This manual uses a typical 120-ton water-cooled chiller
consisting of four modules with brazed plate evaporators
for example purposes. The model number and a chiller’s
precise configuration can be found on the chiller model
nameplate. See
“Model Number and Coding,” p. 7
.
Table 9.
Typical Manhattan™ water-cooled chiller specification for example purposes
Chiller System (four 30-ton water-cooled chiller modules) Model # TPWCCMV0300D3-MM
Evaporator Type
brazed plate
Condenser Type
brazed plate
Evaporator Flow
300 gpm
Condenser flow
260 gpm
Evaporator Fluid
70/30 water/glycol
Condenser fluid
water
Entering Fluid Temperature
54 °F (12 °C)
Entering Fluid Temperature
85 °F (29 °C)
Leaving Fluid Temperature
44 °F (7 °C)
Leaving Fluid Temperature
95 °F (37.3 °C)
Evaporator Pressure Drop
4.4 psi
Condenser Pressure Drop
3.1 psi
Maximum Operating Pressure
650 psi (refrigerant side)
System Capacity
1,503,500 btu/hr. (120 tons)
Refrigerant
R410A
Connections
6 in. roll grooved
Chiller Modules (4)
Compressors
two per module
Rated Load Amps
48.4 amps each
Horsepower
15
Total Full Load Amps
96.8 amps per module
Locked Rotor Amps
340 amps
Electrical Power Supply
208/60/3
System
Total Full Load Amps
387 amps
Maximum Overcurrent Capacity
500 amps
Minimum Circuit Ampacity
394 amps
Dimensions
Each Chiller Module
24 W x 66 L x 77 H in.
(a)
Overall Chiller System
96 W x 66 L x 77 H in.
(b)
Weight
Each Chiller Module
1,600 lbs.
Overall Chiller System
6,400 lbs.
(a) Client module is 32 in. wide, including power distribution panel.