Installation
32
RT-SVX35H-EN
Shipping Fasteners
Removing Supply and Exhaust Fan Shipping
Channels (Motors >5Hp)
Each supply fan assembly and exhaust fan assembly for
W_HE (casings 2 through 6) units shipped with a motor
larger than 5 hp is equipped with rubber isolators, (as
standard), or optional spring isolators. Each supply fan
assembly and exhaust fan assembly for W_HE (casing 9)
unit is equipped with spring isolators. Shipping channels
are installed beneath each fan assembly and must be
remove. To locate and remove these channels, refer to
and use the following procedures.
1. Remove and discard the shipping bolts from the fan
assembly rails.
2. Elevate the fan-and-motor assembly and slide the
shipping channels out from between the fan assembly
rails and the unit's base rail.
3. Lower the fan-and-motor assembly onto the isolators.
Make sure that the pins at the top of the isolators are
engaged in the corresponding holes on the fan
assembly.
4. Verify that the fan assembly is being supported by the
isolators.
Figure 13. Removing fan assembly
shipping hardware — W_HE casings 2-6
Summary of Contents for IntelliPak WEHE Series
Page 15: ...General Information RT SVX35H EN 15 Figure 1 Unit component layout and ship with locations...
Page 17: ...Installation RT SVX35H EN 17 Figure 2 Typical control module location...
Page 44: ...Installation 44 RT SVX35H EN Figure 27 Typical field power wiring for W_HE casings 2 through 6...
Page 56: ...Installation 56 RT SVX35H EN Figure 32 Wiring notes for CV controls...
Page 60: ...Installation 60 RT SVX35H EN Figure 35 Wiring notes VAV...
Page 68: ...System Start up 68 RT SVX35H EN Figure 38 Typical fenwall ignition control system...
Page 69: ...System Start up RT SVX35H EN 69 Figure 39 Typical Fenwall ignition control system...