12

PUB. NO. 22-1802-03

Performance
Data

SW7

SW8

0.1

0.3

0.5

0.7

0.9

CFM

1003

1039

1062

1033

1034

Temp. Rise

58

56

54

56

56

Watts

125

182

246

309

356

CFM

1137

1193

1185

1197

1185

Temp. Rise

51

48

49

48

49

Watts

170

239

293

370

446

CFM

1262

1290

1327

1344

1331

Temp. Rise

46

45

44

43

43

Watts

218

286

366

440

534

CFM

1415

1454

1476

1500

1421

Temp. Rise

63

61

60

59

63

Watts

297

378

453

534

561

CFM

1645

1672

1701

1659

1456

Temp. Rise

54

53

52

54

61

Watts

435

539

632

671

580

CFM

1834

1857

1837

1686

1506

Temp. Rise

48

48

48

53

59

Watts

608

705

778

699

630

OFF

Medium**

ON

Airflow 

Setting

Dip Switch Setting

External Static Pressure

Low

High

Low

Medium**

ON

ON

ON

High

Heat

in

g

Heating 

1st Stage

Heating 

2nd 

Stage

OFF

OFF

ON

ON

OFF

*UD2D120AFV52A  Furnace Heating Airflow (CFM) and Power (watts) vs. External Static Pressure With Filter

OFF

OFF

SW1

SW2

SW3

SW4

0.1

0.3

0.5

0.7

0.9

CFM

1141

1197

1205

1196

1188

Watts

170

246

299

369

443

CFM

1325

1374

1403

1434

1412

Watts

252

332

408

496

567

CFM

1536

1575

1615

1619

1474

Watts

370

464

563

640

605

CFM

1334

1376

1424

1411

1417

Watts

251

330

415

469

562

CFM

1582

1628

1659

1663

1465

Watts

387

491

595

672

595

CFM

1813

1836

1838

1707

1504

Watts

577

684

771

710

620

CFM

1704

1731

1733

1735

1552

Watts

489

589

666

750

663

CFM

1960

1971

1937

1799

1602

Watts

739

841

891

813

700

CFM

2208

2107

1970

1849

1683

Watts

1080

1025

942

863

776

Notes:
1.  * First letter may be "A" or "T".
2.  ** Factory setting.
3.  Continuous Fan Setting:  Heating or cooling airflow is approximately 50% of selected cooling value.
4.  For variable speed low speed airflows are approximately 30% of listed values.
5.  LOW 350 cfm/ton is recommended for variable speed application for COMFORT & HUMID CLIMATE setting; NORMAL is 400 cfm/ton;
  HIGH 450 cfm/ton is for DRY CLIMATE setting.

Cooling

ON

ON

OFF

ON

OFF

OFF

OFF

*UD2D120AFV52A Furnace Cooling Airflow (CFM) and Power (Watts) vs. External Static Pressure With Filter

External Static Pressure

OFF

ON

OFF

ON

OFF

ON

OFF

OFF

OFF

ON

ON

ON

OFF

OFF

OFF

OFF

OFF

OFF

ON

OFF

5**

OFF

OFF

High (450 

CFM/ton)

ON

OFF

OFF

4

3.5

Low (350 

CFM/Ton)

Normal (400 

CFM/ton)

High (450 

CFM/ton)

ON

OFF

Airflow 

Setting

Normal (400 

CFM/ton)

Low (350 

CFM/Ton)

Normal (400 

CFM/ton)

High (450 

CFM/ton)

Dip Switch Setting

OFF

OFF

Unit 

Outdoor 

Low (350 

CFM/Ton)

Summary of Contents for TUD2B060AFV32A

Page 1: ...izontal 80 2 Stage Variable Speed Gas Fired Furnace with Whole House Air Cleaner PUB NO 22 1802 03 XV80i TUD2B060AFV32A TUD2B080AFV32A TUD2C080AFV42A TUD2B100AFV32A TUD2D120AFV52A 2009 Trane All Right...

Page 2: ...can be converted to L P gas INTEGRATED SYSTEM CONTROL Exclusively designed operational program provides total control of furnace limit sensors blowers gas valve flame control and includes self diagnos...

Page 3: ...pment Optional Equipment General Data TUD2B060AFV32A TUD2B080AFV32A TUD2C080AFV42A TUD2B100AFV42A TUD2D120AFV52A Performance Data Electric Data Field Wiring Diagrams Dimensions Contents 2 2 2 2 2 4 4...

Page 4: ...gauge aluminized steel heat exchanger Multi port In shot burners Complete front service access Alternate bottom left right return air Slide out blower assembly Hingedblowerdoor Perfect fit door catch...

Page 5: ...mostat Electronic Programmable 5 2 1 Stage Heating 1 Stage Cooling BAYSTAT340 Thermostat Heating Cooling Single Stage Mounts Vertically BAYSTAT305 Thermostat Electronic Programmable 2 Stage Heating 2...

