Figure 5.
Reinstall end panel
Installation – FIADMPR103*
10
ACC-SVN231A-EN
Factory Installed Damper (Field
Set-Up)
Downflow Configuration
To position damper for downflow operation, complete the
following steps:
WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could
result in death or serious injury.
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Verify that no power is
present with a voltmeter.
1. Remove filter access panel.
2. Remove the lower screws in the end panel. See
. Lay blockoff angle aside for later
installation.
Figure 6.
Remove lower screws
3. Do not remove the screws in the upper row of the end
panel.
4. Grasp the bottom of the end panel and pull the
economizer assembly outward into the operating
position. See
.
5. Remove approximately 3-inches of gasket material
from the bottom of each corner post to expose the
holes used to attach the economizer assembly to the
unit. See
.
6. With the screws provided, secure each side of the
economizer assembly by inserting a screw through the
clearance hole in the bottom of the corner post and into
the engagement hole in the economizer assembly.
Refer to
.
Figure 7.
Remove gasket material
Remove screws and lay blockoff
angle aside. Do not discard.
Blockoff Angle
Summary of Contents for Precedent FIADMPR102 Series
Page 14: ...Notes 14 ACC SVN231A EN...
Page 15: ...Notes ACC SVN231A EN 15...