CTV-SVX009D-GB
48
4
UNT-PRC002-GB
Technical Data
FWD
08
12
20
30
45
Power supply
(V/Ph/Hz)
230/1/50
Capacities
Cooling capacity on water (1)
(kW)
5,2
8,3
15
18,8
30,1
Heating capacity on water (2)
(kW)
6,3
11,9
18,9
20,9
38,2
Fan motor
(type)
2 x direct drive centrifugal
Fan power input (3)
(kW)
0,23
0,46
0,65
1,04
1,51
Current amps (3)
(A)
1,1
2,2
3,1
4,7
5,5
Start-up amps
(A)
3,2
5,5
9,3
14,1
16,5
Air flow
minimum
(m
3
/h)
490
980
1400
1800
2700
nominal
(m
3
/h)
820
1650
2300
3000
4500
maximum
(m
3
/h)
980
1970
2600
3600
5400
Main coil
Water entering/leaving connections
(type)
ISO R7 rotating female
(Dia)
3/4"
3/4"
1 1/2"
1 1/2"
1 1/2"
Electric heater (accessory for blower only)
Electric power supply
(V/Ph/Hz)
230/1/50
230/1/50 or 400/3/50
400/3/50
400/3/50
400/3/50
Heating capacity
(kW)
2/4
8
10
12
12
Hot water coil (accessory for blower only)
Heating capacity (4)
(kW)
6,3
12
17,4
22,4
34,5
G2 filter (filter box accessory)
Quantity
2
2
2
2
2
Dimensions ( LxWxth)
(mm)
386x221x8
486x271x8
586x321x8
586*421*8
586*621*8
G4 filter (filter box accessory)
Quantity
-
2
2
2
2
Dimensions ( LxWxth)
(mm)
-
486x264x48
586x314x48
586*414*48
586*614*48
Condensate pump (accessory)
(type)
Centrifugal
Water flow - lift height
(l/h - mm)
24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5)
(dB(A))
36/40/43
38/41/44
46/50/53
47/52/57
47/52/58
Sound power level (5)
(dB(A))
46/50/53
48/51/54
56/60/63
57/62/67
57/62/68
Unit dimensions
Width x Depth
(mm)
890 x 600
1090 x 710
1290 x 820
1290 x 970
1290 x 1090
Height
(mm)
250
300
350
450
650
Shipped unit dimensions
Width x Depth
(mm)
933 x 644
1133 x 754
1333 x 864
1333 x 1008
1333*1133
Height
(mm)
260
310
360
460
660
Weight
(kg)
32
46
61
76
118
Colour
galvanised steel
Recommended fuse size
Unit alone (aM/gI)
(A)
8/16
8/16
8/16
8/25
8/25
Unit with electric heater (gI)
(A)
16 (2kW),25 (4kW)
40 (230V),3*16 (400V)
3*20
3*25
3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
Unit Start Up Procedures
Temporary Shutdown and Restart
Temporary Shutdown is used for control operation,
maintenance or to repair the unit typically less than one
week.
To shut the unit down for a short time, use the following
procedure:
1. Press the STOP key on the TD7. The compressors
will continue to operate and, after unloading for
20 seconds, will stop when the compressor contactors
de-energize.
2. Stop the water circulation by turning off the chilled
water pump at least one minute after the stop of the
compressors.
To restart the unit after a temporary shutdown, enable the
chilled-water pump and press the AUTO key.
The unit will start normally, provided the following
conditions exist:
• The UC800 receives a call for cooling and the
differential-to-start is above the set point
• All system operating interlocks and safety circuits are
satisfied
CAUTION!
Under freezing conditions, the chilled water pump
must remain in operation during the full shutdown period of
the chiller if the chilled water loop does not contain glycol,
to prevent any risk of evaporator freeze-up. Refer to charts 1
and 2.
Extended Shutdown Procedure
The following procedure is to be followed if the system is to
be taken out of service for an extended period of time (i.e.
seasonal shutdown):
1. Test the unit for refrigerant leaks and repair as necessary
2. Open the electrical disconnect switches for the chilled-
water pump. Lock the switches in the “OPEN” position.
3. Close all chilled-water supply valves. Drain the water
from the evaporator.
4. Open the unit main electrical disconnect and unit-
mounted disconnect (if installed) and lock in the “OPEN”
position.
5. At least every three months (quarterly), check the
refrigerant pressure in the unit to verify the refrigerant
charge integrity.
CAUTION!
Lock the chilled-water pump disconnects open
to prevent pump damage. Lock the disconnect switch in
the “OPEN” position to prevent accidental startup and
damage to the system when it has been set up for extended
shutdown.
During an extended shutdown period, especially over the
winter season, the evaporator and free cooling circuits
must be drained of water, if the chilled water loop does not
contain glycol, to prevent any risk of evaporator freeze-up.