12
Installation (for qualified installers only)
© Travis Industries
4140811
100-01340
Gas Line Requirements
MASSACHUSETTS INSTALLATIONS - WARNING:
THIS PRODUCT MUST BE INSTALLED BY A LICENSED PLUMBER OR GAS FITTER WHEN INSTALLED WITHIN THE
COMMONWEALTH OF MASSACHUSETTS.
OTHER MASSACHUSETTS CODE REQUIREMENTS:
Flexible connector must not be longer than 36 inches.
Shutoff valve must be a “T” handle gas cock.
Only direct vent sealed combustion products are approved for bedrooms or bathrooms.
Fireplace dampers must be removed or welded in the open position prior to the installation of a fireplace insert or gas log.
A carbon monoxide (CO) detector is required in the same room as the appliance.
The gas line must be installed in accordance with all local codes, if any; if not, follow ANSI 223.1 and
the requirements listed below.
A manual shutoff valve is required within 3’ of the heater. It should be placed upstream of the flex line
(if used) and may be installed behind the access door inside the heater.
The heater and gas control valve must be disconnected from the gas supply piping during any
pressure testing of that system at test pressures in excess of 1/2 psig. For pressures under 1/2 psig,
isolate the gas supply piping by closing the manual shutoff valve.
Leak test all gas line joints and the gas control valve prior to and after starting the heater.
This heater is designed either for natural gas or for propane (but not for both). Check the sticker on
the top of the gas control valve to make sure the correct fuel is used (see illustration on page 4).
Installation must be performed by a qualified installer, service agency or the gas supplier (In
Massachusetts a licensed plumber/gas-fitter).
Gas Inlet Pressure
Standard Input Pressure
Natural Gas
7" W.C. (1.74 kPA)
Propane
13" W.C. (2.73 kPA)
If the pressure is not sufficient, make sure the piping used is large enough, the supply regulator is
adequately adjusted, and the total gas load for the residence does not exceed the amount supplied.
The supply regulator (the regulator that attaches directly to the residence inlet or to the propane tank)
should supply gas at the suggested input pressure listed above. Contact the local gas supplier if the
regulator is at an improper pressure.
Directions for Connecting a Gas Pressure Test Gauge
The gas control valve (shown to the left) has two accessible ports for testing
line pressure and output pressure. Loosen the brass screw on either test port
and place a 5/16” i.d. rubber or plastic tubing over the tapered test port.
Connect the tubing to the test gauge.
WARNING
: The brass screw must be tightened after testing to prevent gas
leakage.
Input pressure
Output pressure