Installation
52
RT-SVX35H-EN
Temperature vs. Resistance Coefficient
The UCM network relies on various sensors located
throughout the system to provide temperature
information in the form of an analog input. All of the
sensors used have the same temperature vs. resistance
co-efficient and are made from Keystone Carbon D97
material with a 1 degree Centigrade tolerance.
Occupied/Unoccupied Contacts (5K86)
To provide Night Setback control if a remote panel with
NSB (BAYSENS119*) was not ordered, a field supplied
contact (5K86) must be installed. This binary input
provides the Occupied/Unoccupied status information of
the building to the RTM. It can be initiated by a time clock,
or a Building Automation System control output. The
relay’s contacts must be rated for 12 ma @ 24 VDC
minimum. Refer to the appropriate illustrations in
connection terminals in the unit control panel.
Emergency Stop Switch (5S71)
A normally closed (N.C.) switch (5S71) wired to the RTM
may be used during emergency situations to shut down all
unit operations. When opened, an immediate shutdown
occurs. An emergency stop diagnostic is entered into the
Human Interface and the unit must be manually reset.
Refer to the appropriate illustrations in
or
for the proper connection terminals in the
unit control panel. The switch must be rated for 12 ma @
24 VDC minimum.
Outside Air Sensor (3RT3) - BAYSENS016A
This device senses the outdoor air temperature and sends
this information in the form of an analog input to the RTM.
It's factory installed on units with an economizer, but can
be field provided/installed and used for informational
purposes on units without an economizer. Refer to the
appropriate illustrations in
the proper connection terminals in the unit control panel.
Refer to Table 3-10 for Temperature vs. Resistance
coefficient.
Generic Building Automation System (1U51)
The Generic Building Automation System (GBAS) module
allows a non-Trane building control system to
communicate with the rooftop unit and accepts external
setpoints in form of analog inputs for cooling, heating,
demand limiting, and supply air pressure parameters.
Generic Building Automation System Module (GBAS 0-
5vdc) - Provided for those cases where non-Tracer building
management system is used. The GBAS module provides
a binary input for Demand Limiting, four (4) analog inputs
for setpoint adjustment and five (5) relay outputs for
diagnostic reporting. Inputs can use a potentiometer or 0-
5 vdc signal.
Generic Building Automation System Module (GBAS 0-10
vdc) - Used to provide broad control capabilities for
building automation systems other than Trane's Tracer™
system. The GBAS module provides a binary input for
Demand Limiting, four (4) analog inputs for setpoint
adjustment and four (4) analog outputs as well as one (1)
relay output for diagnostic reporting. Inputs can use a
potentiometer or 0-10 vdc signal.
Refer to
for the input wiring to the GBAS
module and the various desired setpoints with the
corresponding DC voltage inputs for both VAV and CV
applications.
For complete application details of the module, refer to
Engineering Bulletin UN-PRB001-EN.
Note:
Refer to wiring notes,
Table 15. Temperature vs. resistance coefficient
Temp
(°F)
Resistance
(in. 1000 Ohms)
Temp
(°F)
Resistance
(in. 1000 Ohms)
-40
346.1
71
11.6
-30
241.7
72
11.31
-20
170.1
73
11.03
-10
121.4
74
10.76
-5
103
75
10.5
0
87.56
76
10.25
5
74.65
77
10
10
63.8
78
9.76
15
54.66
79
9.53
20
46.94
80
9.3
25
40.4
85
8.25
30
34.85
90
7.33
35
30.18
100
5.82
40
26.22
105
5.21
45
22.85
110
4.66
50
19.96
120
3.76
55
17.47
130
3.05
60
15.33
140
2.5
65
13.49
150
2.05
66
13.15
160
1.69
67
12.82
170
1.4
68
12.5
180
1.17
69
12.19
190
0.985
70
11.89
200
0.83
Summary of Contents for IntelliPak WEHE Series
Page 15: ...General Information RT SVX35H EN 15 Figure 1 Unit component layout and ship with locations...
Page 17: ...Installation RT SVX35H EN 17 Figure 2 Typical control module location...
Page 44: ...Installation 44 RT SVX35H EN Figure 27 Typical field power wiring for W_HE casings 2 through 6...
Page 56: ...Installation 56 RT SVX35H EN Figure 32 Wiring notes for CV controls...
Page 60: ...Installation 60 RT SVX35H EN Figure 35 Wiring notes VAV...
Page 68: ...System Start up 68 RT SVX35H EN Figure 38 Typical fenwall ignition control system...
Page 69: ...System Start up RT SVX35H EN 69 Figure 39 Typical Fenwall ignition control system...