background image

RTWB-SVN01B-E4

29

Pre-start checkout

General

When installation is complete, but
prior to putting the unit into service,
the following pre-start procedures
must be reviewed and verified:

[  ] Inspect all wiring connections to

be sure they are clean and tight.

W

WA

AR

RN

NIIN

NG

G

Disconnect all electric power,
including remote disconnects,
before servicing. Failure to
disconnect power before servicing
can cause severe personal injury or
death.

C

CA

AU

UT

TIIO

ON

N

Check the tightness of all
connections in the compressor
power circuit (disconnects, terminal
block, contactors, compressor
junction box terminals, …). Loose
connections can cause overheating
at the connections and
undervoltage conditions at the
compressor motor.

[  ] Verify that all refrigerant valves

are open.

C

CA

AU

UT

TIIO

ON

N

Do not operate the unit with the
compressor, oil discharge, or liquid
line valves closed. Failure to have
these open may cause serious
compressor damage.

[  ] Check the power supply voltage

to the unit at the main-power,
fused disconnect switch. Voltage
must be within the voltage
utilization range, given in Table 7
and also stamped on the unit
nameplate. Voltage  imbalance
must not exceed 2%

W

WA

AR

RN

NIIN

NG

G

Disconnect all electric power,
including remote disconnects,
before servicing. Failure to
disconnect power before servicing
can cause severe personal injury or
death.

[  ] Check the unit power phasing to

be sure that it has been installed
in an “ABC“ sequence.

W

WA

AR

RN

NIIN

NG

G

It is imperative that l1-l2-l3 in the
starter be connected in the A-B-C
phase sequence to prevent
equipment damage due to reverse
rotation.

[  ] Fill the evaporator and condenser

chilled-water circuits. Refer to
Table 2 for liquid capacities. Vent
the system while it is being filled.
Open the vents on the top of the
evaporator and condenser during
filling, and close them when
filling is completed

The use of improperly treated or
untreated water in this equipment
may result in scaling, erosion,
corrosion, algae, or slime. The
services of a qualified water
treatment specialist should be
engaged to determine what
treatment, if any, is advisable. The
Trane Company warranty specifically
excludes liability of corrosion,
erosion, or deterioration of Trane
equipment. Trane assumes no
responsibilities for the results of the
use of untreated or improperly
treated water or saline or brackish
water.

C

CA

AU

UT

TIIO

ON

N

Do not use untreated or improperly
treated water. Equipment damage
may occur

[  ] Close the fused disconnect

switch that supplies power to the
chilled-water pump starter and
the condenser pump starter.

[  ] Start the chilled-water pump and

condenser-water pump to begin
circulation of the water. Inspect
all piping for leakage and make
any necessary repairs.

[  ] With water circulating through

the system, adjust the water flow
and check the water-pressure
drop through the evaporator and
condenser. Refer to Tables 5 and
6.

[  ] Adjust the chilled-water flow

switch and the condenser-water
flow switch (if installed) for
proper operation.

[  ] Prove all interlock and

interconnecting wiring interlock
as described in section 3.

[  ] Check and set, as required, all

Clear Language Display menu
items.

[  ] Stop the chilled-water pump and

the condenser-water pump.

Unit Start-Up
Procedures

Summary of Contents for RTWB Helical-Rotary

Page 1: ...RTWB Helical Rotary Chillers 200 to 700 kW Sizes 207 224 RTWB SVN01B E4 Installation Operation Maintenance...

Page 2: ...c refer to national regulation RTWB SVN01B E4 Important Notice American Standard Inc 2001 Refrigerant emission control In respect of the environment all service operation must use recovery systems to...

Page 3: ...mometers Water pressure relief valves Flow sensing devices Refrigerant pressure relief valve venting Thermal insulation Installation Electrical General recommendations Power supply wiring Compressor m...

Page 4: ...tion and maintenance of RTWB units When the unit arrives compare all nameplate data with ordering submittal and shipping information A typical nameplate is shown in Figure 1 Figure 1 Typical unit name...

Page 5: ...r obvious damage to the unit or packing material Inspect the unit for concealed damage as soon as possible after delivery and before it is stored Concealed damage must be reported within 72 hours afte...

Page 6: ...ion of the unit Adaptive Control logic can correct these variables when necessary to optimize operational efficiencies avoid chiller shutdown and keep producing chilled water Compressor unloaders are...

Page 7: ...y and install valves in the water piping upstream and downstream of the evaporator and condenser water boxes to isolate the shells for maintenance and to balance and trim the system Supply and install...

Page 8: ...7 208 210 211 212 214 216 217 218 220 222 224 Evaporator type EG 120 EG 120 EG 140 EG 170 EG 170 EG 200 EG 200 EG 200 EG 250 EG 250 EG 340 EG 340 Condenser type CG 120 CG 120 CG140 CG 170 CG 170 CG 20...

Page 9: ...sulting from an improperly designed or constructed foundation Vibration eliminators Provide rubber boot type isolators for all water piping at the unit Provide flexible conduit for electrical connecti...

Page 10: ...t damage Connect an anti rotation strap between the lifting beam and the compressor before lifting the unit Failure to do so may result in personal injury or death if a lifting cable fails Installatio...

Page 11: ...l panel A vent is provided on the top of the evaporator at the return end Be sure to provide additional vents at high points in the piping to bleed air from the chilled water system Install necessary...

Page 12: ...e components and their general location are given above Entering chilled water piping Air vents to bleed air from system Water pressure gauges with shutoff valves Vibration eliminators Shutoff isolati...

Page 13: ...entage of load on the chiller Nevertheless it is required to maintain a minimum temperature differential of 18 C between the leaving chilled water temperature and the leaving condenser temperature Thi...

Page 14: ...ine or brackish water Figure 9 Cooling device bypass Cooling device bypass is also a valid control method if the chiller temperature requirements can be maintained 1 3 way valve or 2 2 way valves 2 Cu...

Page 15: ...Flow switches must stop or prevent compressor operation if either system water flow drops off drastically Follow the manufacturer s recommendations for selection and installation procedures General g...

Page 16: ...2844 653 408 959 258 279 854 1064 214 1898 1832 2844 653 408 959 258 279 854 1064 216 1898 1832 2844 653 408 959 258 279 854 1064 217 1898 1832 2844 653 408 959 258 279 854 1064 218 2008 1932 2952 59...

Page 17: ...denser water flow L s Condenser Code Pass Number Minimum Water Flow Maximum Water Flow Connection Diameter in CG 120 1 8 4 31 0 5 CG 140 1 9 5 34 9 5 CG 170 1 11 9 43 7 5 CG 200 1 17 0 61 0 5 CG 230 1...

Page 18: ...89 0 90 0 90 0 89 0 89 0 89 0 89 Fuse size 2 80A 100A 125A 60 125 160A 2 160 160 200 2 200 250 200 2 250 2 315 2 315 A 315 315 315 400 400 400 630 630 630 630 800 800 mm 240 240 240 240 240 240 2 300...

Page 19: ...iring in conduit to access opening s on the starter control panel Compressor motor phase sequencing Always verify that proper rotation of the RTWB compressors is established before the machine is star...

Page 20: ...11 Zone temperature sensor 6R3 or ice machine control 6S55 option 6R3 and 6S55 cannot be used together module A9TB1 1 2 12 External chilled water setpoint 4 20 mA or 2 10 V dc with communication inter...

Page 21: ...ls 1UTB3 3 and 4 would be a time clock ambient thermostat building automation system 2 UCM Pump Control Contacts Terminals A1TB4 8 and 9 This output is a set of contacts that will close starting the c...

Page 22: ...YES YES NO 7 2 YES YES YES 8 2 YES NO YES 9 3 YES NO NO 10 3 YES YES NO 11 3 YES YES YES 12 3 YES NO YES Notes MMR Machine Manual Reset CMR Circuit Manual Reset MAR Machine Auto Reset CAR Circuit Aut...

Page 23: ...l run normally when the contact is closed When the contact opens the unit will trip off on a manually resettable diagnostic This condition requires manual reset at the chiller switch on the front of t...

Page 24: ...ce building mode to be reentered until the unit has been switched out of ice building mode open 6S55 contacts and then switched back into ice building mode In ice building the current setpoint will be...

Page 25: ...V dc Current mA Resulting current limit setpoint RLA 2 0 4 0 40 3 0 6 0 50 4 0 8 0 60 5 0 10 0 70 6 0 12 0 80 7 0 14 0 90 8 0 16 0 100 9 0 18 0 110 10 0 20 0 120 Outdoor air temperature sensor This se...

Page 26: ...to the designated shield terminal at the Tracer module 3 Connect leads to terminals 1 and 2 ofTB2 of the module A9 of the UCM to theTracer There is no polarity requirement for the connection 4 At the...

Page 27: ...move and discard all shipping materials Install optional neoprene if required Level the unit and secure it to the mounting surface Unit water piping Flush all unit water piping before making final con...

Page 28: ...or 4 Oil separator 5 Electronic expansion valve 6 Oil cooler option 7 Low pressure switch 8 High pressure switch 9 Solenoid valve 10 Refrigerant charging valve 11 Oil separator draining valve 12 Oil c...

Page 29: ...be connected in the A B C phase sequence to prevent equipment damage due to reverse rotation Fill the evaporator and condenser chilled water circuits Refer to Table 2 for liquid capacities Vent the s...

Page 30: ...erative that L1 L2 L3 in the starter be connected in the A B C phase sequence to prevent equipment damage due to reverse rotation It is important that proper rotation of the compressors be established...

Page 31: ...e of refrigerant is indicated if the operating pressures are low and the subcooling is also low If the operating pressures superheat and subcooling readings indicate a refrigerant shortage gas charge...

Page 32: ...T TI IO ON N Lock the disconnects on the Open position to prevent accidental start up and damage to the system when it has been set up for extended shutdown At least every three months check the press...

Page 33: ...or unusual conditions Monthly maintenance Perform all weekly maintenance procedures Measure and record the system superheat Refer to the Start up procedure paragraph Measure and record the system subc...

Page 34: ...mperature differential between the entering and leaving condenser water and abnormally high condensing temperatures There are two accepted methods of cleaning the condenser tubes as discussed in the f...

Page 35: ...r the unit has been off for 10 minutes move the sight glass up and down until the level can be seen 4 After the level has been determined remove the sight glass and hoses Figure 15 System Oil Specific...

Page 36: ...ies are shown inTable 2 Pressure drop across the oil filter is shown in Figure 13 Oil filter pressure drop is the difference between the two pressure control ports Refrigerant filter change If the tem...

Page 37: ...rigerant oil 7 Install the cover plate and cover plate gasket Periodic Maintenance 8 Install a new copper gasket under the bolt head that had one at time of removal Replace all other bolts and tighten...

Page 38: ...ove the cover and the oil filter element 6 Install the new filter element 7 Coat the new cover gasket with refrigerant oil 8 Install the cover plate and cover plate gasket 9 Install a new copper gaske...

Page 39: ...1 Connect 110 V power to the female stepload solenoid and the male load unload solenoids This must be done to evacuate all of the cavities in the compressor 2 Open all service valves 3 Connect hoses f...

Page 40: ...tion by a specialist in our equipment Regular maintenance ensures that any malfunction is detected and corrected in good time and minimizes the possibility that serious damage will occur Finally regul...

Reviews: