Important Reinstall the propane orifices to the same depth as the orifices supplied with the equipment See Table 14 for help in selecting orifices if orifice change is required Furnace input rate and...

Page 21: ...W1 thermostat contacts close signaling the control module to run its self check routine After the control module has verified that the 1st stage pressure switch contacts are open and the limit switch...

Page 22: ...d gas valve causing shutdown when the door is removed Operation with the door removed or ajar can permit the escape of dangerous fumes All panels must be securely closed at all times for safe operatio...

Page 23: ...ntrol module has shut the system down and gone into lockout the system must be manu ally reset before the unit will restart To reset turn the system power off then on then off and then on again within...

Page 24: ...place IFC Continuous OFF Check Power 2 Flashes System Lockout Retries or Recycles exceeded 3 Flashes Draft Pressure Error Possible problems a Venting problem b Pressure switch problem c Inducer proble...

Reviews: