background image

 

TAM8­22

ALERT CODES FOR *AM8

Alert 

Code

Alert Group

Display 

Assembly Text

A/TCONT900

A/TZONE 950

Notification 

Level

AFC 

Fault 

Code

EVC 

Fault 

Code

EHC 

Fault 

Code

HHC 

Fault 

Code

Alert Description

Possible Cause

18

Control failure

CNTRL FLT

ERR18

ERR 18.0

Critical

ON

Internal Control Error

Control fault, replace AFC 

19

Twinning fault

TWIN ERR

ERR19

ERR 19.0

Information

8

Air handler twinning error

More than one ID unit connected on the 

communicating bus is not allowed

52

Indoor air sensor error

ICAS OPEN

N/A

N/A

Information

6

Indoor air sensor is open

Sensor open, unplugged, wiring harness

52

Indoor air sensor error

ICAS SHORT

N/A

N/A

Information

6

Indoor air sensor is shorted

Sensor shorted, wiring harness

90

Communication busy fault

SYS COM CRC

N/A

N/A

Information

3

Excessive communication errors

R & B to thermostat reversed polarity

91

Communication inactive fault

SYS COMM 

ERR

ERR91

ERR 91.02

Critical

3

Loss of Heat/Cool demand message

Open / Shorted data line / CCM 

communication error

91

Communication inactive fault

NO SYS CLK

ERR91

ERR 91.03

Critical

3

Loss of Bit Master

Control fault, replace AFC 

92

Fuse failure

CHECK FUSE

N/A

N/A

Critical

1*

24V fuse open error

24VAC circuit short

104

Heater relay fault

EH RLY 

OPEN#

ERR104

ERR 104.0

User Display

12

2

Heater relay stuck open error

Heater relay failure

104

Heater relay fault

ALL RLY OPEN

ERR104

ERR 104.02

Critical

12

2

All heater relay stuck open error

Heater relay failure

104

Heater relay fault

EK RLY 

WELD#

ERR104

ERR 104.01

Critical

12

3

Heater Relay Stuck Closed Error

Heater relay failure, open element, open 

non cycling limit switch

105

Heater interlock relay fault

BL INTLK OP

ERR105

ERR 105.0

User Display

12

8

Interlock Relay Stuck Open Error

Blower interlock relay failure

105

Heater interlock relay fault

BL INTLK CL

ERR105

ERR 105.01

User Display

12

8

Interlock Relay Stuck Closed Error

Blower interlock relay failure

106

External shutdown fault

EXT SW OPEN

ERR106

ERR 106.0

User Display

1

External shutdown input open error

External float switch, other device open 

114

PM bad or missing fault

PM DATA ERR

N/A

N/A

Information

2

PM data corrupt (Operation allowed)

PM error

114

ID motor error

ID MTR ERR

ERR114

ERR 114.02

User Display

2

Motor HP is < than PM value (Operation 

not allowed)

Incorrect VS motor or PM installed

114

PM bad or missing fault

PM MISSING

ERR114

ERR 114.03

Critical

2

PM missing with good local copy 

(Operation allowed)

PM error

114

PM bad or missing fault

PM UNIT ERR

N/A

N/A

Information

2

Bad data in PM with good local copy 

(Operation allowed)

PM error

114

PM bad or missing fault

PM MEM ERR

ERR114

ERR 114.05

Critical

2

Bad data in PM with no local copy  

(Operation allowed)

PM error

114

PM bad or missing fault

PM MISSING

ERR114

ERR 114.06

Critical

2

PM missing with no local copy (Operation 

not allowed)

PM error

114

ID motor error

MTR PWR HI

ERR114

ERR 114.07

User Display

2

Motor HP is > than PM value (Operation 

allowed)

Incorrect VS motor or PM installed

123

Demand configuration fault

EH CONFIG

ERR123

ERR 123.0

User Display

12

6

Electric heat configuration rrror

KW jumper position on PARK 

(replacement control only)

