background image

Page 8

SEQUENCE OF OPERATION

GENERAL

Operation of the system cooling  and heating cycles is controlled by
the position of the system switch on the room thermostat. Once the
system switch is placed in either the HEAT OR COOL position, unit
operation is automatic. The optional automatic changeover thermo-
stat, when in the AUTO position, automatically changes to heat or
cool with sufficient room temperature change. Continuous fan
mode during cooling operation may not be appropriate in humid
climates. If the indoor air exceeds 60% relative humidity or simply
feels uncomfortably humid, it is recommended that the fan only be
used in the AUTO mode.

With the unit disconnect closed, voltage is supplied to the unit
control transformer and the crankcase heater (if provided).

COOLING — MECHANICAL COMPRESSOR CYCLE

On a call for mechanical cooling, the indoor fan “G” and the
compressor circuit “Y1” are energized. The indoor fan circuit “G”

starts with power from the control transformer and then energizes
the fan relay coil (F) 

and motor speed tap terminal

. This closes the fan relay (F) contacts and the indoor fan motor (IDM)
starts.

The compressor circuit starts with power from the control trans-
former through the thermostat switch “Y1” to the compressor
contactor (CC) coil. This closes the (CC) contacts and starts the
compressor (CPR) and the outdoor fan motor (ODM). When the call
for cooling is complete, the compressor contactor (CC), outdoor fan
motor (ODM), and indoor fan relay (F) is de-energized.

HEATING — ELECTRIC HEATERS

On a call for heat, power from the thermostat is received at “W1”,
which energizes the contactor coils. The contactor closes powering
the heater, provided all element limits are closed.

NOTE:

 The indoor thermostat must be configured to provide a “G”

signal to energize the indoor fan relay (F) during the heating mode.
The heater control circuit will not be energized unless the indoor fan
relay (F) is energized.

TROUBLESHOOTING CHART

SYSTEM

 

FAULTS

ELECTRICAL

REFRIGERANT CIRCUIT

P-PRIMARY CAUSES  S-SECONDARY CAUSES

Liquid Pressure Too high

Liquid Pressure Too Low

Suction Pressure Too High

Suction Pressure Too Low

Liquid Refrigerant floodback (TXV System)

Liquid Refrig. floodback (Cap. Tube System)

I. D. Coil Frosting

Compressor Runs Inadequate or No Cooling

Compressor & O.D. fan Do Not Start

Compressor Will Not Start But O.D. Fan Runs

O.D. Fan Won't Start

Compressor Hums But Will Not Start

Compressor Cycles on IOL

I.D. Blower Won't Start

Summary of Contents for TCK024B1

Page 1: ...CK030B1 TCK036B1 TCK042B1 WARNING HAZARDOUS VOLTAGE DISCONNECT POWER and DISCHARGE CAPACITORS BEFORE SERVICING Indicates a potentially hazardous situation which if not avoided could result in death or...

Page 2: ...s or other sources of contaminated air should not be near unit air inlet if outside air is to be introduced as a make up air 5 Check the handling facilities to insure the safety of personnel and the u...

Page 3: ...outside of the structure with at least 2 inches of insulation and weatherproof There must be a weath erproof seal where the duct enters the structure 4 Complete the installation according to the instr...

Page 4: ...32 70 72 32 70 72 139 70 308 441 17 3 8 413 16 1 8 WCK030B1 33 60 74 37 20 82 33 60 74 30 40 67 135 20 298 302 11 7 8 413 16 1 8 WCK024B1 38 60 85 34 92 77 29 02 64 32 20 71 135 20 298 0 413 16 1 8 T...

Page 5: ...Voltage variation should remain within the limits stamped on the unit nameplate DISCONNECT SWITCH Provide an approved weatherproof disconnect either on the side of the unit or within close proximity a...

Page 6: ...t run and then apply power by closing the system main disconnect switch This will activate the compressor sump heat Do not change the Thermostat System Switch until power has been applied long enough...

Page 7: ...tion Is the condensate line properly sized run trapped and pitched Is the filter of the correct size and number Is it clean and in place Is the wiring properly sized and run according to the unit wiri...

Page 8: ...e compressor circuit starts with power from the control trans former through the thermostat switch Y1 to the compressor contactor CC coil This closes the CC contacts and starts the compressor CPR and...

Page 9: ...ing electrical components and wiring for possible replacement and connection tightness condensate drain for cleaning unit duct connections to see that they are physically sound and sealed to the unit...

Page 10: ...lly this limited warranty will not apply unless the packaged unit is 1 installed by a licensed or qualified HVAC technician 2 applied and installed in accordance with the manufacturer s recommendation...

Page 11: ...t be obligated to pay for the cost of lost refrigerant No liability shall attach to Warrantor until products have been paid for and then liability shall be limited solely to the purchase price of the...

Page 12: ...s to record the following information to ensure your product registration process is quick and easy PackagedUnitSerialNumber_____________________________________________________ PackagedUnitModelNumbe...

Reviews: