INSTALLER'S GUIDE

IMPORTANT:

 Wear appropriate gloves, arm sleeve protectors, 

and eye protection when servicing or maintaining this equipment.

IMPORTANT:

 Proper refrigerant charge and proper air flow are 

critical to achieve rated capacity and efficiency. Installation of 

this product should follow the manufacturer’s refrigerant charging 

and air flow instructions. 

Failure to confirm proper charge and 

airflow may reduce energy efficiency and shorten equipment 

life. 

IMPORTANT:

 Reconnect all grounding devices. All parts of this 

product capable of conducting electrical current are grounded. If 

grounding wires, screws, straps, clips, nuts, or washers used to 

complete a path to ground are removed for service, they must be 

returned to their original position and properly fastened.

CAUTION

!

CAUTION

!

CONTAINS REFRIGERANT!
SYSTEM CONTAINS OIL AND REFRIGERANT UNDER 
HIGH PRESSURE. RECOVER REFRIGERANT TO RELIEVE 
PRESSURE BEFORE OPENING SYSTEM. Failure to follow 
proper procedures can result in personal illness or injury 
or severe equipment damage.

CAUTION

!

RECONNECT ALL GROUNDING DEVICES.
All parts of this product that are capable of conduct-
ing electrical current are grounded.  If grounding wires, 
screws, straps, clips, nuts, or washers used to complete 
a path to ground are removed for service, they must be 
returned to their original position and properly fastened.

CAUTION

!

Hot Surface!

Do Not touch top of compressor. May cause minor to severe 

burning.

Unit contains R-410A Refrigerant!

R-410A operating pressure exceeds the limit of R-22. Proper 

service equipment is required. Failure to use proper service 

tools may result in equipment damage or personal injury.

SERVICE

Use only R-410A Refrigerant and approved POE com-

pressor oil.

These units use R-410A refrigerant which operates at 
50 to 70% higher pressures than R-22. Use only R-410A 
approved service equipment. Refrigerant cylinders are 
painted a “Rose” color to indicate the type of refriger-
ant and may contain a “dip” tube to allow for charging 
of liquid refrigerant into the system. All R-410A sys-
tems use a POE oil that readily absorbs moisture from 
the atmosphere. To limit this “hygroscopic” action, the 
system should remain sealed whenever possible. If a 
system has been open to the atmosphere for more than 
4 hours, the compressor oil must be replaced. Never 
break a vacuum with air and always change the driers 
when opening the system for component replacement. 
For specific handling concerns with R-410A and POE oil 
reference Retrofit Bulletins SS-APG006-EN and APP-
APG011-EN.

s

WARNING

Important: 

 Make sure to follow all safety precautions in the 

unit Installer's Guide. 

Important: Make certain that the unit has been installed in 

a level position to ensure proper draining. 

STEP 1

 - Recover refrigerant, disconnect power leads 

and remove mounting washers/nuts and set aside 
from the existing compressor. Also disconnect LPCO 
wires from the wire termination point. If a start kit is 
installed, remove it.

Section 2. Installation

CAUTION

!

If using existing refrigerant lines make certain that all joints 

are brazed, not soldered.