152

Heater element fault

EH ELMNT 

OP#

ERR152

ERR 152.0

User Display

12

4

Heater element open

Low airflow, dirty coil/filter

153

Thermal limit switch fault

EH CTCO TRIP

ERR153

ERR 153.0

User Display

12

5

Cycling thermal cut-out trip has occurred

Low airflow, dirty coil/filter

154

EH airflow limit fault

EH OFF/NO AF

ERR154

ERR 154.0

Critical

12

7

Electric heat control locked out because of 

insufficient airflow

EHC locked out

154

EH airflow limit fault

EH LIM/NO AF

ERR154

ERR 154.1

User Display

12

7

Electric heat control is under restricted 

operation because of insufficient airflow

Heater-Air handler mismatch

155

Indoor electronic expansion valve 
motor fault

EEV MTR ERR

ERR155

ERR 155.0

User Display

11

5

EEV motor fault has been detected for 8 

consecutive times and valve is locked out

Faulty EEV motor / wiring harness

155

Indoor electronic expansion valve  
motor fault

EEV MTR ERR

ERR155

ERR 155.01

User Display

11

1

EEV electric motor current indicates open 

or short

Faulty EEV motor / wiring harness

156

System low on charge fault

SYSTEM1  

ERR

ERR156

ERR 156.0

User Display

11

7

System 1 - High superheat

System low on charge, liquid line 

restriction, ET/GT sensor calibration

157

Condensate fault

CONDESAT 

FLT

ERR157

ERR 157.0

Critical

11

11

Condensate overflow condition detected

Condensate line clogged

158

Coil freeze fault

ID COIL FRST

ERR158

ERR 158.0

User Display

11

13

Indoor coil freeze condition detected

Low / incorrect airflow, low refirgerant 

charge, ET sensor calibration

159

Unit Bus fault 

AFC COMM 

ERR

ERR159

ERR 159.0

Critical

5

14

1

1

AFC communication error

Wire harness between AFC and 

distribution board 

EHC COMM

Wi

h

b t

EHC

d

159

Unit Bus fault

EHC COMM 

ERR

ERR159

ERR 159.01

User Display

5

1

EHC communication error

Wire harness between EHC  and 

distribution board 

159

Unit Bus fault

HHC COMM 

ERR

ERR159

ERR 159.02

User Display

5

1

HHC communication error

Wire harness between HHC  and 

distribution board 

159

Unit Bus fault

EVC COMM 

ERR

ERR159

ERR 159.03

User Display

5

14

EVC communication error

Wire harness between EVC  and 

distribution board 

159

Unit Bus fault

CDA COMM 

ERR

ERR159

ERR 159.04

Information

5

Display Assembly communication error

Wire harness between Display Assembly  

and distribution board 

160

Indoor EEV control configuration error

CONFIG FLT

ERR160

ERR 160.0

User Display

11

15

Configuration group index or evap 

temperature sensor type are not 

configured 

PM programming or internal 

communication error

161

Evaporator temperature sensor fault

ET SEN ERR

ERR161

ERR 161.0

User Display

11

3

Indoor coil temperature sensor reading is 

out of range, indicates open or short

Sensor open / shorted, unplugged, wiring 

harness problem 

161

Gas temperature sensor fault

GT SEN ERR

ERR161

ERR 161.01

User Display

11

4

Indoor coil temperature sensor reading is 

out of range, indicates open or short

Sensor open / shorted, unplugged, wiring 

harness problem 

163

Indoor EEV control fault

EEV CNTL FLT

ERR163

ERR 163.0

User Display

11

2

EEV electric motor drive or feedback or 12 

V failure detected 

EEV motor drive or motor feedback or 12v 

failure

164

Indoor EEV  fault

EEV CLSE 

ERR

ERR164

ERR 164.0

User Display

11

6

EEV migrated to 'Close' position but 

superheat is not at the desired set point, 

valve is not responding to a change in 

position

Possible stuck valve, ET/GT sensor 

calibration

164

Indoor electronic expansionvValve fault

EEV OPEN 

ERR

ERR164

ERR 164.01

User Display

11

6

EEV migrated to 'Open' position but 

superheat is not at the desired set point, 

valve is not responding to a change in 

position

Possible stuck valve, ET/GT sensor 

calibration

166

Superheat is flooding fault

SYSTEM4 ERR

ERR166

ERR 166.0

User Display

11

10

System 4 - Low superheat

Stuck valve, ET/GT sensor calibration, 

restricted distributor line that ET is 

connected to

167

Indoor electronic expansion valve 
control is not controlling because 
outdoor status is unknown

OD DATA MISS

ERR167

ERR 167.0

User Display

11

16

OD status unknown to EVC 

If Comm LED on OD unit is flashing the 

correct device count, replace AFC

outdoor status is unknown

,

p

168

Indoor heat demand is not available to 
hydronic heat control

HH FAULT 

ERR168

ERR 168.0

User Display

12

6

Hydronic Heat is not controlling because 

Indoor heat demand is not received

If Unit LED on HHC is flashing once every 

four seconds, replace HHC

169

Hydronic heat control configuration 
fault

HH CONFIG

ERR169

ERR 169.0

User Display

12

5

Hydronic heat capacity is unknown to 

hydronic heat control

Dip switch on HHC not set (replacement 

control only)

170

Hydronic heat control freeze condition 
detected

HH FRZ DET

ERR170

ERR 170.0

User Display

12

2

Hydronic heat coil freeze detected

Hydronic coil freeze inlet temperature 

sensor reading is less than 38ºF 

171

Communication inactive fault

BLW COMM 

ERR

ERR171

ERR 171.0

Critical

4*

Blower Communication is not detected

Faulty wiring harness, VS motor

172

Display Assembly stuck key

KEY FAULT

ERR172

ERR 172.0

User Display

Display Assembly has a stuck key

Faulty Display Assembly

173

Open coil freeze sensor (hydronic heat 
only)

HH FRZ OPEN

ERR173

ERR 173.01

User Display

12

4

Hydronic coil freeze inlet temperature 

sensor open condition detected

Sensor open, unplugged, wiring harness 

open 

173

Shorted coil freeze sensor (hydronic 
heat only)

HH FRZ 

SHORT

ERR173

ERR 173.0

User Display

12

3

Hydronic coil freeze inlet temperature 

sensor short condition detected

Sensor short, wiring harness shorted

Notes:
1.  * AFC STATUS LED will be solid ON during this fault

2.  COMM LED (amber) will flash the number of communicating devices connected
3.  BM LED should be ON Solid when power is applied
4.  STATUS LED will flash once per second in Idle mode. 
          Once a thermostat demand is received, it will flash 1 time/100 CFM requested 
5.  UNIT LED (blue) will flash once every four seconds when communications are norma

Summary of Contents for Hyperion AAM8A0A24V21CA

Page 1: ...RANTS OR REFRIGERANT SUBSTITUTES OR REFRIGERANT ADDITIVES WARNING LIVE ELECTRICAL COMPONENTS During instal lation testing servicing and troubleshooting of this product it may be necessary to work with...

Page 2: ...x 21 8 157 146 PRODUCT SPECIFICATIONS MODEL RATED VOLTS PH HZ RATINGS 1 INDOOR COIL Type Rows F P I Face Area sq ft Tube Size in Refrigerant Control Drain Conn Size in 2 DUCT CONNECTIONS INDOOR FAN Ty...

Page 3: ...TAM8 3 WIRING DIAGRAM FOR AM8 AIR HANDLERS 5 ET WIRING MAY BE BROWN OR ORANGE...

Page 4: ...3 The AFC sends a command to the serial communi cating blower motor to run proper airflow and close the blower interlock relay on the EHC 4 Humidifier contacts close 5 As demand from the thermostat i...

Page 5: ...s only operational during the cooling mode and is not operational during heating or defrost modes Note Standard aftermarket condensate switches Normally Closed can be wired in series with the External...

Page 6: ...Clear History selection and push the Enter key At the Are You Sure question push the Enter again Option 2 a Press and hold the Unit Test Button for 10 12 sec onds b Release the Unit Test button and wa...

