General Information

6

 CVRF-SVN005C-EN

Remove the existing chiller nameplate on the unit and relocate 
to the outside of the new control panel. Important information 
is contained on this existing nameplate that must be retained 
for future unit servicing. 

If nameplate cannot be removed and relocated, copy 
information from old nameplate onto new vinyl nameplate 
included in retrofit package.

Symbio™ Panel Conversion Kit 
Contents

Each Symbio™ panel conversion kit includes a pre-assembled 
control panel with a number of standard features and options 

installed, wired, bound, and tested, along with some device 
LLIDs shipped loose that require field installation and binding.
Before commencing the Symbio™ control retrofit, be sure to 
compare the data on the panel nameplate and ordering and 
shipping information to the data in the following tables to verify 
that the proper Symbio™ components were shipped. The 
tables are split into those components that are factory installed 
and those that are shipped loose and need to be field installed.
If an inspection of the conversion package reveals damage or 
material shortages, be sure to file these claims with the carrier 
immediately. Specify the extent of the damage or material 
shortages and be sure to notify the appropriate Trane 
representative. Do not install a damaged component or panel.

Table 2.

LLID legend and identification

(a)

 

LLID Name

Description

Part Number

Tracer® Adaptiview™ color display

MOD03183

LON

LonTalk

®

Communications interface for chillers

KIT18458, KIT; ECHELON MODULE FIELD INSTALL 
KIT

DAIO

Dual analog input and output

BRD04875

DBI

Dual low voltage binary input

BRD04873

DHVBI

Dual high voltage binary input

BRD04874

DRO

Dual relay output

BRD04878

HPRO

High power relay output

MOD01401

IGV

Inlet guide vane stepper actuator

ACT00680

Power supply

27 Vac to 24 Vdc for bus power supply

BRD02102

Pressure sensor

Low pressure range, 0 to 50 psia

TDR00733

Pressure sensor

High pressure range, 0 to 475 psia

TDR00734

Pressure transducer

Danfoss pressure transducer, 475 PSI 

7/16-20 NUF

TDR00735

QRO

Quad relay output

BRD04879

Starter module

Trane control board, starter module

BRD04877

Starter module power supply

110 Vac/24 Vdc power supply

PWR00147

Starter module on sub plate without power supply or LV 
PTs

Starter sub-panel for unit mount medium voltage 

starters

018504210100

Starter module on sub plate without power supply with 
LV PTs

Starter sub-panel for remote mount medium voltage 

starters

018504330100

Starter module on sub plate with power supply without 
LV PTs

Starter sub-panel for unit mount low voltage starters 018504220100

Starter module on sub plate with power supply and LV 
PTs

Starter sub-panel for remote mount low voltage 

starters

018504350100

AFD starter nodule on sub plate without power supply 
or LV PTs

Assembly for unit mount UCP2 AFDB, AFDC, and non-
communicating AFDH

018504340100

AFD starter nodule on sub plate with power supply 
without LV PTs

Assembly for remote mount UCP2 AFDB, AFDC, and 
non-communicating AFDH

018504370100

Temp sensor

Low range temperature sensor

SEN02133

Triac

Dual triac output

BRD04876

TWTI

Triple winding temperature input

MOD02462

Symbio™ controller

MOD02979

Summary of Contents for Symbio CVRF

Page 1: ...apart from the Symbio control panel SAFETY WARNING Only qualified personnel should install and service the equipment The installation starting up and servicing of heating ventilating and air condition...

Page 2: ...that is used in these service procedures In addition some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants Know the ap...

Page 3: ...his document and the information in it are the property of Trane and may not be used or reproduced in whole or in part without written permission Trane reserves the right to revise this publication at...

Page 4: ...Purge 21 PRGD PRGG and PRGF EarthWise Purge 21 LONTALK Option Installation 22 Communication Option Installation 22 Wi Fi Installation 22 Air Fi Installation 23 LTE Modem Installation 23 Communication...

Page 5: ...s before you attempt to perform the control system conversion Application Guidelines This Symbio control package is specifically designed to upgrade the controls of CVHE CVHF and CHVG water cooled chi...

Page 6: ...or chillers KIT18458 KIT ECHELON MODULE FIELD INSTALL KIT DAIO Dual analog input and output BRD04875 DBI Dual low voltage binary input BRD04873 DHVBI Dual high voltage binary input BRD04874 DRO Dual r...

