System Start-up
66
RT-SVX35H-EN
On Variable Air Volume systems, the sequencing time
delay relay (4DL6) will energize the combustion blower
motor relay (4K33) which switches the combustion blower
motor to high speed and energizes the 2nd stage solenoid
on the gas valve (4L7) after approximately 60 seconds.
If the flame rod (4U19) does not detect a pilot flame within
the 10 second trial for ignition period, the control will
lockout. If a flame failure occurs during operation, the gas
valve (4L7), the sequencing time delay relay (4DL6), and
the combustion blower relay (4K33) is de-energized. The
system will purge and attempt to relight the pilot. If a flame
is not detected after this attempt, the Honeywell ignition
control (4U18) will lock out. The combustion blower motor
will continue to operate as long as a heating demand
exists and the system switch (4S24) is "On".
Once the heating demand has been satisfied, the
combustion blower and the Honeywell ignition control
board (4U18) is de-energized.
Propane Gas
Units that operate on propane gas after 1990 have two (2)
additional controls that affect the combustion blower
motor operation and the sequence of the gas valve
operation.
With the post purge time delay relay (4DL4), the additional
service switch (4S24), and the additional 115 volt control
relay (4K31) installed, the sequence of operation is as
follows:
Power is applied to the Honeywell ignition control board
(4U18) through the high limit switch (4S26). The
Honeywell ignition control board (4U18) will sequence
through its prepurge timing and pilot ignition sequence to
The post purge time delay relay (4DL4) delays the starting
of the combustion blower motor by approximately 60
seconds. Once the timing has elapsed, the combustion
blower motor will start, closing the combustion air switch
(4S25).
Energize the control relay (4K31) and the sequence time
delay relay (4DL6). 24 volts is applied from the new service
switch (4S24) through the normally open control relay
(4K31) contacts to energize the 1st stage solenoid on the
gas valve (4L7).
On an additional call for heat, the K3 contacts on the Heat
Module will close to energize the combustion blower relay
(4K33) which switches the combustion blower motor to
high speed and closes its normally open contacts allowing
24 volts to energize the 2nd stage on the gas valve (4L7).
Once the heating demand has been satisfied, the
Honeywell ignition control board (4U18) and the post
purge time delay relay (4DL4) is de-energized. The
combustion blower motor will continue to operate for
approximately 15 seconds to purge the heat exchanger on
the "Off" cycle.
Modulating Gas Sequence of Operation
Full and Limited Modulating Gas Furnace
A typical electrical schematic for the modulating ignition
control system is illustrated in
. As you
review it and the sequence of operations, keep the
following in mind:
1. The furnace will not light unless the manual gas valves
are open and the control circuit switch 4S24 is closed.
2. The control systems are wired to ensure that heating
and cooling cannot occur simultaneously.
3. The unit supply fans must run continuously so air flow
switch 4S38 will stay closed.
4. Modulating Gas heat is available during both occupied
and unoccupied operation.
Whenever there is a call for heat, 1U50-K1 energizes and
combustion blower motor 4B11 begins to operate at High
speed on the 850 and 1000 MBH heaters. The blower will
operate on low speed for the 500 MBH. A relay 4K119 in
parallel with the main gas valve actuator control output,
insures the actuator will be open prior to proof of flame.
This will force the combustion air actuator 4U82 to the
open position, causing the auxiliary switch on 4U82 to
close. This insures complete purging of the combustion
chamber during the 60 second purge cycle.
Ignition control IC board 4U18 will not energize, however,
unless the supply air flow switch 4S38, combustion air
flow switch 4S25, high limit cutout 4S26, the auxiliary
switch on combustion air actuator 4U82 and the proof of
closure switch on gas valve 4L22 are closed. These are all
part of the safety interlock system.
With all these conditions satisfied, the IC board energizes
and initiates an internal 60 second prepurge time delay.
When the prepurge period expires, 4U18 energizes both
the ignition transformer 4T7 and solenoid 4L9 on the
intermittent pilot valve. At that point, 4U18 gives electrode
4E1 approximately 10 seconds to establish a pilot flame.
(The presence of this flame is proven by flame rod 4U19.)
If 4U18 does not detect a pilot flame at the end of this
period, it will shut down and lock out the ignition /
combustion circuit.
If the pilot is ignited within 10 seconds, the IC board de-
energizes the ignition transformer 4T7 and electrode 4E1.
At this point, relay 4K119 will energize, starting the
combustion air actuator and the furnace. The feedback
signal from the discharge temperature sensor will cause
the modulating output from the heat module to change the
damper position as required to maintain the outlet
temperature within the desired band.
Summary of Contents for IntelliPak WEHE Series
Page 15: ...General Information RT SVX35H EN 15 Figure 1 Unit component layout and ship with locations...
Page 17: ...Installation RT SVX35H EN 17 Figure 2 Typical control module location...
Page 44: ...Installation 44 RT SVX35H EN Figure 27 Typical field power wiring for W_HE casings 2 through 6...
Page 56: ...Installation 56 RT SVX35H EN Figure 32 Wiring notes for CV controls...
Page 60: ...Installation 60 RT SVX35H EN Figure 35 Wiring notes VAV...
Page 68: ...System Start up 68 RT SVX35H EN Figure 38 Typical fenwall ignition control system...
Page 69: ...System Start up RT SVX35H EN 69 Figure 39 Typical Fenwall ignition control system...