Page 7: ...01 845 220 196 890 770 262 211 863 680 297 221 350 CFM ton CFM Watts 876 127 895 174 898 220 888 261 864 297 400 CFM ton CFM Watts 993 1070 178 215 1012 1023 231 236 1017 967 281 255 1009 901 327 270...

Page 8: ...103 100 812 668 145 112 803 463 186 115 788 NA 226 NA 430 CFM ton CFM Watts 868 73 871 116 869 161 864 205 853 248 450 CFM ton CFM Watts 904 993 80 99 910 896 126 122 911 775 173 136 907 621 219 141 8...

Page 9: ...01 961 184 177 1008 848 234 189 1011 731 282 196 420 CFM ton CFM Watts 1033 101 1046 152 1052 205 1060 257 1062 307 450 CFM ton CFM Watts 1100 1243 112 159 1114 1143 168 183 1127 1040 225 202 1136 933...

Page 10: ...7 204 1208 1220 212 229 1218 1115 276 246 1221 999 337 255 1215 868 393 256 400 CFM ton CFM Watts 1196 160 1209 225 1218 289 1219 349 1212 403 450 CFM ton CFM Watts 1343 1463 200 272 1361 1374 275 300...

Page 11: ...ton CFM Watts 1392 226 1400 293 1403 356 1400 413 1394 465 400 CFM ton CFM Watts 1583 1714 303 370 1595 1639 382 546 1601 1562 455 431 1600 1483 521 450 1593 1401 580 459 400 CFM ton CFM Watts 1586 3...

Page 12: ...417 350 CFM ton CFM Watts 1564 274 1578 348 1582 416 1578 476 1569 529 400 CFM ton CFM Watts 1770 1873 386 443 1784 1813 468 481 1789 1747 543 512 1788 1675 612 534 1781 1597 671 546 400 CFM ton CFM...

Page 13: ...1 Circuit 2 Minimum Circuit Ampacity Maximum Overload Protection AM8A0B30V21SA Heater Model No No of Circuits 240 Volt Note May be A or T Note Motor Amps 1 MCA and MOP for circuit 1 contains the motor...

Page 14: ...6 43 45 9 60 32800 40 0 55 60 7 20 24600 34 6 49 50 9 60 32800 40 0 50 50 7 20 24600 34 6 43 45 4 80 16400 20 0 25 25 3 60 12300 17 3 22 25 Heater Attribute Data AM8A0C48V41SA Minimum Circuit Ampacity...

Page 15: ...el No Outdoor Unit Model No Subcooling AM8A0B30V21CA 4A6H6024E 4TWX6024E 9 AM8A0C36V31CA 4A6H6036E 4TWX6036E 10 AM8A0C48V41CA 4A6H6048E 4TWX6048E 8 AM8A0B30V21CA 4A7A6024E 4TTX6024E 8 AM8A0C36V31CA 4A...

Page 16: ...To Internal Condensate Switch Optional GT Sensor See Table ET Sensor J7 Motor J10 STATUS LED FAULT LED UNIT LED FAULT UNIT STATUS STATUS LED WIRE TIE FAULT LED UNIT LED BM LED COMM LED TEST Unit Test...

Page 17: ...ED WIRE TIE FAULT LED UNIT LED BM LED COMM LED TEST Unit Test HUM J11 J6 24 VAC FAULT UNIT STATUS Y1 O D R B Y2 COMM BM Examples communicating thermostat communicating air cleaner etc AFC Fault LED De...

Page 18: ...LED Description OFF Standby 1 Stepper Motor or wiring harness has an open circuit or intermittent short 2 Control has detected an internal failure Verify EEV motor resistance and harness wiring 3 Satu...

Page 19: ...T LED BLUE LED EHC FAULT CODES RED LED EHC Fault LED Description OFF No fault 1 Internal communication error 2 Heat relay stuck open 3 Heat relay stuck closed 4 Non cycling limit NTCO or element open...

