Installation

ACC-SVN232A-EN

3. Block-off installation

a. Attach block-off 5 to unit using four screws as 

illustrated in 

Figure 5

.

The block-off is designed to close the opening created 
between the economizer and the base, when the 
economizer assembly is in its operating position.

b. Remove approximately 3-inch of gasket material 

from the bottom of each corner post to expose the 
holes used to attach the economizer assembly to 
the unit, as illustrated in 

Figure 6

 detail "A".

Note:

There are two holes, a (large) clearance hole and a 
(small) engagement hole. Their function will be 
discussed later.

4. Economizer assembly installation

a. Place tape (refer to 

“Parts List,” p. 5

) wher

shipping screws were removed.

b. Place the economizer assembly into the opening 

with the back right flange, on the economizer, 
behind the corner post flange, as illustrated in 
following figure.

c. Position the left side flange on the economizer in 

front of the corner post flange. 

d. With the screws provided, secure the bottom right 

hand side of the economizer assembly by inserting 
the screws through the clearance holes in the 
corner post and into the engagement holes in the 
economizer assembly. Refer to 

Figure 7

e. Secure the bottom left hand side of the economizer 

assembly by inserting the screws through the 
clearance holes in the economizer assembly and 
into the engagement holes of the corner post. Refer 
to 

Figure 7

.

f. Secure economizer using four screws on left side 

and 4 screws on right side as illustrated in 

Figure 7

.

g. Attach connecting rod bracket to outdoor damper 

blade using two screws on each side as illustrated 
in following figure, detail "B". Check for binding by 
slowly operating the dampers by hand.

Figure 5.

Install block-off

Figure 6.

Remove gasket material

Figure 7.

Install economizer assembly

Figure 8.

Attach connecting rod bracket

Summary of Contents for FIAECON003 Series

Page 1: ...nstall and service the equipment The installation starting up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Improper...

Page 2: ...rdous situation which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could result in equipment or pro...

Page 3: ...arks All trademarks referenced in this document are the trademarks of their respective owners WARNING Follow EHS Policies Failure to follow instructions below could result in death or serious injury A...

Page 4: ...recedent 5 Field Installed Option 5 Factory Installed Option 5 Installation Precedent 6 Field Installed Option 6 Factory Installed Option Field Set Up 8 Mist Eliminator Servicing 9 Minimum Position Se...

Page 5: ...provide reasonable evidence that the damage did not occur after delivery 6 Notify the carrier s terminal of damage immediately by phone and by mail Request an immediate joint inspection of the damage...

Page 6: ...ves from potential electrical mechanical and chemical hazards MUST follow precautions in this manual and on the tags stickers and labels as well as the following instructions Unless specified otherwis...

Page 7: ...post flange as illustrated in following figure c Position the left side flange on the economizer in front of the corner post flange d With the screws provided secure the bottom right hand side of the...

Page 8: ...Figure 12 7 With the screws provided secure each side of the economizer assembly by inserting a screw through the clearance hole in the bottom of the corner post and into the engagement hole in the e...

Page 9: ...screws provided 11 Using field supplied silicone sealant seal all seams cracks and gaps around the back panel and vertical edge of the hood panels Mist Eliminator Servicing 1 Remove screws from end p...

Page 10: ...made using the Symbio service and installation mobile app or Symbio 700 on board UI Wiring Connections Refer to main unit schematic sheet 6 for electrical connections to Fresh air module located in re...

Page 11: ...Notes ACC SVN232A EN 11...

Page 12: ...gn and specifications without notice We are committed to using environmentally conscious print practices Trane and American Standard create comfortable energy efficient indoor environments for commerc...

Reviews: