Installation

8

 ACC-SVN232A-EN

5. Attach end panel back to unit.

Factory Installed Option 
(Field Set-Up)

Each economizer ships inside the unit and requires partial 
assembling and setup in the field.

1. Remove the filter/fan compartment access panel.

2. Remove the lower screws in the end panel. See 

Figure 11

. Lay block-off angle aside for later 

installation.

3. Remove and discard shipping bracket.

4. Do not remove the screws in the upper row of the end 

panel.

5. Grasp the bottom of the end panel and pull the 

economizer assembly outward into the operating 
position. See 

Figure 11

.

6. Remove approximately 3-inch of gasket material from 

the bottom of each corner post to expose the holes 
used to attach the economizer assembly to the unit. 
See 

Figure 12

7. With the screws provided, secure each side of the 

economizer assembly by inserting a screw through the 
clearance hole in the bottom of the corner post and into 
the engagement hole in the economizer assembly. 
Refer to following figure.

Figure 9.

Attach end panel

WARNING

Hazardous Voltage w/Capacitors!

Failure to disconnect power and discharge capacitors 
before servicing could result in death or serious injury.
Disconnect all electric power, including remote 
disconnects and discharge all motor start/run 
capacitors before servicing. Follow proper lockout/ 
tagout procedures to ensure the power cannot be 
inadvertently energized. Verify with a CAT III or IV 
voltmeter rated per NFPA 70E that all capacitors have 
discharged.

Figure 10.

Remove filter access panel

Figure 11.

Pull economizer assembly outward

Figure 12.

Remove gasket material

Remove screws and lay block-off 
angle aside.

Block-off Angle

Detail
  “A”

Clearance hole

Summary of Contents for FIAECON003 Series

Page 1: ...nstall and service the equipment The installation starting up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Improper...

Page 2: ...rdous situation which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could result in equipment or pro...

Page 3: ...arks All trademarks referenced in this document are the trademarks of their respective owners WARNING Follow EHS Policies Failure to follow instructions below could result in death or serious injury A...

Page 4: ...recedent 5 Field Installed Option 5 Factory Installed Option 5 Installation Precedent 6 Field Installed Option 6 Factory Installed Option Field Set Up 8 Mist Eliminator Servicing 9 Minimum Position Se...

Page 5: ...provide reasonable evidence that the damage did not occur after delivery 6 Notify the carrier s terminal of damage immediately by phone and by mail Request an immediate joint inspection of the damage...

Page 6: ...ves from potential electrical mechanical and chemical hazards MUST follow precautions in this manual and on the tags stickers and labels as well as the following instructions Unless specified otherwis...

Page 7: ...post flange as illustrated in following figure c Position the left side flange on the economizer in front of the corner post flange d With the screws provided secure the bottom right hand side of the...

Page 8: ...Figure 12 7 With the screws provided secure each side of the economizer assembly by inserting a screw through the clearance hole in the bottom of the corner post and into the engagement hole in the e...

Page 9: ...screws provided 11 Using field supplied silicone sealant seal all seams cracks and gaps around the back panel and vertical edge of the hood panels Mist Eliminator Servicing 1 Remove screws from end p...

Page 10: ...made using the Symbio service and installation mobile app or Symbio 700 on board UI Wiring Connections Refer to main unit schematic sheet 6 for electrical connections to Fresh air module located in re...

Page 11: ...Notes ACC SVN232A EN 11...

Page 12: ...gn and specifications without notice We are committed to using environmentally conscious print practices Trane and American Standard create comfortable energy efficient indoor environments for commerc...

Reviews: