12
IPB-99-7-EN-10-6-99
Performance
Data Heating
English Units
WCC030FD00B AT 1000 CFM
O.D.
HEATING CAPACITY (BTUH/1000) AT
TOTAL POWER IN KILOWATTS AT
TEMP.
INDICATED INDOOR DRY BULB TEMP.
INDICATED INDOOR DRY BULB TEMP.
F.
60
70
75
80
60
70
75
80
-18
7.94
7.70
7.57
7.45
1.62
1.69
1.72
1.75
-13
9.10
8.83
8.69
8.55
1.70
1.77
1.81
1.84
-8
10.3
9.95
9.80
9.64
1.78
1.86
1.90
1.93
-3
11.4
11.1
10.9
10.7
1.86
1.94
1.98
2.02
2
12.6
12.2
12.0
11.8
1.94
2.03
2.07
2.12
7
13.8
13.3
13.1
12.9
2.02
2.11
2.16
2.21
12
14.9
14.5
14.2
14.0
2.10
2.20
2.25
2.30
17
16.1
15.6
15.4
15.1
2.18
2.29
2.34
2.39
22
18.0
17.4
17.2
16.9
2.26
2.37
2.42
2.47
27
19.9
19.3
19.0
18.7
2.34
2.45
2.50
2.56
32
21.8
21.1
20.8
20.4
2.41
2.53
2.59
2.65
37
23.7
22.9
22.6
22.2
2.49
2.61
2.67
2.73
42
25.5
24.8
24.4
24.0
2.57
2.69
2.76
2.82
47
30.5
29.6
29.1
28.7
2.66
2.79
2.85
2.91
52
32.9
31.9
31.4
30.9
2.73
2.87
2.94
3.00
57
35.4
34.3
33.7
33.2
2.81
2.95
3.02
3.09
62
37.8
36.6
36.0
35.4
2.89
3.04
3.11
3.18
67
40.2
38.9
38.3
37.7
2.97
3.12
3.19
3.27
72
42.6
41.3
40.6
39.9
3.05
3.20
3.28
3.35
CORRECTION FACTORS - OTHER AIRFLOWS
(VALUE AT 1000 CFM TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
870
1130
HEATING CAP.
X0.98
X1.02
COMPR. KW
X1.02
X0.98
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 1000 CFM
HEATING CAP. (HIGH TEMP.) = 29600 BTUH
HEATING CAP. (LOW TEMP.) = 15600 BTUH
COMPR. POWER (HIGH TEMP.) = 2195 WATTS
COMPR. POWER (LOW TEMP.) = 1695 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 3.12
COEFF. OF PERF. (LOW TEMP.) = 2.00
OUTDOOR FAN POWER = 250 WATTS
INDOOR FAN POWER = 340 WATTS
NOTE: RATED WITH 25 FEET OF 7/8
SUCTION AND 3/8 LIQUID LINE
WCC040FD00B AT 1325 CFM
O.D.
HEATING CAPACITY (BTUH/1000) AT
TOTAL POWER IN KILOWATTS AT
TEMP.
INDICATED INDOOR DRY BULB TEMP.
INDICATED INDOOR DRY BULB TEMP.
F.
60
70
75
80
60
70
75
80
-18
10.5
10.2
10.1
9.97
2.27
2.36
2.40
2.45
-13
12.1
11.7
11.6
11.4
2.35
2.45
2.49
2.54
-8
13.6
13.2
13.1
12.9
2.43
2.53
2.58
2.64
-3
15.1
14.7
14.5
14.3
2.51
2.62
2.67
2.73
2
16.6
16.2
16.0
15.8
2.58
2.70
2.76
2.82
7
18.2
17.7
17.5
17.3
2.66
2.79
2.85
2.91
12
19.7
19.2
19.0
18.7
2.74
2.87
2.94
3.01
17
21.2
20.7
20.4
20.2
2.82
2.96
3.03
3.10
22
23.8
23.2
22.9
22.6
2.93
3.07
3.15
3.22
27
26.4
25.8
25.4
25.1
3.04
3.19
3.26
3.34
32
29.0
28.3
27.9
27.5
3.14
3.30
3.38
3.46
37
31.6
30.8
30.4
30.0
3.25
3.42
3.50
3.58
42
34.2
33.3
32.9
32.4
3.36
3.53
3.62
3.70
47
40.5
39.4
38.9
38.3
3.48
3.66
3.75
3.84
52
43.7
42.5
41.9
41.4
3.59
3.78
3.87
3.96
57
46.9
45.6
45.0
44.4
3.70
3.89
3.99
4.09
62
50.1
48.8
48.1
47.4
3.81
4.01
4.11
4.21
67
53.3
51.9
51.2
50.4
3.92
4.13
4.23
4.33
72
56.5
55.0
54.2
53.5
4.03
4.24
4.35
4.46
CORRECTION FACTORS - OTHER AIRFLOWS
(VALUE AT 1325 CFM TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
1153
1497
HEATING CAP.
