11
UNT-PRC002-GB
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan
Power level in dB(A), per Hz frequency band
Overall power
Unit
speed
125
250
500
1000
2000
4000
8000
dB(A)
1
55
50
42
37
37
31
30
46
FWD 08
2
57
54
47
40
30
38
40
50
3
58
57
50
42
32
40
43
53
1
57
51
45
42
34
33
28
48
FWD 10
2
58
54
48
45
38
39
35
51
3
60
58
50
48
40
42
39
54
1
57
51
45
42
34
33
28
48
FWD 12
2
58
54
48
45
38
39
35
51
3
60
58
50
48
40
42
39
54
1
56
62
50
48
39
38
36
56
FWD 14
2
61
66
55
53
47
46
45
60
3
63
69
58
56
50
50
49
63
1
57
63
51
49
40
39
37
57
FWD 20
2
61
66
55
53
47
46
45
60
3
63
69
58
56
50
50
49
63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan
Power level in dB(A), per Hz frequency band
Overall power
Unit
speed
125
250
500
1000
2000
4000
8000
dB(A)
1
56
55
55
53
46
45
42
57
FWD 08
2
63
62
60
60
53
53
53
64
3
66
65
63
62
56
55
57
67
1
62
58
55
58
51
48
44
61
FWD 10
2
66
63
60
62
56
55
52
66
3
70
67
63
65
59
59
57
69
1
62
58
55
58
51
48
44
61
FWD 12
2
66
63
60
62
56
55
52
66
3
70
67
63
65
59
59
57
69
1
66
65
65
65
57
50
46
68
FWD 14
2
73
72
69
71
64
59
57
74
3
78
76
73
75
69
64
63
78
1
68
72
64
64
56
52
50
69
FWD 20
2
76
76
68
71
65
61
61
75
3
78
79
71
74
69
66
66
78
CG-SVX051A-GB
21
Unit size
080
090
100
110
130
Digit 56=2 EC fan
Max Power Input per Motor
kW
1.55
1.55
1.55
1.55
1.55
Max Amps per Motor
A
2.5
2.5
2.5
2.5
2.5
Motor RPM (Cooling mode)
rpm/min
780
810
850
900
950
Digit 56=3 EC fan HESP
Max Power Input per Motor
kW
1.82
1.82
1.82
1.82
1.82
Max Amps per Motor
A
2.9
2.9
2.9
2.9
2.9
Motor RPM (Cooling mode field setting)
rpm/min
720
750
790
840
880
Chilled Water Pump Package options
Single pump - Standard head pressure (digit 24=2)
Available Head Pressure (1)
kPa
125
126
112
157
151
Motor Power
kW
5.5
5.5
5.5
7.5
7.5
Rated Amps
A
11.0
11.0
11.0
14.4
14.4
Single pump - High head pressure (digit 24=4)
Available Head Pressure (1)
kPa
250
254
243
233
228
Motor Power
kW
11.0
11.0
11.0
11.0
11.0
Rated Amps
A
20.8
20.8
20.8
20.8
20.8
Dual pump - Standard head pressure (digit 24=1)
Available Head Pressure (1)
kPa
125
126
112
157
151
Motor Power
kW
5.5
5.5
5.5
7.5
7.5
Rated Amps
A
11.0
11.0
11.0
14.4
14.4
Dual pump - High head pressure (digit 24=3)
Available Head Pressure (1)
kPa
250
254
243
233
228
Motor Power
kW
11.0
11.0
11.0
11.0
11.0
Rated Amps
A
20.8
20.8
20.8
20.8
20.8
Optional Expansion Tank Volume
l
50
50
50
50
50
Max User water loop Volume for factory- mounted
expansion tank (1)
l
1750
1750
1750
1750
1750
Optional water Buffer tank volume
l
607
607
607
607
607
Hot Water Pump Package Options
Single pump - Standard head pressure (digit 59=2)
Available Head Pressure (1)
kPa
190
189
181
174
166
Motor Power
kW
3.0
3.0
3.0
3.0
3.0
Rated Amps
A
5.9
5.9
5.9
5.9
5.9
Single pump - High head pressure (digit 59=4)
Available Head Pressure (1)
kPa
321
321
313
306
297
Motor Power
kW
5.5
5.5
5.5
5.5
5.5
Rated Amps
A
10.5
10.5
10.5
10.5
10.5
Dual pump- Alternate running - Standard head pressure (digit 59=1)
Available Head Pressure (1)
kPa
Motor Power
kW
3.0
3.0
3.0
3.0
3.0
Rated Amps
A
5.9
5.9
5.9
5.9
5.9
Dual pump - Alternate running - High head pressure (digit 59=3)
Available Head Pressure (1)
kPa
321
317
341
301
293
Motor Power
kW
5.5
5.5
5.5
5.5
5.5
Rated Amps
A
10.5
10.5
10.5
10.5
10.5
Dual pump - Simultaneous running - Standard head pressure (digit 59=5)
Available Head Pressure (5)
kPa
159
157
143
135
127
Motor Power
kW
6.0
6.0
6.0
6.0
6.0
Rated Amps
A
11.8
11.8
11.8
11.8
11.8
Dual pump - Simultaneous running - High head pressure(digit 59=6)
Available Head Pressure (5)
kPa
290
289
274
267
257
Motor Power
kW
11.0
11.0
11.0
11.0
11.0
Rated Amps
A
21.0
21.0
21.0
21.0
21.0
Antifreeze protection option
Without any Water Pump Package
"Without chilled water and hot water pump
package (digit 24=X and digit 59=X)"
kW
0.66
0.72
0.72
0.82
0.92
Combinations without Hot Water Pump Package
With chilled water single pump and without
hot water pump package without buffer tank
(digit 24=2/4, digit 50=X digit 59=X)
kW
1.30
1.36
1.36
1.46
1.56
With chilled water dual and without hot water
pump package without buffer tank (digit
24=1/3, digit 50=X digit 59=X)
kW
1.36
1.42
1.42
1.5
1.6
With chilled water single pump and without hot
water pump package with buffer tank (digit
24=2/4, digit 50≠X digit 59=X)
kW
2.18
2.24
2.24
2.34
2.44
With chilled water dual pump and without hot
water pump package with buffer tank (digit
24=1/3, digit 50≠X, digit 59=X)
kW
2.24
2.30
2.30
2.40
2.50
Table 4 - General data CMAF 080-130 High Efficiency (Continued)
General Data