Introduction

Transtector’s AC Edge 240 is a compact (2U) 240Vac secondary power distribution panel featuring two, 240Vac single phase 60A 

input buses with dedicated neutrals.  The AC Edge provides power for a wide range of local or remote, wireless and wireline, data 

and mission critical communications applications.  The panel fits 19 in. or 23 in. racks (23 in. brackets sold seperately; need 2X of P/N 

2001-389).
The AC Edge supports the use of six breaker output positions per line.  Accepted breakers listed in the table on Page 14 range from 

1A to 10A with a UL classification of QVNU2.  5A and 10A breakers are available from Transtector, sold separately and installed by site 

personnel (see Page 14 for part numbers).
The front of the panel contains six LEDs: 

• 

One on each line (labeled PWR, the LED is green when power is supplied to the unit and off when no power is supplied)

• 

One on each line for tripped breaker indication (labeled FA, the LED is off during normal operation and red indicating a tripped 

breaker)

• 

One on each supression module (the LED is green when powered and functioning and red when powered and not functioning). 

Form C dry contacts on the rear provide connectivity via  a single 15-socket (female), D-type connector (HD-15) to remote audible/

visual alarm devices for announcing/displaying power, breaker, and bay failures. The supression modules can be replaced when 

required (only when the unit is not powered, see page 14 for instructions).
Input ground connection made via a two hole compression lug on the back of the chassis.  Chassis ground connection is tied to input 

ground.  All output connections are made via the IEC 320-C13 connectors on the back of the unit.

Summary of Contents for AC Edge 240

Page 1: ...Installation Manual 1101 1173 M REV H AC Edge 240 Dual Phase 60A 6 6 AC Power Distribution Unit Model AC240V60DF 6 6 P N 1101 1173...

Page 2: ...on Procedure Inspect Shipping Container Inspect Contents of Container Accessory Kit Installing Mounting Brackets Mounting Panel to Rack Ground Wiring Input Wiring Test Voltages and Alarms Outputs Brea...

Page 3: ...front of the panel contains six LEDs One on each line labeled PWR the LED is green when power is supplied to the unit and off when no power is supplied One on each line for tripped breaker indication...

Page 4: ...A output per phase and 10 A per output position L1 input feeds L1 outputs L2 input feeds L2 outputs Breaker Output Current 1 A to 10 A single pole hydraulic magnetic non delay slow trip breakers sold...

Page 5: ...7 kg Weight shipping 20 lbs 9 kg Chassis Dimensions Nominal without rack mounting brackets 3 47 H x 17 4 W x 13 5 D 88 mm x 442 mm x 342 mm Rack Mounting 2RU 19 per EIA Standard RS 310 D optional 23...

Page 6: ...priate consideration of equipment nameplate ratings should be used when addressing this concern Reliable Earthing Reliable earthing of the rack mounted equipment should be maintained Particular attent...

Page 7: ...carrier s representative be present during unpacking Note Transtector is not liable for damages incurred during shipping Inspect Contents of Container 2 During unpacking inspect panel for damage If d...

Page 8: ...Installation 8 Flat Washer 12 Panel to Rack Installation 4 Lock Washer 12 Split Panel to Rack Installation 4 Screw 12 24 x 5 Pan Head Phillips Panel to Rack Installation 4 19 Mounting Bracket Rack Mo...

Page 9: ...kg Take care to support the panel when installing panel to rack Two persons may be required in the following step 9 Mount panel to rack using two sets of supplied fasteners per side total of four 12 2...

Page 10: ...ound lug The ground lug is located just left of the access panel shown in Figure 3 12 Fasten lug to panel using the provided M6 KEPS nuts and flat washers Tighten to 50 55 inch pounds 6 2 Newton meter...

Page 11: ...position and NEUTRAL 2 to the 2nd position from the bottom of the input terminal block see Figure 4a and 4b To secure wires follow figure 4a 1 Strip wire to 18mm 0 70in 2 Fully insert wire into termi...

Page 12: ...L1 Power Alarm NC 10 L1 Suppression Status NO 3 L2 Power Alarm NO 11 L2 Suppression Status NC 4 L2 Power Alarm NC 12 L2 Suppression Status NO 5 L1 Fuse Alarm NO 13 Common 6 L1 Fuse Alarm NC 14 Common...

Page 13: ...installation of breakers ensure that circuit breakers are switched off 27 Install circuit breakers in the off position with ON letters oriented towards the top of the unit and OFF towards the bottom...

Page 14: ...and free the breaker see Figure 6 Figure 6 Removing a breaker Circuit Breakers The AC Edge 240 panel is compatible with single pole Carling Technologies M Series or AIRPAX SNAPAK series hydraulic magn...

Page 15: ...15 Transtector 2017 All Rights Reserved Dimensions...

Page 16: ...AWG YAV10 2TC14 8 AWG YA8CL 2TC14 LCD8 14A L 6 AWG YA6CL 2TC14 LCD6 14A L 4 AWG YA4CL 2TC14 LCD4 14A L 2 AWG YA2CL 2TC14 LCD2 14A Q Maintenance AC Edge 240 panels require no scheduled maintenance Ser...

Page 17: ...duct Transtector conveys no license under its patent rights or those of others Transtector reserves the right to change this product and this publication without notice Transtector Systems Inc 10701 A...