52
LPC-SVX01C-EN
Operation
general
information
To install the stand-alone operator
display:
1.
Unsnap the gray plastic backing from
the operator display.
2.
Carefully disconnect the operator-
display cable from the connector
inside the operator display.
3.
Use the plastic backing as a template
to mark the position of the four
mounting holes on the mounting
surface. See Figure O-GI-12.
4.
Set the plastic backing aside and drill
holes for #8 (4 mm) screws or #8 wall
anchors.
5.
Secure the plastic backing to the wall
with #8 (4 mm) mounting screws
(not supplied).
6.
Connect the operator-display cable to
the operator display, then snap the
operator display to the plastic
backing. The operator-display cable is
keyed to the connector. If you have
difficulty connecting it, make sure the
key is lined up with the slot.
7.
Run the operator-display cable to the
Tracer AH540/541, affixing it to the
wall with wiring staples or wire mold.
Do not run operator-display cable in
the same wire bundle with high-
voltage power wires. Running input/
output wires with 24 Vac power wires
is acceptable.
8.
Feed the cable into the Tracer AH540/
541 enclosure.
9.
Attach the operator-display cable to
the operator-display connector on the
circuit board (see Figure O-GI-13). The
operator display receives power
from the Tracer AH540/541 and turns
on automatically when it is connected
to the controller.
Figure O-GI-12. Stand-alone operator-display mounting holes
Summary of Contents for LPC
Page 50: ...50 LPC SVX01C EN Operation general information Figure O GI 9 Tracer AH540 termination board ...
Page 91: ...LPC SVX01C EN 91 Maintenance diagnostics Table M D 2 Tracer AH540 541 diagnostics ...
Page 92: ...92 LPC SVX01C EN Maintenance diagnostics Table M D 2 continued Tracer AH540 541 diagnostics ...
Page 94: ...94 LPC SVX01C EN Maintenance troubleshooting Table M T 2 Valves stay open ...
Page 95: ...LPC SVX01C EN 95 Maintenance troubleshooting Table M T 3 Valves stay closed ...
Page 96: ...96 LPC SVX01C EN Maintenance troubleshooting Table M T 4 Outdoor air damper stays open ...
Page 97: ...LPC SVX01C EN 97 Maintenance troubleshooting Table M T 5 Outdoor air damper stays closed ...
Page 107: ...LPC SVX01C EN 107 Maintenance appendix Table M A 6 Hard wired CO2 sensor values ...
Page 109: ......