Page 6: ...Variable SeeAirflow Table 1 2 Variable 115 1 60 Centrifugal Direct 2 1 100 2543 1727 115 1 60 0 70 0 40 Yes Whole House Air Cleaner 65 4Round Alum Steel Type 1 20 4 45 4 56 Redundant Two Stage Hot Su...

Page 7: ...Ignition Multi port In shot 6 115 1 60 15 3 20 1 2 H x W x D 41 3 4 x 26 1 2 x 30 1 2 40 x 24 1 2 x 28 1 2 193 181 UD2B100AFV32A Upflow Horizontal 65 000 52 000 100 000 80 000 40 70 Direct 10 x 7 1 V...

Page 8: ...137 198 259 316 361 CFM 831 883 915 935 941 Watts 122 182 238 292 345 CFM 1023 1052 1055 1061 1048 Watts 203 266 316 370 413 CFM 1156 1174 1188 1196 1085 Watts 280 351 415 482 442 CFM 1063 1094 1090...

Page 9: ...22 1111 1101 1083 Watts 269 317 361 405 442 CFM 1310 1295 1273 1246 1136 Watts 405 457 498 535 490 CFM 1458 1420 1369 1266 1154 Watts 569 599 606 561 506 CFM 1329 1310 1287 1253 1142 Watts 424 472 516...

Page 10: ...1334 1296 Watts 252 326 394 456 502 CFM 1167 1193 1208 1196 1193 Watts 190 255 321 378 443 CFM 1356 1378 1383 1358 1321 Watts 279 355 424 473 518 CFM 1521 1528 1537 1537 1344 Watts 379 545 534 606 55...

Page 11: ...atts 146 206 260 309 343 CFM 848 907 934 946 946 Watts 133 188 245 289 334 CFM 1018 1044 1055 1065 983 Watts 206 262 319 370 357 CFM 1139 1160 1184 1122 1020 Watts 274 344 411 417 386 CFM 1071 1089 11...

Page 12: ...563 640 605 CFM 1334 1376 1424 1411 1417 Watts 251 330 415 469 562 CFM 1582 1628 1659 1663 1465 Watts 387 491 595 672 595 CFM 1813 1836 1838 1707 1504 Watts 577 684 771 710 620 CFM 1704 1731 1733 1735...

Page 13: ...PUB NO 22 1802 03 WIRING DIAG WIRING DIAG WIRING DIAG WIRING DIAG WIRING DIAGRAMS FOR GAS FURNACES RAMS FOR GAS FURNACES RAMS FOR GAS FURNACES RAMS FOR GAS FURNACES RAMS FOR GAS FURNACES Electrical Da...

Page 14: ...22 1802 03 SCHEMA SCHEMA SCHEMA SCHEMA SCHEMATIC DIAGRAMS FOR GAS FURNACES TIC DIAGRAMS FOR GAS FURNACES TIC DIAGRAMS FOR GAS FURNACES TIC DIAGRAMS FOR GAS FURNACES TIC DIAGRAMS FOR GAS FURNACES Elect...

Page 15: ...s only for thermostats requiring connection to transformer common terminal 11 Optional humidistat is to be connected between R and BK Factory installed jumper R to BK on the circuit board must be cut...

Page 16: ...delays 9 Optional humidistat is to be connected between R and BK Factory installed jumper R to BK on the circuit board must be cut if optional humidistat is used The jumper must also be cut when apply...

Page 17: ...ER SEE NOTE 9 FIELD ADDED JUMPER W1 TO W2 2ND STAGE WILL FIRE 10 MINUTES AFTER 1ST B C B C TO 115 V 1 PH 60 HZ POWER SUPPLY PER LOCAL CODES HUM SEE NOTE 5 FIELD WIRING DIAGRAM FOR VARIABLE SPEED 2 STA...

Page 18: ...NOTE 9 W14 JUMPER SEE NOTE 9 From Dwg B342020 Rev 0 B C B C TO 115 V 1 PH 60 HZ POWER SUPPLY PER LOCAL CODES HUM SEE NOTE 5 FIELD WIRING DIAGRAM FOR VARIABLE SPEED 2 STAGE FURNACE 2 STAGE HEATING 1 ST...

Page 19: ...TRANSFORMER SEE NOTE 3 SEE NOTE 6 SEE NOTE 7 From Dwg B342018 Rev 0 B C B C TO 115 V 1 PH 60 HZ POWER SUPPLY PER LOCAL CODES HUM SEE NOTE 5 FIELD WIRING DIAGRAM FOR VARIABLE SPEED 2 STAGE FURNACE 2 S...

Page 20: ...IN INCHES MODEL DIM A DIM B DIM C DIM D DIM E UD2B060AFV32A UD2B080AFV32A UD2B100AFV32A 17 1 2 9 5 8 16 1 4 16 16 UD2C080AFV42A 21 13 1 16 19 3 4 19 1 2 19 1 2 UD2D120AFV52A 24 1 2 15 5 16 23 1 4 23...

Page 21: ...NOTES...

Page 22: ...Since Trane has a policy of continuous product improvement it reserves the right to change design and specifications without notice Trane 6200 Troup Highway Tyler TX 75707 www trane com...

Reviews: