40 18-CD30D1-12
Installer’s Guide
USER INTERFACE MENU
SERVICE PROCEDURE TO ACCESS
USER INTERFACE FOR THE MODULATING FURNACE
This procedure should only be performed by trained service
personnel.
▲
WARNING
!
ELECTRICAL SHOCK HAZARD
DO NOT BYPASS THE DOOR SWITCH BY ANY
PERMANENT MEANS.
FAILURE TO FOLLOW WARNING COULD RESULT IN
SERIOUS PERSONAL INJURY OR DEATH.
▲
WARNING
!
ELECTRICAL SHOCK HAZARD
DO NOT TOUCH ANY COMPONENTS OTHER THAN THE
DISPLAY ASSEMBLY AND THE DOOR SWITCH DURING
THIS PROCEDURE.
FAILURE TO FOLLOW WARNING COULD RESULT IN
SERIOUS PERSONAL INJURY OR DEATH.
USER INTERFACE
ENTER
Push left & right
to scroll through
menu options
Push up & down
to scroll through
setup menu
Push ENTER
to make selection
Viewing Window
User Interface pictured above adjusts Variable Speed Airflow options and is used
for custom setup of Furnace operations- See menu options in User Interface on pages 45-46.
Y
1. Remove Blower Door panel by turning the two door
latches.
2. Lower door panel and remove from service access area.
3. Use one hand depress the door switch (there must be
power to the control system for the display assembly to
function) and keep the door switch depressed during
programming.
4. Using the other hand move through the Display Assembly
menu using the arrow buttons.
5. The User Interface menu on pages 41-42 is a guide to
the menu options.
6. When programming is complete release Door Switch
and replace the Blower Door.
NOTE:
If power is lost during programming, all changes made
will be saved.