Installation
46
RT-SVX35H-EN
Figure 29. Customer connection wire range
Table 11. Electrical service sizing data for W_HE casings 2 - 9
Unit Component(s)
200/60/3, Nominal
(180-220V Utiliz.)
230/60/3, Nominal
(207-253V Utiliz.)
460/60/3, Nominal
(414-506V Utiliz.)
575/60/3, Nominal
(517-633V Utiliz.)
Electric Heat (WEHE Only):
FLA (1)
FLA (1)
FLA (1)
FLA (1)
30 Kw
83.3
72.2
36.1
28.9
50 Kw
138.8
120.3
60.1
48.1
70 Kw
194.3
168.4
84.2
67.4
90 Kw
249.8
216.5
108.3
86.6
110 Kw
305.3
264.6
132.3
105.9
130 Kw
-n/a-
-n/a-
156.4
125.1
150 Kw
-n/a-
-n/a-
180.4
144.3
170 Kw
-n/a-
-n/a-
204.5
163.6
190 Kw
-n/a-
-n/a-
228.5
182.8
Combustion Blower Motor
(WFHE Only):
FLA
FLA
FLA
FLA
235, 350, 500 MBh
2.1
1.8
0.9
0.7
850 & 1,000 MBh
2.8
2.4
1.2
1
Note:
“Full load amp” values shown for the electric heat were determined at 480 and 600 volts, respectively.
Summary of Contents for IntelliPak WEHE Series
Page 15: ...General Information RT SVX35H EN 15 Figure 1 Unit component layout and ship with locations...
Page 17: ...Installation RT SVX35H EN 17 Figure 2 Typical control module location...
Page 44: ...Installation 44 RT SVX35H EN Figure 27 Typical field power wiring for W_HE casings 2 through 6...
Page 56: ...Installation 56 RT SVX35H EN Figure 32 Wiring notes for CV controls...
Page 60: ...Installation 60 RT SVX35H EN Figure 35 Wiring notes VAV...
Page 68: ...System Start up 68 RT SVX35H EN Figure 38 Typical fenwall ignition control system...
Page 69: ...System Start up RT SVX35H EN 69 Figure 39 Typical Fenwall ignition control system...