P a g e
|
11
2.4
ENVIRONMENT REQUIREMENT
Item
Requirement
Machine Hall
Space
When user installs machine frame array in one machine hall, the distance
between 2 rows of machine frames should be 1.2~1.5m and the distance
against wall should be no less than 0.8m.
Machine Hall
Floor
Electric Isolation, Dust Free
Volume resistivity of ground anti-static material: 1X107~1X1010
,
Grounding current limiting resistance: 1M
(Floor bearing should be
greater than 450Kg/
㎡
)
Environment
Temperature
5~40
℃
(sustainable)
,
0~45
℃
(short time)
installing air-conditioning is recommended
Relative
Humidity
20%~80% sustainable 10%~90% short time
Pressure
86~105KPa
Door
&
Window
Installing rubber strip for sealing door-gaps and dual level glasses for
window
Wall
It can be covered with wallpaper, or brightness less paint.
Fire
Protection
Fire alarm system and extinguisher
Power
Requiring device power, air-conditioning power and lighting power are
independent to each other. Device power requires AC 110V±10%, 50/60Hz
or AC 220V±10%, 50/60Hz. Please carefully check before running.
2.5
GROUNDING REQUIREMENT
➢
All function modules’ good grounding is the basis of reliability and stability of devices. Also,
they are the most important guarantee of lightning arresting and interference rejection.
Therefore, the system must follow this rule.
➢
Grounding conductor must adopt copper conductor in order to reduce high frequency
impedance, and the grounding wire must be as thick and short as possible.