Installation - Electrical
CLCH-SVX013B-EN
59
Typical Wiring Schematics
Figure 80.
Typical VFD wiring schematic
31
1TB13-10
1TB13-9
30
1TB13-8
7
40
1F2
41
1TB13-6
A
B
27A,B
A
B
16A,B,C
Jumper
16C
1TB13-3
15
15A
Jumper
1TB13-5
1K42
1TB13-4
1S10 D
16
1K5
15
3
14
1TB13-7
2
6
A
14A
A
25A
1CB11
21A
1K40
1K41
+10V REF
COM(-)
1K40
26A
22A
1K41
28A
29A
23A,B
B
460V
18
8
1F1
1T1
15A
2B,C,D
3B,C
C
1B,C,D
C
The overload relay trip setting must be adjusted to
Correspond with the motor full load current as shown on
the motor nameplate.
Control transformer shown for 460V primary. For 200 or
230V or 575V refer to Inset A.
Relay(s)--contacts: silver-cadmium oxide: 1/6 hp 5 amp @ 120V
AC, 1/3 hp 5 amp @240V AC. See 24V schematic diagram for
coil connections and actual quantity of transformer relays.
Closes to run auto mode or bypass auto for option VFD or
starter.
Program terminal 27 inv. coasting stop.
Program terminal 18 as run.
The minimum circuit ampacity, the maximum fuse size, and
disconnect size are calculated based on the inverter input
line currents per article 430-2 of the National Electrical
Code.
All field wiring must be in accordance with the National
Electrical Code (NEC), state and local requirements. Other
countries applicable national and/or local requirements
shall apply. Field conductors shall have insulation
rating not less than 600v copper conductors only.
Dashed lines indicate recommended field wiring by others.
Phantom lines indicate control option.
Ref. Control panel schematic for specific detail.
JJS-60
JJS-80
JJS-90
JJS-100
FWP-125A
FWP-175B
100
125
50
40
75
60
575
460
200/230
Voltage
1F40
1F41
1F42
AFC Fuse
JJS-10
JJS-6
JJS-40
JJS-50
JJS-3
JJS-80
JJS-100
JJS-125
FWH-200B
FWH-250B
FWH-150B
JJS-60
JJS-15
JJS-20
JJS-30
JJS-35
JJS-45
125
2,3
1,1.5
5,7.5
10
15
25
20
30
100
15,20
50
75
60
25
40
30
JJS-10
JJN-125
JJN-80
JJN-25
JJS-30
JJN-15
JJN-20
JJN-10
Part No.
JJS-6
JJS-20
JJS-25
JJS-30
FWH-150B
FWH-200B
JJN-60
JJN-50
20
25,30
2,3
7.5
1,1.5
10
5
40
50
7.5
1,1.5
5
15
10
2
3
HP
Bussman Class T Drive Fuse Part No.
Device Prefix Location Code
Location
Air handler section
Low voltage panel (Unit schematic)
High voltage panel
3
2
1
Area
16
8
7
6
5
1
2
3
4
Notes:
3B1
1U5
1TB13
1S10
1T1
1OL
1K42
1K41
1K5
1K40
1K3
1U5
RUN
COM
+24VDC
REF IN
10L
A
D
12
A
A
55
53
27
18
INT
1F40
1F41
1F42
1TB13-1
1K42
B
C
15B,C,D
B
B
B
9A
8A
7A
L3
L2
L1
05
4
5
04
02
01
50VAC, 1A
Run signal
1F40,1F41,1F42
1F1,1F2
Drive
1CB11
Fault signal
240VAC, 2A
03
W/T3
V/T2
U/T1
1K41
13A
12A
1K41
1K41
11A
10A
B
B
B
D
D
D
5A,B
1K40
6A,B
1K40
4A,B
1K40
T2
A
1OL
T2
A
1OL
T3
T3
A
1OL
T1
16
T1
Splice
Splice
Splice
8
Supply fan
1PD1
5
6
4
7
3
1K3
2
1
8
L2
L3
L1
Customer
supplied
power
3
2
1
H4
H2
120V
H3
H1
X1
X2
M
3
24A
1K3
4
3
VFD
Auto
Bypass
OFF
Hand
1K42
1PD1
101E
102E
103E
12
12
If unit has shipping splits wiring will terminate to module at
each shipping split.
5
6
4
7
3
1K5
2
1
8
1K41
15AG
INSET A
1F1
40
41
1F2
41
1F1
40
1F2
X3
40
1F1
1F2
42
X2
X4
X1
X2
X1
X2
200V
1T1
X1
3B1
Supply
fan
number 1
Line
Voltage
Primary Transformer Fuses
Fuse Rating (AMPS) - 600V Class LP-CC Time Delay
Item
MFR.
MFR. Part NO.
Danfoss NO.
200
1F1,1F2 Bussman
FNQ-R-1.25
34046200
230
Bussman
FNQ-R-1.25
34046200
460
Bussman
FNQ-R-0.60
34046000
575
Bussman
FNQ-R-0.50
34053600
TAP SETTING
1F1,1F2
1F1,1F2
1F1,1F2
H2
H4
H3
H1
H4
H2
H3
H1
Tap setting
230V
1T1
Tap setting
575V
1T1
Tap setting
H2
H1
120
120
120
Attach ground or equipment ground.
27
27
2A
3A
1A
Customer
supplied
auto speed ref
Attach
earth
ground
To
Ret/Exh
fan
VFD circuit breaker
Control circuit primary fuse(s)
AFC fuse(s)
Supply fan start/stop relay
Supply fan low limit relay
Bypass contactor
Isolation contactor
Run permissive relay
Overload relay
VFD/OFF/Bypass Auto/Bypass hand switch
Primary transformer
Supply fan power distribution block
Terminal strip control circuit
Drive controller (AFC)
Supply fan motor
Legend
Description
Device
Designation
Summary of Contents for Performance Climate Changer PSCA
Page 81: ......