X0.98
X1.01
COMPR. KW
X1.02
X0.98
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 1325 CFM
HEATING CAP. (HIGH TEMP.) = 39400 BTUH
HEATING CAP. (LOW TEMP.) = 20700 BTUH
COMPR. POWER (HIGH TEMP.) = 2600 WATTS
COMPR. POWER (LOW TEMP.) = 1900 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 3.18
COEFF. OF PERF. (LOW TEMP.) = 2.06
OUTDOOR FAN POWER = 500 WATTS
INDOOR FAN POWER = 560 WATTS
NOTE: RATED WITH 25 FEET OF 7/8
SUCTION AND 3/8 LIQUID LINE
WCC050FD00B AT 1675 CFM
O.D.
HEATING CAPACITY (BTUH/1000) AT
TOTAL POWER IN KILOWATTS AT
TEMP.
INDICATED INDOOR DRY BULB TEMP.
INDICATED INDOOR DRY BULB TEMP.
F.
60
70
75
80
60
70
75
80
-18
14.3
13.9
13.8
13.6
2.94
3.06
3.12
3.18
-13
16.8
16.4
16.2
16.0
3.09
3.23
3.30
3.36
-8
19.4
18.9
18.7
18.4
3.25
3.40
3.47
3.55
-3
21.9
21.4
21.1
20.8
3.41
3.57
3.65
3.73
2
24.5
23.9
23.6
23.3
3.57
3.74
3.82
3.91
7
27.0
26.3
26.0
25.7
3.72
3.91
4.00
4.09
12
29.5
28.8
28.5
28.1
3.88
4.08
4.17
4.27
17
32.1
31.3
30.9
30.5
4.04
4.25
4.35
4.45
22
33.9
33.1
32.7
32.3
4.08
4.29
4.39
4.50
27
35.8
34.9
34.5
34.0
4.12
4.33
4.44
4.54
32
37.7
36.7
36.2
35.8
4.16
4.37
4.48
4.59
37
39.5
38.5
38.0
37.5
4.20
4.42
4.53
4.63
42
41.4
40.3
39.8
39.3
4.24
4.46
4.57
4.68
47
55.0
53.6
52.9
52.2
4.69
4.94
5.06
5.19
52
58.8
57.3
56.6
55.8
4.80
5.06
5.18
5.31
57
62.6
61.0
60.2
59.4
4.91
5.17
5.30
5.43
62
66.5
64.8
63.9
63.0
5.02
5.29
5.42
5.55
67
70.3
68.5
67.6
66.7
5.13
5.40
5.54
5.68
72
74.1
72.2
71.2
70.3
5.24
5.52
5.66
5.80
CORRECTION FACTORS - OTHER AIRFLOWS
(VALUE AT 1675 CFM TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
1457
1893
HEATING CAP.
X0.99
X1.01
COMPR. KW
X1.02
X0.98
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 1675 CFM
HEATING CAP. (HIGH TEMP.) = 53600 BTUH
HEATING CAP. (LOW TEMP.) = 31300 BTUH
COMPR. POWER (HIGH TEMP.) = 3760 WATTS
COMPR. POWER (LOW TEMP.) = 3065 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 3.18
COEFF. OF PERF. (LOW TEMP.) = 2.16
OUTDOOR FAN POWER = 500 WATTS
INDOOR FAN POWER = 680 WATTS
NOTE: RATED WITH 25 FEET OF 7/8
SUCTION AND 3/8 LIQUID LINE