Start/stop using terminal 18 and coasting stop using
terminal 27.
Par. 302
Digital input
=
Start
[7]
Par. 304
Digital input
=
Coasting stop inverted
[2]
For Precise start/stop the following settings are
made:
Par. 302
Digital input
=
Precise start/stop
[27]
Par. 304
Digital input
=
Coasting stop inverted
[2]
Pulse start using terminal 18 and pulse stop using
terminal 19. In addition, the jog frequency is activated
via terminal 29.
Par. 302
Digital input
=
Pulse start
[8]
Par. 303
Digital input
=
Stop inverted
[6]
Par. 304
Digital input
=
Coasting stop inverted
[2]
Par. 305
Digital input
=
Jog
[13]
Speed up/down using terminals 29/33.
Par. 302
Digital input
=
Start
[7]
Par. 303
Digital input
=
Freeze reference
[14]
Par. 305
Digital input
=
Speed up
[16]
Par. 307
Digital input
=
Speed down
[17]
Voltage reference via a potentiometer.
Par. 308
Analog input
=
Reference
[1]
Par. 309
Terminal 53, min. scaling
= 0 Volt
Par. 310
Terminal 53, max. scaling
= 10 Volt
104
TR1
2800
Series
VFD
Connection Examples
Start/Stop
Pulse Start/Stop
Speed Up/Down
Potentiometer Reference
Electrical Installation
Summary of Contents for VarioTrane TR1 2800 Series
Page 2: ...T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D 1 1...
Page 3: ...2 2 T TR R1 1 2 28 80 00 0 S Se er ri ie es s V VF FD D...
Page 4: ...TR1 2800 Series VFD 3...
Page 7: ...6 TR1 2800 Series VFD...
Page 87: ...Illustration 5 7 192H4719 Illustration 5 8 192H4720 86 TR1 2800 Series VFD...
Page 95: ...Branch Circuit Protection Short circuit protection 94 TR1 2800 Series VFD...
Page 107: ...All about TR1 2800 Series VFD 106 TR1 2800 Series VFD...