STEP 6

 - Braze, leak check with nitrogen, vacuum 

and recharge per data plate. 

STEP 7

 - Install new compressor power lead, 

LPCO wires, connect crankcase heater wires and 
secure any other wires that were moved during the 
compressor replacement. Replace run capacitor if 
required in parts notes.

Note

:  After and prior to start-up of the new com-

pressor, ensure that all piping and wiring are not in 
contact with the access panels when reinstalled.

Note:

 If discharge line vibration is an issue, order 

part numbers CMP01450 & BAR00178 (clamp and 
bar)

Note:

 If powered reverse rotation is a problem on 

single-phase units, order part number RLY03032 
(time delay relay). 

STEP 5

 - Set the new compressor, tighten the 

mounting nuts and use the Trane-supplied  
tubing connectors to dry-fit the pipes before  
brazing. Replace liquid line drier in the outdoor  
coil section of the unit. 