12
BAS-SVX065E-EN
Typical Applications and Terminations
The following tables provide information about supported applications and termination wiring.
Table 4. UC400 controller typical applications
Waterside
Economizing
Hot Gas Reheat
Electric
Heat
Boiler-less
Heat Pump
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Cooling Only
X
X
X
X
X
X
X
X
X
X
The following table 1 lists 1 or 2 compressor control with discrete 1– or 2–speed fans based on
Trane GE units.
Table 5. Factory programmed terminations for Trane GE units
Inputs/Outputs/Communication
UC400/
UC400–
BController
Terminations
Factory Programmed Assumed Terminations
Analog Inputs
AI1
Space Temperature Local
AI2
Space Temperature Setpoint Local
AI3
Local Fan Mode Switch
AI4
Discharge Air Temperature Sensor
AI5
Entering Water Temperature Sensor
Universal Inputs
UI1
Relative Humidity Sensor or CO
2
Sensor
UI2
Leaving Water Temperature
Binary Inputs
BI1
Occupancy
BI2
Compressor 1 lockout status
BI3
Compressor 2 lockout status
Binary Outputs (Relay)
BO1
Fan High
BO2
Waterside Economizer
BO3
Fan Low