Page 7: ...LID Name Description Part Number Table 4 Field installed LLIDs for various options DBI DHVBI DBO HPRO QRO DAIO LON IGV PS 475 PSI Temp Sensor PS 0 to 50 or 475 PSI Starter Module Color Display WiFi Ai...

Page 8: ...eplacement This is a partial list in addition to normal service tools and hardware Type A to Type B USB cable Computer having Tracer TU version 13 0 or newer Digital multi meter with phase detection c...

Page 9: ...ssure transducers on the copper oil lines Table 5 Fusing added for 2F1 2F2 and 2F3 as needed for optional PT transformers Voltage Vac Fuse A Voltage Vac Fuse A 200 1 600 1 230 1 2400 1 380 1 4200 1 46...

Page 10: ...None A 480 Vac or less B Greater than 600 Vac C 2300 2400 Vac D 3300 Vac E 4200 Vac F 6600 Vac 50 Hz Digit 10 11 Design Sequence A0 1st Design sequence Digit 12 Actuator 1 Stepper actuator 2 Pulse act...

Page 11: ...B Starter module with plate for low voltage remote starter C Starter module with plate for unit AFD D Starter module with plate for remote AFD E Starter module with plate for medium voltage unit star...

Page 12: ...trol panel disconnect switches and secure them in that position WARNING Hazardous Voltage w Capacitors Failure to disconnect power and discharge capacitors before servicing could result in death or se...

Page 13: ...1 to H2 If you have wired a temporary thermostat and 115 Vac power source to the oil heater leads wait to connect these wires until the Tracer AdaptiView retrofit is complete to avoid too much cooling...

Page 14: ...the control panel select the side that s most suitable for your specific application Note There is a production display arm bracket BRK04345 provided that where applicable can be mounted to the existi...

Page 15: ...es not spring up or sag down out of the position it is moved to by the operator CAUTION Tension in Display Support Arm Failure to follow instructions below could result in unexpected movement of the s...

Page 16: ...s labeled with loosen tighten or indicators Figure 7 Joint locations on the display arm 2 Joint 3 has a 6 mm hex screw controlling the tension on a gas spring which allows the Tracer AdaptiView displa...

Page 17: ...commended that existing bulb wells be used Installing new wells would necessitate opening the chiller to atmosphere WARNING Refrigerant under High Pressure Failure to follow instructions below could r...

Page 18: ...the hole in the strain relief Figure 10 Strain relief Option I O Installation Wire additional LLIDs as shown on schematics Pay careful attention to which LLIDs require low voltage inputs and which ar...

Page 19: ...bus on the chiller The Symbio retrofit kit includes a general wire kit that has several different types of wires An example of a wiring layout can be seen in Figure 12 p 20 Each application will vary...

Page 20: ...the correct cables so that you don t have any open plugs when finished Avoid placing wire ties directly over plug connectors This may press on the locking mechanism and over time the plugs may release...

Page 21: ...LID 3A6 will not be needed disconnect and remove 2 The condenser saturated refrigerant temperature LLID purge liquid temperature will not be needed disconnect and remove 3 The existing 120 27 Vac tran...

Page 22: ...N005C EN LONTALK Option Installation Symbio 800 system uses a U60 LON module through the USB connection instead of the LCI C LLID 1 Install the U60 LON module KIT18458 KIT ECHELON MODULE FIELD INSTALL...

Page 23: ...e 20 Air Fi wiring ref 50712738 LTE Modem Installation Modem part is MOD03184 MODULE CELLULARLE USB 2 9 METER CABLE Refer to provided literature for setup and operation details 1 Drill a 1 36 inch hol...

Page 24: ...tallation standard application need to field drill a 1 09 inch hole on side of box for a snap bushing This bush can be replaced as field straight connector and conduit 3 4 inch size as NEMA 4 applicat...

Page 25: ...re two transducer 0185 3475 0100 provided per heat exchanger Field connect by male to 2 female 1000mm branch cable CAB01147 which provided in package Figure 26 Standard accuracy option Mounting of Flo...

Page 26: ...ovided Meter Option The high accuracy customer provided meter option provides an analog input output LLID to monitor a customer provided high accuracy meter 0 10 Vdc or 4 20 mA outputs Rosemont etc Th...

Page 27: ...following Wire AWG From To 14B 16 1A29 J3 2 1X1 21 2K 16 1A29 J3 1 1X2 10 4 4 RED J11 1 J1 1 OPTIONALWA TER FLOW METE R CUSTOMER PROVIDE 4 20MA INPUT 1A21 DUAL ANALOG I O OPTIONA L INPUT 1 OUTPUT1 2...

Page 28: ...ent grade accuracy power volts and amps monitoring of Symbio controls installations It has 1 accuracy for measuring both real power and energy and reactive power and energy All data measured by the me...

Page 29: ...minated at the Modbus distribution terminal 1X3 beside Symbio 800 using the 3 poles connector which provide in energy meter kits Figure 36 Distribution terminal Figure 37 Modbus wiring ref 50712738 48...

Page 30: ...0 2T51 2T52 LINE 99 TO 1X3 WHT BLK WHT BLK WHT BLK RED BLK BLU YEL ORG BRN WHT 2F54 2F52 2F53 0 5A 0 5A 0 5A DETAIL A ENERGY METER OPTION NOT USED WB22 X1 X2 X1 X2 X1 X2 G MODBUS VOLTINPUTS L1 L2 L3 N...

Page 31: ...e start relay start capacitor and related wiring from Symbio panel and discard These items will not be used in this application 2 Wire oil pump contactor coil between terminals 1X1 14 and 1X1 6 as per...

Page 32: ...and 1X1 6 per schematic Figure 43 Refrigerant oil pump wiring ref 50712738 Installation of Oil Pump Motor Wiring and Terminals The CVRF installation will relocate the oil pump relay to the control pa...

Page 33: ...of the dry run test can be performed The pilot relay method must be used when the contactor coils are voltages other than 115 Vac If both direct control or pilot relay control can be used on your app...

Page 34: ...needed A description of the sub panel s types and uses is below Table 8 Sub panel types Model Digit 33 Application Part Number Description Starter Mount Type PTs Configuration Selection FACT FCOD E St...

Page 35: ...e and black leads on the sub panel in the order below Note If replacing a UCP2 starter module you can remove and discard the 27 VAC UCP2 starter module transformer as it is not required for the CH530...

Page 36: ...Figure 49 Pilot relay switching configuration Figure 50 Wye delta interlock and pilot relay wiring Starter Work 36 CVRF SVN005C EN...

Page 37: ...as follows 1 Remove existing UCP2 module keeping potential transformers and secondary current transformers if needed for reuse 2 Install existing potential transformers on lower panel if required and...

Page 38: ...to refer to the wiring diagrams listed in Wiring Diagram Matrix p 46 as you review the following instructions The wire numbers and component designations indicated in these steps appear in these figu...

Page 39: ...ications to starter module b For remote mount AFDs i Wire per schematic starter module will be powered by sub panel power supply ii Use existing communications cable to connect Symbio communications b...

Page 40: ...and its orientation The polarity dot should face incoming power in other words towards the disconnect Figure 55 Current transformer single turn down Wire the leads from the CT male quick connects to t...

Page 41: ...ordered secondary CTs In this case two CTs are used per phase to either achieve the necessary turn down or for metering convenience The first stage consists of either the X13580271010 TRR01287 X135802...

Page 42: ...600 05 00 600 2 5 1 432 336 504 TRR00451 TRR00975 700 05 00 700 2 5 1 504 384 576 TRR00451 TRR00975 800 05 00 800 2 5 1 576 480 720 TRR00451 TRR00975 1000 05 00 1000 2 5 1 720 480 720 TRR00655 TRR0097...

Page 43: ...Figure 57 Dual CT wiring example Starter Work CVRF SVN005C EN 43...

Page 44: ...ater than 600 Vac a large medium voltage PT is used to step from line voltage to 115 Vac and a second PT steps the voltage to less than 30 Vac The large PT is a three phase type except for the 6600 Va...

Page 45: ...ering the starter panel cabinet NOTICE Module Damage Failure to follow the following instruction could result in equipment damage Do NOT connect the secondaries of the line to 120 Vac potential transf...

Page 46: ...50710524 Primary Reactor CS 50710525 Auto X Former CS 50710527 Starter Subpanel VFD 50711536 Energy Meter Option 480V and Low 50712756 Energy Meter Option 575 and 600V 50712757 Energy Meter Option MV...

Page 47: ...Notes CVRF SVN005C EN 47...

Page 48: ...re committed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor environments for commercial a...

Reviews: