40
- Leaving Water Temp. Cutout
Setpoint: Establishes a leaving chilled
water temperature, below which the
UCM will begin unloading
compressors and, if necessary,
terminate unit operation. See
discussion in “Leaving Water
Temperature Cutout”. See Table 15 for
proper settings.
41
- Low Refrigerant Temp. Cutout
Setpoint: Establishes a saturated
evaporator refrigerant temperature,
below which the UCM will begin
unloading compressors and, if
necessary, terminate unit operation.
See discussion in “Low Refrigerant
Temperature Cutout”. See Table 15 for
proper settings.
Table 15
Leaving Fluid Temperature Setpoints
Chilled
Leaving
Low
Water
Water Temp
Refrig Temp
Recommended ***
Solution Freeze
Setpoint - F
Cut out - F
Cut out - F
% Ethylene Glycol
Point - F
40
35
22
0
32
39
34
20
3
38
33
18
6
37
32
17
8
36
31
15
10
25
35
30
14
12
34
29
12
14
33
28
11
15
21
32
27
9
17
31
26
7
19
30
25
6
20
16
29
24
4
21
28
23
2
23
27
22
0
25
10
26
21
-1
26
25
20
-3
28
24
19
-5
29
23
18
-6
30
4
22
17
-8
31
21
16
-10
33
20
15
-11
34
19
14
-13
35
-3
18
13
-15
36
17
12
-17
37
16
11
-18
38
15
10
-19
39
14
9
-21
40
-11
13
8
-23
41
12
7
-24
42
11
6
-26
43
10
5
-27
43
9
4
-29
44
8
3
-31
45
-21
7
2
-32
46
6
1
-34
47
5
0
-35
47
4
- 1
-37
48
3
-2
-38
49
2
-3
-39
50
-32
1
-4
-39
50
0
-5
-39
50
***Recommended % Ethylene Glycol will give freeze protection consistent with other
chiller safety controls (solution freeze point is nominally 10 F above refrig temp cutout).
Summary of Contents for RTAA-130
Page 2: ... American Standard Inc 1991 ...
Page 8: ...8 RTAA IOM 3 ...
Page 24: ...24 RTAA IOM 3 ...
Page 50: ...50 RTAA IOM 3 Figure 30 Refrigerant Circuit Identification ...
Page 52: ...52 RTAA IOM 3 Figure 31 Remote Evaporator Piping Example ...
Page 59: ...59 RTAA IOM 3 Continued from Previous Page See Notes on Next Page ...
Page 63: ...63 RTAA IOM 3 Continued from Previous Page See Notes on Page 61 ...
Page 65: ...65 RTAA IOM 3 Continued from Previous Page See Notes on Page 61 ...
Page 76: ...76 RTAA IOM 3 ...
Page 92: ...92 RTAA IOM 3 Figure 51 Operator Interface Controls ...
Page 120: ...120 RTAA IOM 3 ...
Page 127: ...127 RTAA IOM 3 Continued from Previous Page 2307 1566C ...
Page 128: ...128 RTAA IOM 3 Figure 57 Unit Sequence of Operation RTAA 130 to 200 Tons 2306 9122A ...
Page 132: ...132 RTAA IOM 3 Figure 58 Operator s Log ...
Page 138: ...138 RTAA IOM 3 ...