Installation – FIADMPR102*

Uncrate the damper and locate all parts shown in 

Figure 1

.

Each damper ships with items 1, 2 and 3 attached. Remove 
screws completely from items 1 and 2. Remove item 3 by 
loosening the three screws but do not remove them. See 
figure below.

Figure 1.

Damper components

WARNING

Hazardous Voltage w/Capacitors!

Failure to follow instructions below could result in 
death or serious injury.

Power down the outdoor unit before making contact 
with the inverter circuit board. Follow proper lockout/
tagout procedures to ensure the power cannot be 
inadvertently energized.Wait for at least 15 minutes to 
allow the unit to fully discharge high DC voltage. 
Confirm the unit is fully discharged using a CAT III or IV 
voltmeter rated per NFPA 70E.

1. Remove unit end panel, retain the screws removed 

from the top of panel and the screws removed from 
bottom of panel for use later

2. To install the damper, lift into position by fitting the 

upper left hand corner around the channel in the 
cabinet post. Then pivot the damper into the opening 
in the cabinet. Refer to 

Figure 2, p. 6

.

3. Once the damper is in place, lift the damper and panel 

assembly to align the upper two screw holes. Secure 
the top by inserting two screws, top left 1 then top right 
2. Refer to 

Figure 2, p. 6

.

4. Pull out on the bottom of the damper and secure 

bottom left 3. Refer to 

Figure 3, p. 6

.

Figure 2.

Damper panel

5. Remove the filter access panel. Position the adapter 

backing plate inside the filter section. The adapter 
backing plate will slip over the three screws that were 
loosened in 

Figure 1, p. 6

. Align the screw engagement 

hole in the adapter backing plate, with the screw 
clearance hole in economizer side panel and secure 
lower right side of damper with screw four. Refer to 

Figure 2, p. 6

.

6. Install the bottom blockoff and secure with three 

screws. Refer to 

Figure 3, p. 6

.

Figure 3.

Bottom blockoff

1

2

3

Do not 
remove screws

Align (3) tabs on bracket 
with (3) slots in panel.
Pivot into place and
secure with three screws
engaged into damper
side panel.

Align (3) slots in panel
with (3) tabs on damper
side panel. Pivot panel
into place.

Adapter 
Backing Plate Panel

Bottom Blockoff

1

2

3

4

Summary of Contents for Precedent FIADMPR102 Series

Page 1: ...0 W D GS 150 300 SAFETY WARNING Only qualified personnel should install and service the equipment The installation starting up and servicing of heating ventilating and air conditioning equipment can b...

Page 2: ...hat is used in these service procedures In addition some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants Know the appl...

Page 3: ...cies those regulations supersede these policies Non Trane personnel should always follow local regulations Introduction ACC SVN231A EN 3 Copyright This document and the information in it are the prope...

Page 4: ...PR102 6 Factory Installed Damper Set Up 7 Downflow Configuration 7 General Information FIADMPR103 8 Inspection 8 Parts List 8 Installation FIADMPR103 9 Field Installed Damper 9 Factory Installed Dampe...

Page 5: ...rted within 15 days 4 If concealed damage is discovered stop unpacking the shipment 5 Do not remove damaged material from the receiving location Take photos of the damage if possible The owner must pr...

Page 6: ...around the channel in the cabinet post Then pivot the damper into the opening in the cabinet Refer to Figure 2 p 6 3 Once the damper is in place lift the damper and panel assembly to align the upper t...

Page 7: ...ntly energized Verify that no power is present with a voltmeter 1 Remove filter access panel 2 Remove bottom blockoff from its shipping location See Figure 4 p 7 Figure 4 Remove bottom blockoff 3 Remo...

Page 8: ...ed damage must be reported within 15 days 4 If concealed damage is discovered stop unpacking the shipment 5 Do not remove damaged material from the receiving location Take photos of the damage if poss...

Page 9: ...r lockout tagout procedures to ensure the power cannot be inadvertently energized Verify with a CAT III or IV voltmeter rated per NFPA 70E that all capacitors have discharged 2 Remove unit end panel r...

Page 10: ...d panel See Figure 6 p 10 Lay blockoff angle aside for later installation Figure 6 Remove lower screws 3 Do not remove the screws in the upper row of the end panel 4 Grasp the bottom of the end panel...

Page 11: ...assembly is in its operating position a Holding the blockoff angle with the holes at the bottom and the bottom angle outward tilt the top forward and insert it into the opening between the economizer...

Page 12: ...g for the required ventilation air use the Symbio service and installation mobile app or Symbio 700 on board UI to adjust the economizer minimum position setpoint BAS in the fresh return air settings...

Page 13: ...bus Common 1 2 3 24 VAC OUT Common IMC IMC 1 2 3 4 IMC Bus White P5 White BK R BL O 24 VAC OUT Common IMC IMC 1 2 3 4 TO UC P4 SHEET 3 1 2 3 4 Common Spare Universal IO 1 Alt 5 VDC OUT Common 5 VDC OU...

Page 14: ...Notes 14 ACC SVN231A EN...

Page 15: ...Notes ACC SVN231A EN 15...

Page 16: ...gn and specifications without notice We are committed to using environmentally conscious print practices Trane and American Standard create comfortable energy efficient indoor environments for commerc...

Reviews:

Related manuals for Precedent FIADMPR102 Series