Pre-Installation Checklist
Complete the following checklist before
beginning unit installation.
Verify the unit size and tagging with
the unit nameplate.
Make certain the floor or foundation
is level, solid, and sufficient to support
the unit and accessory weights. See
the Dimensions and Weights section.
Level or repair the floor before
positioning the unit if necessary.
Allow minimum recommended
clearances for routine maintenance
and service. Refer to unit submittals
for dimensions.
Allow one and one half fan diameters
above the unit for the discharge
ductwork.
13a. If changing from horizontal discharge
to vertical (such as front/top to top/
front) then a duct extension will need
to be added to join the fan to the roof.
b.
On units without internal isolation the
duct extension is secured to the fan
housing with screws. The duct can be
purchased from Service Parts or can
be fabricated in the field.
c.
On units with internal isolation the
duct extension is wider at the bottom
to form a gap between and the fan
housing, which is bridged by a flexible
foam gasket. Contact Service Parts
for a duct extension kit. (See Fig. 1)
14a. If changing from vertical to horizontal
(such as top/front to front/top) then
the duct extension will need to be
replaced by mounting angles to join
the fan to the cabinet.
b. On units without internal isolation the
mounting angles can be secured to
the fan and to the cabinet with
screws. The angles can be purchased
from Service Parts or can be
fabricated in the field.
c.
On units with internal isolation the
mounting angles do not extend as far
and do not reach the cabinet panel.
The gap is bridged by a flexible foam
gasket. Also the gasket stays
compressed using a thrust restraint
assembly. Contact Service parts for
angle/gasket kit. (See Fig. 2)
15. Reattach roof
16. Reattach coil to roof support.
17. Reattach front/back panels
18. Reattach access doors.
Figure I-PC-5. Contact Service Parts for a Duct Extension Kit
Figure I-PC-6 Service PArts for Angle/Access Kits
Summary of Contents for LPC
Page 50: ...50 LPC SVX01C EN Operation general information Figure O GI 9 Tracer AH540 termination board ...
Page 91: ...LPC SVX01C EN 91 Maintenance diagnostics Table M D 2 Tracer AH540 541 diagnostics ...
Page 92: ...92 LPC SVX01C EN Maintenance diagnostics Table M D 2 continued Tracer AH540 541 diagnostics ...
Page 94: ...94 LPC SVX01C EN Maintenance troubleshooting Table M T 2 Valves stay open ...
Page 95: ...LPC SVX01C EN 95 Maintenance troubleshooting Table M T 3 Valves stay closed ...
Page 96: ...96 LPC SVX01C EN Maintenance troubleshooting Table M T 4 Outdoor air damper stays open ...
Page 97: ...LPC SVX01C EN 97 Maintenance troubleshooting Table M T 5 Outdoor air damper stays closed ...
Page 107: ...LPC SVX01C EN 107 Maintenance appendix Table M A 6 Hard wired CO2 sensor values ...
Page 109: ......