Dimensions and Weights
CLCH-SVX08C-EN
11
Dimensions and Weights
Service Clearances
A minimum clearance of the section width plus 12 inches
on the access door side of the gas heat section is
recommended for routine maintenance. This clearance
provides enough room to replace the heat exchanger in
the event of failure. The section side panels must be
removed to access the heat exchanger. Refer to
for service clearance recommendations for the air handler.
Figure 4. Service clearance for indoor units
Filter mixing box
Coil
Fan
Gas heat
Access
door
UV
lights
VFD
F
E
D
C
B
A
Table 3.
Service clearance dimensions (inches)
Component
3
4
6
8
10 12 14 17 21 22 25 26 30 31 35 36 40 41 50 51 57 66 80 100 120
A (filter)
48 48 48 48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
52
56
58
58
B (coil, humidifier) 48 59 59 66
77
82
87
87
95
77
95
77 109 87 115 96 128 96 141 110 141 156 156 170 197
C (UV Lights)
48 48 48 48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
52
56
58
58
C (TCACS)
43 59 59 63
75
81
83
83
58
75
58
75
83
83
75
59
83
83
83
83
83
83
83
75
83
D (external motor
control or low
voltage panel)
61 61 61 61
61
61
61
61
64
64
64
64
64
64
64
64
64
64
64
64
64
64
64
64
64
D (internal starter
or VFD)
48 48 48 48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
E (fan)
48 48 48 48
51
54
58
61
60
51
66
51
66
58
66
60
70
60
77
66
77
93
93 101 101
F (gas heat
Ext Vestibule)
n/a n/a 89 90 108 100 100 105 115 n/a 115 n/a 118 n/a 136 n/a 140 n/a 156 n/a 156 170 179 180 n/a
F (gas heat
Int Vestibule)
n/a n/a 56 63
74
79
84
84
92 n/a 92 n/a 106 n/a 112 n/a 125 n/a 138 n/a 138 153 153 167 194
Notes:
At a minimum, the above clearance dimensions are recommended on one side of the unit for regular service and maintenance. Refer to as-built
submittal for locations of items such as filter access doors, coil, piping connections, motor locations, hoods, pipe cabinets, etc. Sufficient clearance
must be provided on all sides of unit for removal of access panels, plug panels, or section-to-section attachment brackets. Clearance for starters,
VFDs, or other high-voltage devices must be provided per NEC requirements. For specific dimensional and weight information, refer to the unit
submittals. The dimensions and weights in this manual are approximate. Trane has a policy of continuous product and product data improvement
and reserves the right to change design and specifications without notice.