PKG-SVX19B-E4
26
BACKFLOW LINE DIMENSIONING (LIQUID)
To avoid gas development inside the line and to ensure an
adequate pressure is reached inside the laminating unit,
the liquid line must be correctly dimensioned. Generally, the
systems are dimensioned so that pressure loss along the line
causes a variation of the saturation temperature between
0,5 K and 1 K
During the installation of the cooling unit, a solenoid
valve should be fitted on the liquid line between
the inner unit and the external condenser, to avoid
malfunctioning and to protect the compressor from
unwanted liquid migration during start- up.
Liquid line external diameters
Remote air cooled condenser
EDA* - EUA*
MODEL
1105
1106
2107
2207
2109
2209
Number/
Suggested model (1) (2)
1 x
CAP0661
1 x
CAP0661
1 x
CAP0801
2 x
CAP0331
1 x
CAP1011
2 x
CAP0361
EDA* - EUA*
MODEL
2111
2211
1113
2213
2216
2218
Number/
Suggested model (1) (2)
1 x
CAP1301
2 x
CAP0511
1 x
CAP1301
1 x
CAP1802
2 x
CAP0661
1 x
CAP2002
2 x
CAP0801
1 x
CAP3002
2 x
CAP1011
EDA* - EUA
*
MODEL
1105
1106
2107 - 2109
2207 - 2209
2213 - 2216
2222
2225
-
2110 - 2113
2211 - 2213
2218
4222
4225
4228
R410A
1 x
16 mm
1 x
16 mm
1 x
16 mm
2 x
16 mm
2 x
16 mm
2 x
18 mm
2 x
18 mm
2 x
22 mm
EDA* - EUA*
MODEL
2222
4222
2225
4225
4228
Number/
Suggested model (1) (2)
1 x
CAP2002
1 x
CAP2002
1 x
CAP3002
2 x
CAP3002
1 x
CAP4002
(1) With fan speed control
(2) External temperature = 35°C