background image

6

 ACC-SVN232A-EN

Installation

Field Installed Option

1. Assemble connecting rods 4 to return air damper 3 by 

aligning holes 1 and 2, and attach rods using two 
screws as shown below.

2. Remove the filter/fan compartment access panel and 

the unit end panel (evaporator end).

a. Place the return air damper assembly into the 

return air opening as illustrated in 

Figure 4

. Confirm 

damper is positioned with the sheet metal lip in the 
upward position.

b. Attach the pivotal brackets to the unit using two 

screws per bracket.

c. Raise the damper and rods into the vertical 

position. Position the connecting rods against the 
filter rack to prevent them from interfering with the 
economizer. See 

Figure 4

.

d. Confirm damper is positioned with sheet metal lip 

in the upward position as illustrated in following 
figure.

WARNING

Hazardous Service Procedures!

Failure to follow all precautions in this manual and on 
the tags, stickers, and labels could result in death or 
serious injury.
Technicians, in order to protect themselves from 
potential electrical, mechanical, and chemical hazards, 
MUST follow precautions in this manual and on the 
tags, stickers, and labels, as well as the following 
instructions: Unless specified otherwise, disconnect all 
electrical power including remote disconnect and 
discharge all energy storing devices such as capacitors 
before servicing. Follow proper lockout/tagout 
procedures to ensure the power can not be 
inadvertently energized.When necessary to work with 
live electrical components, have a qualified licensed 
electrician or other individual who has been trained in 
handling live electrical components perform these 
tasks.

WARNING

Hazardous Voltage w/Capacitors!

Failure to disconnect power and discharge capacitors 
before servicing could result in death or serious injury.
Disconnect all electric power, including remote 
disconnects and discharge all motor start/run 
capacitors before servicing. Follow proper lockout/ 
tagout procedures to ensure the power cannot be 
inadvertently energized. Verify with a CAT III or IV 
voltmeter rated per NFPA 70E that all capacitors have 
discharged.

Figure 2.

Assemble connecting rods

1

2

Figure 3.

Remove panels

Figure 4.

Install return air damper assembly 

Summary of Contents for FIAECON003 Series

Page 1: ...nstall and service the equipment The installation starting up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Improper...

Page 2: ...rdous situation which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could result in equipment or pro...

Page 3: ...arks All trademarks referenced in this document are the trademarks of their respective owners WARNING Follow EHS Policies Failure to follow instructions below could result in death or serious injury A...

Page 4: ...recedent 5 Field Installed Option 5 Factory Installed Option 5 Installation Precedent 6 Field Installed Option 6 Factory Installed Option Field Set Up 8 Mist Eliminator Servicing 9 Minimum Position Se...

Page 5: ...provide reasonable evidence that the damage did not occur after delivery 6 Notify the carrier s terminal of damage immediately by phone and by mail Request an immediate joint inspection of the damage...

Page 6: ...ves from potential electrical mechanical and chemical hazards MUST follow precautions in this manual and on the tags stickers and labels as well as the following instructions Unless specified otherwis...

Page 7: ...post flange as illustrated in following figure c Position the left side flange on the economizer in front of the corner post flange d With the screws provided secure the bottom right hand side of the...

Page 8: ...Figure 12 7 With the screws provided secure each side of the economizer assembly by inserting a screw through the clearance hole in the bottom of the corner post and into the engagement hole in the e...

Page 9: ...screws provided 11 Using field supplied silicone sealant seal all seams cracks and gaps around the back panel and vertical edge of the hood panels Mist Eliminator Servicing 1 Remove screws from end p...

Page 10: ...made using the Symbio service and installation mobile app or Symbio 700 on board UI Wiring Connections Refer to main unit schematic sheet 6 for electrical connections to Fresh air module located in re...

Page 11: ...Notes ACC SVN232A EN 11...

Page 12: ...gn and specifications without notice We are committed to using environmentally conscious print practices Trane and American Standard create comfortable energy efficient indoor environments for commerc...

Reviews: