Chiller Troubleshooting
ARTC-SVX002A-EN
69
5690
PU communication internal
Internal communication error.
Contact your local ABB representative.
5691
Measurement circuit ADC
Measurement circuit fault.
Contact your local ABB representative.
5692
PU board powerfail
Power unit power supply failure.
Contact your local ABB representative.
5693
Measurement circuit DFF
Measurement circuit fault.
Contact your local ABB representative.
5696
PU state feedback
State feedback from output phases does
not match control signals.
Contact your local ABB representative.
5697
Charging feedback
Charging feedback signal missing.
Check the feedback signal coming from
the charging system
6181
FPGA version incompatible
Firmware and FPGA versions are
incompatible.
Reboot the control unit (using
parameter
96.08 Control board boot) or by cycling
power. If the problem persists, contact
your local ABB representative
6306
FBA A mapping file
Fieldbus adapter A mapping file read
error.
Contact your local ABB representative.
6481
Task overload
Internal fault.
Reboot the control unit (using
parameter
96.08 Control board boot) or by cycling
power. If the problem persists, contact
your local ABB representative
6487
Stack overflow
Internal fault.
Reboot the control unit (using
parameter
96.08 Control board boot) or by cycling
power. If the problem persists, contact
your local ABB representative
64A1
Internal file load
File read error.
Reboot the control unit (using
parameter
96.08 Control board boot) or by cycling
power. If the problem persists, contact
your local ABB representative
64B2
User set fault
Loading of user parameter set failed
because
• requested set does not exist
• set is not compatible with control
program
• drive was switched off during loading.
Ensure that a valid user parameter set
exists. Reload if uncertain.
64E1
Kernel overload
Operating system error.
Reboot the control unit (using
parameter
96.08 Control board boot) or by cycling
power. If the problem persists, contact
your local ABB representative
6581
Parameter system
Parameter load or save failed.
Try forcing a save using parameter
96.07 Parameter save manually. Retry.
65A1
FBA A parameter conflict
The drive does not have a functionality
requested by PLC, or requested
functionality has not been activated.
Check PLC programming.
Check settings of parameter groups 50
Fieldbus adapter (FBA) and 51 FBA A
settings.
6681
EFB comm loss Programmable fault:
58.14 Communication loss action
Communication break in embedded
fieldbus (EFB) communication.
Check the status of the fieldbus master
(online/offline/error etc.).
Check cable connections to the
EIA-485/X5 terminals 29, 30 and 31 on
the control unit.
6682
EFB config file
Embedded fieldbus (EFB) configuration
file could not be read.
Contact your local ABB representative.
6683
EFB invalid parameterization
Embedded fieldbus (EFB) parameter
settings inconsistent or not compatible
with selected protocol.
Check the settings in parameter group
58 Embedded fieldbus.
6684
EFB load fault
Embedded fieldbus (EFB) protocol
firmware could not be loaded.
Contact your local ABB representative.
Version mismatch between EFB protocol
firmware and drive firmware.
6685
EFB fault 2
Fault reserved for the EFB protocol
application.
Check the documentation of the
protocol.
Code (hex)
Fault / Aux. code
Cause
What to do