Installation Manual

 | 

AC Edge 240

4

Product Specifications

Electrical

Specification

Nominal Universal Voltage Range

220 Vac to 240 Vac

Frequency Rating

50 / 60 Hz

Input Rating

60 A, 250 Vac per phase, max

Input Interrupt Device

Not provided, building install must be capable of interupting up to a 60 A source.

Input Configuration

2 wire + PE ground each phase

Output Configuration

6, IEC 320-C13 outlets per phase (total of 12 positions not to exceed a total of 

60 A output per phase and 10 A per output position).  L1 input feeds L1 outputs, 

L2 input feeds L2 outputs.

Breaker Output Current

1 A to 10 A single-pole, hydraulic-magnetic, non-delay, slow-trip breakers (sold 

separately; see page 14 for breaker part numbers).

Output Wire Size

#18 AWG to #12 AWG, depending on output breaker rating

Alarm Indicators

Power L1, L2 LEDs (2): green for power on; off for power off/failure

Fuse Alarm LEDs (2): red for tripped breaker; off for normal operation

Surge LEDs (1 per module): green for good; red for failure

Alarm Relay Contacts

Dry Form C for power, fuse, and bay alarm failures

Relay Contact Rating

240 Vac, 1.5 A

Bay Relay Activation

12 Vdc

Summary of Contents for AC Edge 240

Page 1: ...Installation Manual 1101 1173 M REV H AC Edge 240 Dual Phase 60A 6 6 AC Power Distribution Unit Model AC240V60DF 6 6 P N 1101 1173...

Page 2: ...on Procedure Inspect Shipping Container Inspect Contents of Container Accessory Kit Installing Mounting Brackets Mounting Panel to Rack Ground Wiring Input Wiring Test Voltages and Alarms Outputs Brea...

Page 3: ...front of the panel contains six LEDs One on each line labeled PWR the LED is green when power is supplied to the unit and off when no power is supplied One on each line for tripped breaker indication...

Page 4: ...A output per phase and 10 A per output position L1 input feeds L1 outputs L2 input feeds L2 outputs Breaker Output Current 1 A to 10 A single pole hydraulic magnetic non delay slow trip breakers sold...

Page 5: ...7 kg Weight shipping 20 lbs 9 kg Chassis Dimensions Nominal without rack mounting brackets 3 47 H x 17 4 W x 13 5 D 88 mm x 442 mm x 342 mm Rack Mounting 2RU 19 per EIA Standard RS 310 D optional 23...

Page 6: ...priate consideration of equipment nameplate ratings should be used when addressing this concern Reliable Earthing Reliable earthing of the rack mounted equipment should be maintained Particular attent...

Page 7: ...carrier s representative be present during unpacking Note Transtector is not liable for damages incurred during shipping Inspect Contents of Container 2 During unpacking inspect panel for damage If d...

Page 8: ...Installation 8 Flat Washer 12 Panel to Rack Installation 4 Lock Washer 12 Split Panel to Rack Installation 4 Screw 12 24 x 5 Pan Head Phillips Panel to Rack Installation 4 19 Mounting Bracket Rack Mo...

Page 9: ...kg Take care to support the panel when installing panel to rack Two persons may be required in the following step 9 Mount panel to rack using two sets of supplied fasteners per side total of four 12 2...

Page 10: ...ound lug The ground lug is located just left of the access panel shown in Figure 3 12 Fasten lug to panel using the provided M6 KEPS nuts and flat washers Tighten to 50 55 inch pounds 6 2 Newton meter...

Page 11: ...position and NEUTRAL 2 to the 2nd position from the bottom of the input terminal block see Figure 4a and 4b To secure wires follow figure 4a 1 Strip wire to 18mm 0 70in 2 Fully insert wire into termi...

Page 12: ...L1 Power Alarm NC 10 L1 Suppression Status NO 3 L2 Power Alarm NO 11 L2 Suppression Status NC 4 L2 Power Alarm NC 12 L2 Suppression Status NO 5 L1 Fuse Alarm NO 13 Common 6 L1 Fuse Alarm NC 14 Common...

Page 13: ...installation of breakers ensure that circuit breakers are switched off 27 Install circuit breakers in the off position with ON letters oriented towards the top of the unit and OFF towards the bottom...

Page 14: ...and free the breaker see Figure 6 Figure 6 Removing a breaker Circuit Breakers The AC Edge 240 panel is compatible with single pole Carling Technologies M Series or AIRPAX SNAPAK series hydraulic magn...

Page 15: ...15 Transtector 2017 All Rights Reserved Dimensions...

Page 16: ...AWG YAV10 2TC14 8 AWG YA8CL 2TC14 LCD8 14A L 6 AWG YA6CL 2TC14 LCD6 14A L 4 AWG YA4CL 2TC14 LCD4 14A L 2 AWG YA2CL 2TC14 LCD2 14A Q Maintenance AC Edge 240 panels require no scheduled maintenance Ser...

Page 17: ...duct Transtector conveys no license under its patent rights or those of others Transtector reserves the right to change this product and this publication without notice Transtector Systems Inc 10701 A...

Reviews: