CPSMC0100-210
Installation
-- Continued
Grounding the Media Converter
The CPSMC0100-210 single-slot chassis comes equipped with grounding lugs
located on the back panel. They require a grounding conductor wire
terminated with a two-hole, compression-type, grounding connector. The
grounding wire -- which must be a copper conductor -- is not included with
the chassis and must be provided by the customer/installer.
The electrical conducting path from the single-slot chassis must:
•
Flow via the grounding lugs to the common bonding network (CBN) for
telecom installations, or to an alternative approved grounding system
(if
required)
for non-telecom installations.
•
Be of sufficiently low impedance to conduct fault currents likely to be
imposed on the media converter, and
•
Enable proper operation of any over-current protection devices.
The conductor must be fastened to the grounding lugs with the enclosed anti-
rotation star-washers and lug-nut fasteners. The applied torque required to the
connector lug-nut fasteners is specified by the connector’s manufacturer.
To properly ground the CPSMC0100-210 single-slot chassis:
1.
Obtain one (1) grounding conductor
(12 AWG copper wire gauge or
larger)
with a two-hole, compression-type, grounding connector.
2.
Attach the grounding conductor to the converter by placing the two-hole
connector onto the grounding lugs and fasten with the enclosed lock-
washers / lug-nuts at the proper torque (per the manufacturer’s
specification).
3.
Attach the opposite end of the
grounding conductor to the
common bonding network
(CBN) for telecom, or to earth
ground (if required) for non-
telecom installations.
grounding lugs
earth ground
grounding
connector
and wire
3/4-inch
spacing
Grounding lugs
(6-32, 1/8" diam.)
12 AWG copper wire
(not included)
Star washer (included)
Lug nuts (included)
Two-hole, compression-type
grounding connector
(not included)
techsupport@transition.com -- Click the “Transition Now” link for a live Web chat.
5
Technical Specifications
For use with Transition Networks Model CPSMC0100-210 or equivalent.
Note:
The maximum power delivery capacity for the chassis slot is 12 Watts.
Compliance
EN55022; CISPR 22; Class A & B; CE Mark
Dimensions
6.086 x 5.875 x 1.5 in
(155 x 149 x 38 mm)
Weight 1.6
lbs.
(0.7 kg)
Approximately
Power Supply
12VDC, 1.25 A
(maximum)
MTBF
49,888 hours
(MIL217F2 V5.0) (MIL-HDBK-217F)
133,257 hours
(Bellcore7 V5.0)
Environment
Tmra*:
0 to 50°C
(32 to 122° F )
Storage Temp: -20 to 85°C
Humidity:
5 to 95%, non condensing
Altitude:
0 to 10,000 feet
Warranty
Lifetime
*Manufacturer’s rated ambient temperature.