Page 20: ...4 D12 D15 D17 R48 R47 R46 R45 R44 MOV1 1 SW1 K1 AUX PGC PGD VSS VDD MCLR P3 C16 1 P4 X1 U3 U2 U1 R39 R37 R36 R35 R34 R33 R32 R31 R30 R29 R28 R27 R26 R25 R24 R23 R22 R20 R19 R18 R17 R16 R15 R14 R13 R12...

Page 21: ...C1 C17 C21 C26 C27 C29 C30 C31 C35 C41 C42 C43 C44 C45 C77 C78 C79 C83 CR1 CR2 CR3 CR4 CR5 CR6 CR9 CR10 CR26 CR42 CR43 CR50 CR51 CR52 CR53 D4 D19 1 1 LED3 LED4 LED5 P1 Q7 Q8 Q9 Q10 Q11 Q14 R1 R2 R26 R...

Page 22: ...ritical 11 11 Condensate overflow condition detected Condensate line clogged 158 Coil freeze fault ID COIL FRST ERR158 ERR 158 0 User Display 11 13 Indoor coil freeze condition detected Low incorrect...

Page 23: ...tiate requires a break and make to initialize To clear faults stored in memory apply a jumper between Close and Test pins for 10 seconds Open Valve Test Touch OPEN pin to TEST pin EEV drives open 5 se...

Page 24: ...42 2 4753 0 81 39 3 9 26166 2 56 110 43 3 4548 0 78 40 4 4 25452 2 52 112 44 4 4354 0 75 41 5 0 24761 2 49 114 45 6 4169 0 72 42 5 6 24090 2 45 116 46 7 3992 0 70 43 6 1 23440 2 42 118 47 8 3825 0 67...

Page 25: ...110 43 3 4548 1 032 36 2 2 28445 2 442 111 43 9 4450 1 016 37 2 8 27661 2 424 112 44 4 4354 1 001 38 3 3 26902 2 406 113 45 0 4260 0 986 39 3 9 26166 2 388 114 45 6 4169 0 971 40 4 4 25452 2 369 115...

Page 26: ...neously for 10 seconds o To Exit the technician menu section press the Up Down menu keys simultaneously for 10 seconds o To move to the top of any menu tree press the Left Right menu keys simultaneous...

Page 27: ...ts Only alerts with a notification level of User or Critical are shown same as the thermostat up to four 4 alerts will be shown most recent first Note 2 Alerts shown will be only AFC faults for initia...

Page 28: ...the different aspects of the system while the air handler is running No changes can be made in the Monitor Menu Superheat is only shown in cooling and defrost modes Airflow Data o The letters ESP Ext...

Page 29: ...orted it The abbreviations for the components are o AF Air Flow control o EV Expansion Valve control o EH Electric Heat control o HH Hydronic Heat control o DA Display Assembly The second line of text...

Page 30: ...ply Air Temperature Defrost Options o MIDCFT Mid Comfort When this option is selected electric heat will be turned on to maintain approximately 70 degree supply air tempera ture if enough electric hea...

Page 31: ...CFM Press Enter key to initiate control Unit must be in Standby or Idle mode o First value is current selection Second value is actual airflow o Use left or right menu keys to decrease or increase ai...

Page 32: ...nd OR OR Replace EVC Verify connections for sensors are plugged in and connected properly NO Start Here Do resistance readings match chart within 5 for the return air temperature Replace sensor s NO Y...

Page 33: ...below 30F Is indoor temperature 85F NO Perform CLOSE VALVE test at EVC YES Does suction pressure go down EEV and coil are working Replace EVC Check operation YES YES Perform temperature sensor check...

Page 34: ...Perform OPEN VALVE test at EVC Does suction pressure rise Replace EVC YES Replace EVC YES Replace EEV Check operation Ohm coil per FIG1 Is ohm reading correct YES Replace coil NO NO NO F B R Insure ID...

Page 35: ...TAM8 35...

Page 36: ...7 www trane com For more information contact your local dealer distributor 05 11 The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change de...